High Frequency Modular UPS RM Plus Series 300 KW-500KW

$0.00

Shipped From Abroad

Features:
  • 50KW single power module in 3U
  • N+1or N+X parallel redundancy for power guarantee
  • Supports horizontal expansion by 1+1 cabinet paralleloperation.
  • Hot-swappable modular design decreases MTTR
  • High scalability
  • Built-in maintenance bypass switch for easy maintenance without interruptible
  • High efficiency double conversion online UPS
  • Flexible battery configuration and adjustable charging current
  • High overload capability
  • Power walk-in function
  • Built-in dynamic password protection
  • Built-in ultra communication slot
Delivery & Availability:
Typically 10-21 working days – excluding furniture and heavy/bulky equipment. Please contact us for further information.
SF1033560130139-8
Brands:: Reeco Power

Description

Features:
  • 50KW single power module in 3U
  • N+1or N+X parallel redundancy for power guarantee
  • Supports horizontal expansion by 1+1 cabinet paralleloperation.
  • Hot-swappable modular design decreases MTTR
  • High scalability
  • Built-in maintenance bypass switch for easy maintenance without interruptible
  • High efficiency double conversion online UPS
  • Flexible battery configuration and adjustable charging current
  • High overload capability
  • Power walk-in function
  • Built-in dynamic password protection
  • Built-in ultra communication slot

 

Specifications:
MODEL RM Plus 300K RM Plus 350K RM Plus 400K RM Plus 500K
Phase 3 Phase in / 3 Phase out
Cabinet Capacity* 300 KW 350 KW 400KW 500KW
Battery  Type Extemal Battery
One Power Module Capacity 50KVA/50KW
Max.   Power Module  No. 6 7 8 10
INPUT
Nominal Voltage 3×380/400/415 VAC (3Ph+N)
Voltage Range ’-20%~+15%
Nominal Frequency 50/60Hz(Auto Sensing)
Frequency Range 40Hz~70Hz
Power Factor >0.99  @100%  Load, >0.98@50%  Load
Harmonic  Distortion   (THDi) <4% @ 100%  load
OUTPUT
Nominal Voltage 3×380/400/415 VAC (3Ph+N)
Voltage  Regulation(Steady  State) ≤ ±1% Typical (balanced load); ~≤ ±2% Typical (unbalanced load)
Nominal Frequency 50/60Hz
Frequency Range(Synchronized) 46Hz~54Hz or 56Hz~64Hz
Overload Capability 1 hour for ≤110%,10 mins for 111%~125%,1 min for 126%~150% and 200ms for >150%
Haronic Distortion ≤2% THD (Linear Load); ≤4% THD (Non-linear Load)
Eficiency 95.50%
BATTERY / CHARGER
Nominal Voltage ‘+/- 192V~+/- 240V (Selectable)
Maximum Voltage ’+/- 240V (12V×40PCS)
Minimum Voltage ‘+/- 192V(12V×32PCS)
Floating Charge Voltage 2.28V/Cell (2.25~2.33 Selectable)
Boost Charging Voltage 2.35V/Cell
Temperature Compensation Yes
Maximum Charging Current
(Per Power Module)
12A (Adjustable)
PHYSICAL
Cabinet Dimension (DxWxH)mm 1065x600x2000 1065x600x2000 1065x1000x2000 1065x1000x2000
Net Weight (Kg) 545 654 932 1020
Power Module (PM-50) Net Weight 44KGS
ENVIRONMENT
Operating Temperature 0~40℃
Relative Humidity 0~95% non-condensing
Altitude* <1000m for Nominal power
IP  Protection IP 20
MANAGEMENT
Smart  RS-232/USB Supports Windows⑧ Family, Linux and MAC
Optional SNMP Power management from SNMP manager and web browser
STANDARDS
Safety IEC/EN 62040-1
EMC IEC/EN 62040-2 Category C3

Reviews

There are no reviews yet.

