The battery cabinet is made of metal material, strong and can bear up to 500KG.
The battery cabinet is assembled in the form of assembly, which is conven-ient for transportation and simple for assembly.
The surface of electrostatic spraying, strong rust resistance, color can be fixed spray.
Other sizes can be customized.
Delivery & Availability:Typically 10-21 working days – excluding furniture and heavy/bulky equipment. Please contact us for further information.
Shipped From Abroad
Features:
Optional 7 ” touch LCD
Online double-conversionDSP technology guarantees high reliability
True galvanic isolation transformer designControl designed to withstand all kinds of loads
Intelligent battery management to prolong battery lifecycle
Redundant fan design and independent ventilation enhance durable operation under harsh environment
Adiustable battery numbers
Accept dual-mains input
Parallel operation with up to 4 units ( option )
Variety of communication options available
Reverse phase frequency operation and supportsnon-neutral input
Delivery & Availability:Typically 10-21 working days – excluding furniture and heavy/bulky equipment. Please contact us for further information.
Shipped From Abroad
Delivery & Availability:Typically 10-21 working days – excluding furniture and heavy/bulky equipment. Please contact us for further information.
Shipped From Abroad
Delivery & Availability:Typically 10-21 working days – excluding furniture and heavy/bulky equipment. Please contact us for further information.
Shipped From Abroad
Features:
True Double conversion Technology
DSP digital control technology enable UPS more stable performance.
Three Level inverter control technology
Large screen LCD display
N+X Parallel Redundancy function (3 units parallel)
EPO emergency stop function
Smart expansion Slots (optional)
Support Generator
Delivery & Availability:Typically 10-21 working days – excluding furniture and heavy/bulky equipment. Please contact us for further information.
Content
Features:
The battery cabinet is made of metal material, strong and can bear up to 500KG.
The battery cabinet is assembled in the form of assembly, which is conven-ient for transportation and simple for assembly.
The surface of electrostatic spraying, strong rust resistance, color can be fixed spray.
Other sizes can be customized.
Technical Specifications
Model
Dimensions(W*D*H) (mm)
Battery Capacity
Battery Numbers
Weight(kg)
B-1B
280x190x220
24AH/17AH
2/3PCS
2.2
B-1
435x210x270
17AH/24AH/38AH
5/3/2 PCS
3.3
65AH/100AH
1PC
B-1A
540x210x230
17AH/24AH/38AH
6/4/3PCS
4.5
B-2
450x470x320
17AH/24AH/38AH
10/6/4 PCS
7
65AH/100AH
2PCS
B-3
585x470x320
17AH/24AH/38AH
14/8/6PCS
9
65AH/100AH
3PCS
B-4
450x470x615
17AH/24AH/38AH
20/12/8PCS
15
65AH/100AH
4PCS
B-6
585x470x615
17AH/24AH/38AH
28/16/12PCS
18
65AH/100AH
6PCS
B-8
780x470x615
17AH/24AH/38AH
44/28/20PCS
21
65AH/100AH
8PCS
B-10
950x470x615
17AH/24AH/38AH
44/28/20PCS
24
65AH/100AH
10PCS
B-12
780x470x910
24AH/38AH
30/24PCS
32
65AH/100AH
12PCS
B-16
780x470x1190
24AH/38AH
40/32PCS
45
65AH/100AH
16PCS
B-20
950x470x1190
24AH/38AH
56/40PCS
50
65AH/100AH
20PCS
B-24
1150x470x1190
65AH/100AH
24PCS
57
B-32
780x880x1190
65AH/100AH
32PCS
95
B-40
950x880x1190
65AH/100AH
40PCS
100
Features:
Three Phase Hybrid Solar Inverter
Off grid three phase solar hybrid inverter with pwm/mppt can be used in single-phase and three-phase ac load with total power not exceeding 100kva/120kva/125kva/150kva/160kva,384vdc to 380vac.
•Pure sine wave output.
•Low DC voltage, saving system cost.
•Three phase solar inverter with built-in PWM or MPPT charge controller.
•AC charge current 0-45A adjustable.
•Wide LCD screen, clearly and precisely shows icon data.
