50/60 Hz synchronised ±1 % With mains absent ±0.1 Hz
Max. Synchronisation Speed
±1 Hz/s
Waveform
Pure Sinewave
Total Harmonic Distortion (THDv)
<2% (Linear Load) ; <5% (Non-linear Load)
Phase Displacement
120° ±1 % (balanced load); 120° ±2% (imbalances 50% of the load)
Dynamic Recovery Time
Restore to 90% of rated value in 3 cycles
Overload capacity
110% for 10min; 150% for 60sec; >160% for 200ms
Admissible Crest Factor
3:1
Admissible Power Factor
0.6-1 (inductive or capacitive)
Imbalance Output Voltage @ 100% Unbalanced Load
<1%
Current Limit
High overload, short-circuit: RMS Voltage Limit; High Crest-Factor current: Peak Voltage Limit
STATIC BYPASS
Type
Solid state
Voltage
3 x 380VAC/400VAC (3Ph + N)
Frequency
50/60 Hz
Activation Criterion
Microprocessor control
Transfer Time
Zero
Admissible Overload
150% for 1 hour; 180% for 30sec; >200% for 200ms
Transfer to Bypass
Immediate, for overloads above 160%
Retransfer
Automatic after alarm clear
MAINTENANCE BYPASS
Type
Without interruption
Voltage
3 * 400V (3Ph + N)
Frequency
50/60 Hz
Overall Efficiency
Line Mode
90%
91%
92%
93%
Battery Mode
90%
91%
93%
93%
BATTERY & CHARGER
Battery Type and Numbers
12VDC * 32 pcs (29-32 pcs adjustable)
Nominal Battery Voltage
384 VDC (Based on 32pcs batteries)
Charging Method
CC/CV
Precision
±1%
Charging Current
Max.: 40 A
Charging Voltage
432 VDC (Based on 32pcs batteries)
PHYSICAL
Dimensions, D x W x H(mm)
656 x 405 x 817
656 x 405 x 941
840x432x1140
975x554x1286
1200x910x1680
1500x1140x1800
Net Weight (Kgs)
180
205
295
330
451
519
950
1350
Features:
Intelligent CPU control
Automatic power on when the the main power recovers
Cold start function
Power off charging function
USB/RS232/RJ-11/RJ-45 communication port (optional)
Offering LED and LCD panels for selection
Application:
Personal Computer
Printer
POS(Point of sales)Terminals
Security System
Fax Machine
Modem, WiFi Router
Technical Specifications:
Model
DP600
DP1000
DP1200
DP2000
DP3000
Capacity
600VA/360W
1000VA/600W
1200VA/720W
2000VA/1200W
3000VA/1800W
INPUT
Voltage
110/120VAA or 220/230/240VAC
Voltage Range
67-137VAC/135-275VAC
Frequency Range
50Hz Or 60Hz(Auto-Sensing)
OUTPUT
Output Voltage
110/120VAA or 220/230/240VAC
AC Voltage Regulation
± 10%
Frequency Range
(Batt. Mode)
50 HZ or 60 Hz ± 10%
Transfer Time
Typical 6-10 ms
Waveform
(Battery Mode)
Simulated Sine Wave
BATTERY
Battery Voltage
12V/7AH*1
12V/9AH*1
12V/7AH*2
12V/9AH*2
12V/7AH*4
Charge Time
8 hours up to 80-90%
PROTECTION
Full Protection
Auto Detection, discharge protection,output Short circuit, Over load, Battery low voltage protection
Communication Port
USB/RS232/RJ11/RJ45 (Optional)
Display
LED/LCD
Alarm
Battery Mode
Every 4 Seconds one beep
Low Battery Capacity
Every 1 Seconds one beep
Overload
Every 1 Seconds one beep
Fault
Keep beeping
ENVIRONMENT
Humidity
0-90% Rh @ 0-40℃ (Non-Condensing)
Noise Level
40dB
Dimension(mm)
320*90*140
330* 100*150
365*140*165
365*140*165
395*145*210
N.W.(kg)
5.2
6
10
12.6
21
Description
HIGH INTELLIGENCE AND RELIABLE POWER SUPPLYIGBT Technology
Full microprocessor control with no-break static and manual bypasses.