Be the first to review “High Frequency Modular UPS RM Plus Series 300 KW-500KW”

Your email address will not be published. Required fields are marked *

Quick Comparison

SettingsHigh Frequency Modular UPS RM Plus Series 300 KW-500KW removeSingle Phase High Frequency Online UPS VT Series 1KVA-3KVA remove3 Phase Low Frequency Online UPS LD31 Series removeBattery Cabinet battery Rack B1-B40 (Support Customized Size) removeSingle Phase High Frequency Online UPS VT Series 6KVA-20KVA remove3 Phase Low Frequency Solar Inverter DX Series remove
NameHigh Frequency Modular UPS RM Plus Series 300 KW-500KW removeSingle Phase High Frequency Online UPS VT Series 1KVA-3KVA remove3 Phase Low Frequency Online UPS LD31 Series removeBattery Cabinet battery Rack B1-B40 (Support Customized Size) removeSingle Phase High Frequency Online UPS VT Series 6KVA-20KVA remove3 Phase Low Frequency Solar Inverter DX Series remove
Image
SKUSF1033560130139-8SF1033560130139-25SF1033560130139-2SF1033560130139-9SF1033560130139-26SF1033560130139-5
Rating
Price

$0.00

$0.00

$0.00

$0.00

$0.00

$0.00

Stock
Availability
Add to cart

DescriptionShipped From Abroad
Features:
  • 50KW single power module in 3U
  • N+1or N+X parallel redundancy for power guarantee
  • Supports horizontal expansion by 1+1 cabinet paralleloperation.
  • Hot-swappable modular design decreases MTTR
  • High scalability
  • Built-in maintenance bypass switch for easy maintenance without interruptible
  • High efficiency double conversion online UPS
  • Flexible battery configuration and adjustable charging current
  • High overload capability
  • Power walk-in function
  • Built-in dynamic password protection
  • Built-in ultra communication slot
Delivery & Availability: Typically 10-21 working days – excluding furniture and heavy/bulky equipment. Please contact us for further information.
Shipped From Abroad
Features:
  • True Double conversion Technology
  • DSP digital control technology enable UPS more stable performance.
  • Three-level inverter technology
  • Active High input power factor correction technology (PFC)
  • Wide Input Voltage Frequency Range& Strong load capacity
  • Zero power switch delay
  • Compatible with Generators
  • Wide input voltage and frequency range can effectively isolate the harmful waves into power by the generator and provide pure,safe and stable power supply.
  • Support intelligent monitoring
  • Fully support remote intelligent monitoring with flexibility in choice of USB cards . AS400 cards , SNMP cards , RS485 cards
Delivery & Availability: Typically 10-21 working days – excluding furniture and heavy/bulky equipment. Please contact us for further information.
Shipped From Abroad
Delivery & Availability: Typically 10-21 working days – excluding furniture and heavy/bulky equipment. Please contact us for further information.
Shipped From Abroad
Features:
  • The battery cabinet is made of metal material, strong and can bear up to 500KG.
  • The battery cabinet is assembled in the form of assembly, which is conven-ient for transportation and simple for assembly.
  • The surface of electrostatic spraying, strong rust resistance, color can be fixed spray.
  • Other sizes can be customized.
Delivery & Availability: Typically 10-21 working days – excluding furniture and heavy/bulky equipment. Please contact us for further information.
Shipped From Abroad
Features:
  • True Double conversion Technology
  • DSP digital control technology enable UPS more stable performance.
  • Three Level inverter control technology
  • Large screen LCD display
  • N+X Parallel Redundancy function (3 units parallel)
  • EPO emergency stop function
  • Smart expansion Slots (optional)
  • Support Generator
Delivery & Availability: Typically 10-21 working days – excluding furniture and heavy/bulky equipment. Please contact us for further information.
Content
Features:
  • 50KW single power module in 3U
  • N+1or N+X parallel redundancy for power guarantee
  • Supports horizontal expansion by 1+1 cabinet paralleloperation.
  • Hot-swappable modular design decreases MTTR
  • High scalability
  • Built-in maintenance bypass switch for easy maintenance without interruptible
  • High efficiency double conversion online UPS
  • Flexible battery configuration and adjustable charging current
  • High overload capability
  • Power walk-in function
  • Built-in dynamic password protection
  • Built-in ultra communication slot
 