•100%imbalance loading design, 3 times peak power.
•Setting different working modes based on variable usage requirements.
•DC first/AC first optional.
•Various communication ports and remote controls
50/60 Hz synchronised ±1 % With mains absent ±0.1 Hz
Max. Synchronisation Speed
±1 Hz/s
Waveform
Pure Sinewave
Total Harmonic Distortion (THDv)
<2% (Linear Load) ; <5% (Non-linear Load)
Phase Displacement
120° ±1 % (balanced load); 120° ±2% (imbalances 50% of the load)
Dynamic Recovery Time
Restore to 90% of rated value in 3 cycles
Overload capacity
110% for 10min; 150% for 60sec; >160% for 200ms
Admissible Crest Factor
3:1
Admissible Power Factor
0.6-1 (inductive or capacitive)
Imbalance Output Voltage @ 100% Unbalanced Load
<1%
Current Limit
High overload, short-circuit: RMS Voltage Limit; High Crest-Factor current: Peak Voltage Limit
STATIC BYPASS
Type
Solid state
Voltage
3 x 380VAC/400VAC (3Ph + N)
Frequency
50/60 Hz
Activation Criterion
Microprocessor control
Transfer Time
Zero
Admissible Overload
150% for 1 hour; 180% for 30sec; >200% for 200ms
Transfer to Bypass
Immediate, for overloads above 160%
Retransfer
Automatic after alarm clear
MAINTENANCE BYPASS
Type
Without interruption
Voltage
3 * 400V (3Ph + N)
Frequency
50/60 Hz
Overall Efficiency
Line Mode
90%
91%
92%
93%
Battery Mode
90%
91%
93%
93%
BATTERY & CHARGER
Battery Type and Numbers
12VDC * 32 pcs (29-32 pcs adjustable)
Nominal Battery Voltage
384 VDC (Based on 32pcs batteries)
Charging Method
CC/CV
Precision
±1%
Charging Current
Max.: 40 A
Charging Voltage
432 VDC (Based on 32pcs batteries)
PHYSICAL
Dimensions, D x W x H(mm)
656 x 405 x 817
656 x 405 x 941
840x432x1140
975x554x1286
1200x910x1680
1500x1140x1800
Net Weight (Kgs)
180
205
295
330
451
519
950
1350
Description
HIGH INTELLIGENCE AND RELIABLE POWER SUPPLYIGBT Technology
Full microprocessor control with no-break static and manual bypasses.
Online double conversion technology (VFl) with isolation transformer on theinverter output.
Extremely high short-circuit current to ensure compatibility with the most diffificult transformer applications (lighting, drives and industrial processes) and an isolation transformer on the inverter output.
Compatibled with Watch & Save 3000 software as standard and can be remotely monitored using the Power NetGuard system from anywhere in the world.
SIMPLE TO INSTALL
Capability to install the UPS into any distribution system(neutral not required on rectifier input).
Capability to separate the rectifier/bypass power networks and to power them from two separate sources, without Galvanic isolation(Necessary on UPS without an output transformer
MAXIMUM BATTERY CARE
Battery deep discharge protection;
Temperature compensating charger;
Built-in automatic and manual battery test feature.
OTHER CHARACTERISTICS
0.8/0.9 power factor suitable for powering ICT and lndustrial loads.
BACK FEED protection: to avoid energy feeding back into the mains supply cause a fault occur.
MAXIMUM RELIABILITY AND AVAILABILITY
Connect up to 6 units in parallel or N+1 redundancy, even of different power ratings.
The UPS continue to work in parallel even if one of theinterconnecting communication cables is disconnected(CLOSED LOOP)
LOW CONSUMPTION LEVELS
LF33 Series UPS can achieve efficiencies >98% thanks to selectable Economy Mode which can be used in stable electrical environments to provide power supply continuity when the mains fail.