Online double conversion technology (VFl) with isolation transformer on theinverter output.
Extremely high short-circuit current to ensure compatibility with the most diffificult transformer applications (lighting, drives and industrial processes) and an isolation transformer on the inverter output.
Compatibled with Watch & Save 3000 software as standard and can be remotely monitored using the Power NetGuard system from anywhere in the world.
SIMPLE TO INSTALL
Capability to install the UPS into any distribution system(neutral not required on rectifier input).
Capability to separate the rectifier/bypass power networks and to power them from two separate sources, without Galvanic isolation(Necessary on UPS without an output transformer
MAXIMUM BATTERY CARE
Battery deep discharge protection;
Temperature compensating charger;
Built-in automatic and manual battery test feature.
OTHER CHARACTERISTICS
0.8/0.9 power factor suitable for powering ICT and lndustrial loads.
BACK FEED protection: to avoid energy feeding back into the mains supply cause a fault occur.
MAXIMUM RELIABILITY AND AVAILABILITY
Connect up to 6 units in parallel or N+1 redundancy, even of different power ratings.
The UPS continue to work in parallel even if one of theinterconnecting communication cables is disconnected(CLOSED LOOP)
LOW CONSUMPTION LEVELS
LF33 Series UPS can achieve efficiencies >98% thanks to selectable Economy Mode which can be used in stable electrical environments to provide power supply continuity when the mains fail.
ADVANCE COMMUNICATION:
RS485/RS232/Dry Contact/SNMP(Optional)
Specifications
Model
10KVA
20KVA
30KVA
40KVA
60KVA
80KVA
100KVA
120KVA
160KVA
200KVA
250KVA
300KVA
400KVA
500KVA
600KVA
Capacity
8KW
16 KW
24 KW
32 KW
48 KW
64 KW
80 KW
96 KW
128 KW
160 KW
200KW
240KW
320KW
400KW
480KW
INPUT
Rated voltage
400 VAC Three-Phase
Voltage range
380/400/415VAC(+25%,Can be set through the LCD panel)
Frequency range
40-70Hz(Automatically select synchronization range according to grid frequency)
Range(HZ)
50±5%(±10%) Bypass synchronization tracking
Rectifying pulse number
6 pulse rectification
6/12 pulse rectification
12 pulse rectifier
Phase system
3φ4W+PE(Three phase five wire system)
Battery voltage
384VDC
480VDC
Battery Quantity
Standard with 32 Cells(30~34, can be set through the LCD panel) Standard 40 Cells(38~42 knots,can be set by LCD panel)
OUTPUT
Power factor
0.8/0.9 (Optional)
Voltage(V)
L-N: 220±1% L-L: 380±1%
Three-phase 100% load
unbalance voltage stability
≤2%,Allow 100% imbalance
Frequency(HZ)
Normal power, tracking the frequency of power, Grid abnormal. 50±0.2%
Transfer time(ms)
0ms
Parallel operation mode
(parallel type)
Max 8 Parallel
Waveform distortion
Linear loadTHD<3% ; Nonlinear loadTHD<5%
Overload capacity
125% full load for 10 minutes, maintain 150 % full load for 1 minute and then switch to bypass power supply,
after reducing the loadcan automatically restore the inverter
Crest factor
3:1
Others
Index
Standard with no transfer time maintenance bypass switch
Communication function
RS232/RS485/Dry Contact/SNMP (Optional)
Panel display
LED displays working status and fault indication; LCD displays three-phase input voltage,
input frequency, three-phase output voltage, load,battery voltage, battery charge and discharge current, etc
Display
7″ Touchable LCD screen display
The audio noise(dB)
<65(within 1 meter)
Alarm function
Battery low voltage, abnormal power supply, overload, UPS failure, over temperature protection
Protection
Input over voltage, battery under voltage, overload, short circuit, over temperature protection
Cooling way
Forced cooling
Operating temperature
0℃ to ~ 40℃
Humidity
0~95%, non-condensing
electromagnetic compatibility
Conform GB7260.2
Size(W*D*H)(mm)
540*660*1135
1100*800*1800
800*800*1900
1200*850*1900
2600*1100*2000
Weight
196
233
276
329
461
547.5
643
754
1375
Features:
Valve sealed design, no free electrolyte, Maintenance -free
Designed floating service life:15 years @ 25 °C/68 °F.