Specifications:
MODEL RM Plus 300K RM Plus 350K RM Plus 400K RM Plus 500K
Phase 3 Phase in / 3 Phase out
Cabinet Capacity* 300 KW 350 KW 400KW 500KW
Battery  Type Extemal Battery
One Power Module Capacity 50KVA/50KW
Max.   Power Module  No. 6 7 8 10
INPUT
Nominal Voltage 3×380/400/415 VAC (3Ph+N)
Voltage Range ’-20%~+15%
Nominal Frequency 50/60Hz(Auto Sensing)
Frequency Range 40Hz~70Hz
Power Factor >0.99  @100%  Load, >0.98@50%  Load
Harmonic  Distortion   (THDi) <4% @ 100%  load
OUTPUT
Nominal Voltage 3×380/400/415 VAC (3Ph+N)
Voltage  Regulation(Steady  State) ≤ ±1% Typical (balanced load); ~≤ ±2% Typical (unbalanced load)
Nominal Frequency 50/60Hz
Frequency Range(Synchronized) 46Hz~54Hz or 56Hz~64Hz
Overload Capability 1 hour for ≤110%,10 mins for 111%~125%,1 min for 126%~150% and 200ms for >150%
Haronic Distortion ≤2% THD (Linear Load); ≤4% THD (Non-linear Load)
Eficiency 95.50%
BATTERY / CHARGER
Nominal Voltage ‘+/- 192V~+/- 240V (Selectable)
Maximum Voltage ’+/- 240V (12V×40PCS)
Minimum Voltage ‘+/- 192V(12V×32PCS)
Floating Charge Voltage 2.28V/Cell (2.25~2.33 Selectable)
Boost Charging Voltage 2.35V/Cell
Temperature Compensation Yes
Maximum Charging Current (Per Power Module) 12A (Adjustable)
PHYSICAL
Cabinet Dimension (DxWxH)mm 1065x600x2000 1065x600x2000 1065x1000x2000 1065x1000x2000
Net Weight (Kg) 545 654 932 1020
Power Module (PM-50) Net Weight 44KGS
ENVIRONMENT
Operating Temperature 0~40℃
Relative Humidity 0~95% non-condensing
Altitude* <1000m for Nominal power
IP  Protection IP 20
MANAGEMENT
Smart  RS-232/USB Supports Windows⑧ Family, Linux and MAC
Optional SNMP Power management from SNMP manager and web browser
STANDARDS
Safety IEC/EN 62040-1
EMC IEC/EN 62040-2 Category C3
Features:
  • True Double conversion Technology
  • DSP digital control technology enable UPS more stable performance.
  • Three-level inverter technology
  • Active High input power factor correction technology (PFC)
  • Wide Input Voltage Frequency Range& Strong load capacity
  • Zero power switch delay
  • Compatible with Generators
  • Wide input voltage and frequency range can effectively isolate the harmful waves into power by the generator and provide pure,safe and stable power supply.
  • Support intelligent monitoring
  • Fully support remote intelligent monitoring with flexibility in choice of USB cards . AS400 cards , SNMP cards , RS485 cards
Applications:
  • Mammogram
  • Ultrasound Equipments
  • Radiology rooms
 
