1 hour for ≤110%,10 mins for 111%~125%,1 min for 126%~150% and 200ms for >150%
Haronic Distortion
≤2% THD (Linear Load); ≤4% THD (Non-linear Load)
Eficiency
96%
BATTERY / CHARGER
Nominal Voltage
’+/- 192V~+/- 240V(Selectable)
Maximum Voltage
’+/- 240V (12V×40 PCS)
Minimum Voltage
‘+/-192V (12V×32 PCS)
Floating Charge Voltage
2.28V/Cell (2.25~2.33 Selectable)
Boost Charging Voltage
2.35V/Cell
Temperature Compensation
Yes
Maximum Charging Current
(Per Power Module)
18A(Adjustable)
PHYSICAL
Cabinet Dimension (DxWxH)mm
1100x600x1475
1100x600x1475
1100x600x2010
1100×600×2010
1065x1000x2000
1065×1000×2000
Net Weight (Kg)
308
352
516
654
932
1020
Power Module (PM-60) Net Weight
44KGS
ENVIRONMENT
Operating Temperature
0~40℃
Relative Humidity
0~95% non-condensing
Altitude*
<1000m for Nominal power
IP Protection
IP 20
MANAGEMENT
Smart RS-232/USB
Supports Windows⑧ Family, Linux and MAC
Optional SNMP
Power management from SNMP manager and web browser
STANDARDS
Safety
IEC/EN62040-1
EMC
IEC/EN 62040-2 Category C3
Features:
Rated Power: 500W
Rated Capacity: 519 . 48wh
Standard Capacity: 3.7V/140400mah
Overload Protecion: 550W + 40W
AC Output: AC 110V+10%/60HZ 230V+10%/50HZ
Output Wave: Pure sine wave
USB Output: QC 18W*2
Type-c Output: PD 60W*2
Cigarret Lighter Output: 14V/8A
DC5525 Output: 14V/8A
Wireless Charging: 15W
Charging Input: 12-26 V/100W Max
WorkingTemperature: -10-40 °C
Weight(Net Weight): 6.8kg
Weight(With Accessories): 8.5kg
Dimension: 345*227*203mm
Applications:
Mammogram
Ultrasound Equipments
Radiology rooms
Description
HIGH INTELLIGENCE AND RELIABLE POWER SUPPLYIGBT Technology
Full microprocessor control with no-break static and manual bypasses.
Online double conversion technology (VFl) with isolation transformer on theinverter output.
Extremely high short-circuit current to ensure compatibility with the most diffificult transformer applications (lighting, drives and industrial processes) and an isolation transformer on the inverter output.
Compatibled with Watch & Save 3000 software as standard and can be remotely monitored using the Power NetGuard system from anywhere in the world.
SIMPLE TO INSTALL
Capability to install the UPS into any distribution system(neutral not required on rectifier input).
Capability to separate the rectifier/bypass power networks and to power them from two separate sources, without Galvanic isolation(Necessary on UPS without an output transformer
MAXIMUM BATTERY CARE
Battery deep discharge protection;
Temperature compensating charger;
Built-in automatic and manual battery test feature.
OTHER CHARACTERISTICS
0.8/0.9 power factor suitable for powering ICT and lndustrial loads.
BACK FEED protection: to avoid energy feeding back into the mains supply cause a fault occur.
MAXIMUM RELIABILITY AND AVAILABILITY
Connect up to 6 units in parallel or N+1 redundancy, even of different power ratings.
The UPS continue to work in parallel even if one of theinterconnecting communication cables is disconnected(CLOSED LOOP)
LOW CONSUMPTION LEVELS
LF31 Series UPS can achieve efficiencies >98% thanks to selectable Economy Mode which can be used in stable electrical environments to provide power supply continuity when the mains fail.
ADVANCE COMMUNICATION:
RS485/RS232/Dry Contact/SNMP(Optional)
Specifications
Model
10KVA
15KVA
20KVA
30KVA
40KVA
60KVA
80KVA
100KVA
Capacity
8KW
12 KW
16 KW
24 KW
32 KW
48 KW
64 KW
80 KW
INPUT
Rated voltage
380/400/415 VAC Three-phase
Voltage range
±20%
Frequency range
45-65Hz
Power factor
>0.92 with harmonic filter
Current harmonic distortion
<5% with harmonic filter
Soft Start
0 -100% in 10″
BYPASS INPUT
Rated voltage
230VAC Single Phase
Permitted voltage range
±15% (selectable from ±10% to ±25% from front panel)
Reviews