Wide operating temperature range from -15°C to 35°C
Nanometer gel electrolytes eliminate the acid stratification and prolong cycle life
Low self-discharge rate: ≤3%/month.
Application
UPS Systems
Portable Equipment
Renewable Energy Systems
Electric Utilities
Outdoor control Equipment
Railroad Utilities
Telecom Systems
Technical Specifications
Model
Nominal Voltage
Capacity
Dimension LXWXH (mm)
Total Height
(mm)
Weight (KG/IBS)
Terminal
VG12-33
12V
33AH
195
130
167
167
10
22.05
M6
VG12-35
12V
35AH
195
130
167
167
11.5
25.35
M6
VG12-38
12V
38AH
197
165
172
172
12.5
27.56
M6
VG12-40
12V
40AH
197
165
172
172
13.2
29.1
M6
VG12-45
12V
45AH
197
165
172
172
15
33.07
M6
VG12-50
12V
50AH
229
138
205
208
15.5
34.17
M6
VG12-55
12V
55AH
229
138
205
208
16.5
36.38
M6
VG12-65
12V
65AH
350
166
175
175
21
46.3
M8
VG12-70
12V
70AH
260
168
208
211
21.8
48.06
M8
VG12-80
12V
80AH
260
168
208
211
24
52.91
M8
VG12-90
12V
90AH
330
171
216
219
27
59.52
M8
VG12-100
12V
100AH
330
171
216
219
29.5
65.04
M8
VG12-120
12V
120AH
407
173
237
237
35
77.16
M8
VG12-150
12V
150AH
484
170
241
241
45
99.21
M8
VG12-200
12V
200AH
522
240
219
222
61.5
135.58
M8
VG12-250
12V
250AH
520
268
220
223
71
156.53
M8
Features:
60KW single power module in 3U
N+1or N+X parallel redundancy for power guarantee
Supports horizontal expansion by 1+1 cabinet paralleloperation.
Hot-swappable modular design decreases MTTR
High scalability
Built-in maintenance bypass switch for easy maintenance without interruptible
High efficiency double conversion online UPS
Flexible battery configuration and adjustable charging current
1 hour for ≤110%,10 mins for 111%~125%,1 min for 126%~150% and 200ms for >150%
Haronic Distortion
≤2% THD (Linear Load); ≤4% THD (Non-linear Load)
Eficiency
96%
BATTERY / CHARGER
Nominal Voltage
’+/- 192V~+/- 240V(Selectable)
Maximum Voltage
’+/- 240V (12V×40 PCS)
Minimum Voltage
‘+/-192V (12V×32 PCS)
Floating Charge Voltage
2.28V/Cell (2.25~2.33 Selectable)
Boost Charging Voltage
2.35V/Cell
Temperature Compensation
Yes
Maximum Charging Current
(Per Power Module)
18A(Adjustable)
PHYSICAL
Cabinet Dimension (DxWxH)mm
1100x600x1475
1100x600x1475
1100x600x2010
1100×600×2010
1065x1000x2000
1065×1000×2000
Net Weight (Kg)
308
352
516
654
932
1020
Power Module (PM-60) Net Weight
44KGS
ENVIRONMENT
Operating Temperature
0~40℃
Relative Humidity
0~95% non-condensing
Altitude*
<1000m for Nominal power
IP Protection
IP 20
MANAGEMENT
Smart RS-232/USB
Supports Windows⑧ Family, Linux and MAC
Optional SNMP
Power management from SNMP manager and web browser
STANDARDS
Safety
IEC/EN62040-1
EMC
IEC/EN 62040-2 Category C3
Features:
One of the most popular rechargeable battery generators in the market. It comes with AC outlets,DC car port,three Quick Charge USB ports,one Type-C port and built-in fast charging wireless charger.
Reviews
There are no reviews yet.