Technical Specifications
Model VT1K VT1KL VT2K VT2KL VT3K VT3KL
Rated power 1KVA/900KW 2KVA/1.8KW 3KVA/2.7KW
Input Voltage range 90~285Vac L+N+G
Frequency range 40-70Hz(Adjustable)
Input power factor >0.99
Output Rated voltage and precision 220Vac (1±2% ) L+N+G
Output frequency 46-54Hz Synchronous mains power; 50Hz( Frequency Range 40-46Hz ~54-60Hz);50Hz(Battery mode)
Rated Current 4.5A 9.1A 13.6A
Output power factor 0.9
Output harmonic ≤4%
Crest factor 3:1
Inverter overload capacity 105%±5%< Load<125%±5% : 50s transfer to bypass 125% ±5% < Load<150 % ±5 % : 25s transfer to bypass Load > 150 % ± 5 %: 300s transfer to bypass
Transfer time 0ms
Efficiency ≥85%
Battery Rated voltage 24Vdc 36Vdc 48Vdc 72Vdc 72Vdc 96Vdc
Battery Numbers 2 3 4 6 6 8
Charge current 1A 6.5A 1A 5.5A 1A 5.5A
Size(LXWXH)mm 350*144*230 425*190*328
Net Weight(KG) 9.5kg 6kg 18.5kg 10kg 23.5kg 11kg
Operating temperature 0°C 〜40°C
Operating humidity 20% 〜95%
Noise ≤50dB
Description
HIGH INTELLIGENCE AND RELIABLE POWER SUPPLY IGBT Technology Full microprocessor control with no-break static and manual bypasses. Online double conversion technology (VFl) with isolation transformer on theinverter output. Extremely high short-circuit current to ensure compatibility with the most diffificult transformer applications (lighting, drives and industrial processes) and an isolation transformer on the inverter output. Compatibled with Watch & Save 3000 software as standard and can be remotely monitored using the Power NetGuard system from anywhere in the world. SIMPLE TO INSTALL Capability to install the UPS into any distribution system(neutral not required on rectifier input). Capability to separate the rectifier/bypass power networks and to power them from two separate sources, without Galvanic isolation(Necessary on UPS without an output transformer MAXIMUM BATTERY CARE Battery deep discharge protection; Temperature compensating charger; Built-in automatic and manual battery test feature. OTHER CHARACTERISTICS 0.8/0.9 power factor suitable for powering ICT and lndustrial loads. BACK FEED protection: to avoid energy feeding back into the mains supply cause a fault occur. MAXIMUM RELIABILITY AND AVAILABILITY Connect up to 6 units in parallel or N+1 redundancy, even of different power ratings. The UPS continue to work in parallel even if one of theinterconnecting communication cables is disconnected(CLOSED LOOP) LOW CONSUMPTION LEVELS LF31 Series UPS can achieve efficiencies >98% thanks to selectable Economy Mode which can be used in stable electrical environments to provide power supply continuity when the mains fail. ADVANCE COMMUNICATION: RS485/RS232/Dry Contact/SNMP(Optional)  
Specifications
Model 10KVA 15KVA 20KVA 30KVA 40KVA 60KVA    80KVA 100KVA
Capacity 8KW 12 KW 16 KW 24 KW 32 KW 48 KW    64 KW    80 KW
INPUT
Rated voltage 380/400/415 VAC  Three-phase
Voltage range ±20%
Frequency range 45-65Hz
Power factor >0.92 with harmonic filter
Current harmonic distortion <5% with harmonic filter
Soft Start 0 -100% in 10″
BYPASS INPUT
Rated voltage 230VAC   Single Phase
Permitted voltage range ±15%  (selectable from ±10% to ±25% from front panel)
Rated frequency 50/60Hz
Permitted frequency range ±2%    (selectable from ±1% to ±5% from front panel)
Standard features Back Feed portection; split bypass line
BATTERY
Type VRLA AGM / GEL;NICd
Battery Voltage 384VDC
Maximum recharge current(A) 0.2 X C10
AC ripple voltage <1%
INVERTER OUTPUT
Rated power(kVA) 10KVA 15KVA 20KVA 30KVA 40KVA 60KVA     80KVA 100KVA
Active power(kW)  8KW 12 KW 16 KW 24 KW 32 KW 48 KW     64 KW 80 KW
Number of phases 1
Rated voltage(V) 230VAC  Single Phase
Regulation of the output voltage 220 ~ 244VAC  phase/neutral (from control panel)
Crest factor(Ipeak/Irms) 3:1
Static stability ±1%
Dynamic stability ±5%
Frequency 50/60Hz configurable
Overload 110% 125% 150% of the rated current for 5h/10’/1′
Frequency stability ±0.05% on mains failure
System 10KVA 15KVA 20KVA 30KVA 40KVA 60KVA     80KVA 100KVA
Remote signaling Volt free contacts
Remote controls EPO and Bypass
Communication RS232 + Romote Contacts
Operation temperature 0℃ to  ~ 40℃
Relative humidity <95% non condensing
Colour Light grey ( RAL 7035)
Noise 54dBA at 1m 60dBA at 1m   65dBA at 1m
Protection degree IP20
Efficiency Smart Mode Up to 98%
Compliance Safety:EN 62040-1-1(Directive 2006/95/EC); EMC:6200-2(Directive 2004/108/EC)
Weight(KG)N.W 176 220 205 213 295 440 520 770
Dimensions:(WxDxH)mm 555*730*1210 800*730*1400 1115*730*1400
Internal batteries optional optional optional No      No No No No
Features:
  • The battery cabinet is made of metal material, strong and can bear up to 500KG.
  • The battery cabinet is assembled in the form of assembly, which is conven-ient for transportation and simple for assembly.
  • The surface of electrostatic spraying, strong rust resistance, color can be fixed spray.
  • Other sizes can be customized.
 