ADVANCE COMMUNICATION:
RS485/RS232/Dry Contact/SNMP(Optional)
Specifications
Model
10KVA
20KVA
30KVA
40KVA
60KVA
80KVA
100KVA
120KVA
160KVA
200KVA
250KVA
300KVA
400KVA
500KVA
600KVA
Capacity
8KW
16 KW
24 KW
32 KW
48 KW
64 KW
80 KW
96 KW
128 KW
160 KW
200KW
240KW
320KW
400KW
480KW
INPUT
Rated voltage
400 VAC Three-Phase
Voltage range
380/400/415VAC(+25%,Can be set through the LCD panel)
Frequency range
40-70Hz(Automatically select synchronization range according to grid frequency)
Range(HZ)
50±5%(±10%) Bypass synchronization tracking
Rectifying pulse number
6 pulse rectification
6/12 pulse rectification
12 pulse rectifier
Phase system
3φ4W+PE(Three phase five wire system)
Battery voltage
384VDC
480VDC
Battery Quantity
Standard with 32 Cells(30~34, can be set through the LCD panel) Standard 40 Cells(38~42 knots,can be set by LCD panel)
OUTPUT
Power factor
0.8/0.9 (Optional)
Voltage(V)
L-N: 220±1% L-L: 380±1%
Three-phase 100% load
unbalance voltage stability
≤2%,Allow 100% imbalance
Frequency(HZ)
Normal power, tracking the frequency of power, Grid abnormal. 50±0.2%
Transfer time(ms)
0ms
Parallel operation mode
(parallel type)
Max 8 Parallel
Waveform distortion
Linear loadTHD<3% ; Nonlinear loadTHD<5%
Overload capacity
125% full load for 10 minutes, maintain 150 % full load for 1 minute and then switch to bypass power supply,
after reducing the loadcan automatically restore the inverter
Crest factor
3:1
Others
Index
Standard with no transfer time maintenance bypass switch
Communication function
RS232/RS485/Dry Contact/SNMP (Optional)
Panel display
LED displays working status and fault indication; LCD displays three-phase input voltage,
input frequency, three-phase output voltage, load,battery voltage, battery charge and discharge current, etc
Display
7″ Touchable LCD screen display
The audio noise(dB)
<65(within 1 meter)
Alarm function
Battery low voltage, abnormal power supply, overload, UPS failure, over temperature protection
Protection
Input over voltage, battery under voltage, overload, short circuit, over temperature protection
Cooling way
Forced cooling
Operating temperature
0℃ to ~ 40℃
Humidity
0~95%, non-condensing
electromagnetic compatibility
Conform GB7260.2
Size(W*D*H)(mm)
540*660*1135
1100*800*1800
800*800*1900
1200*850*1900
2600*1100*2000
Weight
196
233
276
329
461
547.5
643
754
1375
Features:
Digital Control
All parts of this series of UPS adopt digital control, each performance index of UPS is very excellent, and the control system is morestableand reliable.Each module has built-in
automatic bypass switch and corresponding bypass current equalizing inductor, providing good bypass power supply equalization performance.
Intelligent Battery Management
Users can set the charging current, constant current, constant voltage and floatingcharging modescan be automatically and smoothly switched; Battery voltage can beset
±192Vdc/±240Vdc/±216Vdc/±228Vdc/±240Vdc (32/34/36/38/40 pcs optional)
High Power Density Modular Design
The capacity of each single module is30kVA, and the height is3U; UPS modulescan be added and removed onlineto achieve zero maintenance time.
N+x Parallel Redundancy
The quantity of redundant module can be set accordingly, When the redundant module reaches more than 2 hours, the system availability achieves 99.99%,
MTBF(Mean Time Between Failures) lasts more than 250,000 hours; Supporting parallel connection between cabinets.
A maximum of four cabinets can be parallel,and battery pack can be shared when UPS cabinet in parallel.
Touchable LCD Display Screen
Super large LCD display with touching function.
Standard Cabinet Design
The appearance ofthe standard cabinet is beautiful and generous, which can perfectly match the use environment ofthe computer room and save the space.
Safe and Easy to Maintain
When an emergency occurs, users can switch to the maintenance bypass to supply power, and maintenance personnel can safely perform online maintenance;
Press EPO button to shutdown in emergentsituation, and also have REPO function.
Intelligent Management
Centralized monitoring module (with hot-swap function), RS232/RS485 communication interface/SNMPcard (optional), can realize remote monitoringof UPS, relay card is optional.