Technical Specifications
Model Dimensions(W*D*H) (mm) Battery Capacity Battery Numbers Weight(kg)
B-1B 280x190x220 24AH/17AH 2/3PCS 2.2
B-1 435x210x270 17AH/24AH/38AH 5/3/2 PCS 3.3
65AH/100AH 1PC
B-1A 540x210x230 17AH/24AH/38AH 6/4/3PCS 4.5
B-2 450x470x320 17AH/24AH/38AH 10/6/4 PCS 7
65AH/100AH 2PCS
B-3 585x470x320 17AH/24AH/38AH 14/8/6PCS 9
65AH/100AH 3PCS
B-4 450x470x615 17AH/24AH/38AH 20/12/8PCS 15
65AH/100AH 4PCS
B-6 585x470x615 17AH/24AH/38AH 28/16/12PCS 18
65AH/100AH 6PCS
B-8 780x470x615 17AH/24AH/38AH 44/28/20PCS 21
65AH/100AH 8PCS
B-10 950x470x615 17AH/24AH/38AH 44/28/20PCS 24
65AH/100AH 10PCS
B-12 780x470x910 24AH/38AH 30/24PCS 32
65AH/100AH 12PCS
B-16 780x470x1190 24AH/38AH 40/32PCS 45
65AH/100AH 16PCS
B-20 950x470x1190 24AH/38AH 56/40PCS 50
65AH/100AH 20PCS
B-24 1150x470x1190 65AH/100AH 24PCS 57
B-32 780x880x1190 65AH/100AH 32PCS 95
B-40 950x880x1190 65AH/100AH 40PCS 100
Features:
  • True Double conversion Technology
  • DSP digital control technology enable UPS more stable performance.
  • Three Level inverter control technology
  • Large screen LCD display
  • N+X Parallel Redundancy function (3 units parallel)
  • EPO emergency stop function
  • Smart expansion Slots (optional)
  • Support Generator
 
Applications:
  • Mammogram
  • Ultrasound Equipments
  • Radiology rooms
 
Technical Specifications
Model VT6K VT6KL VT10K VT10KL 31VT10KL 31VT15KL 31VT20KL
Capacity 6KVA/5400W 10KVA/9000W 15KVA/13.5KW 20KVA/18KW
Input Nominal Voltage 220/230/240Vac 380/400/415Vac
Voltage Range 120-275VAC(1P2W+G) 207-475VAC(3P4W+G)
Current 31A (max) 50A(max) 50A (max) 75A(max) 100A(max)
Frequency 46-54Hz Synchronous mains power; 50Hz( Frequency Range 40-46Hz ~54-60Hz);50Hz(Battery mode)
Power Factor ≥0.99·
Output Voltage 220/230/240±2%Vac (1P2W+G)
Frequency 50/60 Hz(adjustable) 50/60Hz± 5% (Line mode) 50/60Hz ± 0.05Hz ( Battery mode)
Current 27.3A 45A 68A 91A
Power Factor 0.9
Waveform Pure Sine Wave
Waveform Distortion Line load <2% Line load <3%
Back-up Time Full Load ≥7′ Depends on external batteries bank’s Capacity ≥5′ Depends on external batteries bank’s Capacity
Half Load ≥20 ≥13′
Battery Nominal Voltage 192/240Vdc
Transfer Time 0ms
Overload Capacity 105%±5%< Load<125%±5% :1 min transfer to bypass 125% ±5% < Load<135 % ±5 % :30s transfer to bypass Load > 135 % ± 5 %: 300s transfer to bypass
Communication SNMP,RS-232,USB+lntelligent Slot
Operating Environment Temperature 0°C~40°C
Humidity 15%~90%
Dimension Width (mm) 260 260 260 260 260
Depth (mm) 560 533 560 533 560
Height (mm) 717 501 717 501 717
Net Weight(Kg) 55 12.2 62 21 23 32 33
Features:
Three Phase Hybrid Solar Inverter Off grid three phase solar hybrid inverter with pwm/mppt can be used in single-phase and three-phase ac load with total power not exceeding  100kva/120kva/125kva/150kva/160kva,384vdc to 380vac. •Pure sine wave output. •Low DC voltage, saving system cost. •Three phase solar inverter with built-in PWM or MPPT charge controller. •AC charge current 0-45A adjustable. •Wide LCD screen, clearly and precisely shows icon data. •100%imbalance loading design, 3 times peak power. •Setting different working modes based on variable usage requirements. •DC first/AC first optional. •Various communication ports and remote controls  
Specifications
MODEL DX100KVA DX120KVA DX125KVA DX150KVA DX160KVA 190KVA 200KVA
Rated Power 80KW 96KW 100KW 120KW 128KW 150KW 160KW
Peak Power(20ms) 240KVA 288KVA 300KVA 360KVA 384KVA 450KVA 480KVA
Start Motor 40HP 50HP 50HP 60HP 60HP 80HP 80HP
Battery Voltage 384VDC
Size(L*W*Hmm) 875*720*1380 1123*900*1605
Packing Size(L*W*Hmm) 980*825*1560 1185*960*1750
N.W.(kg) 512 592 612 612 642 705 755
G.W.(kg)(Wooden Packing) 552 632 652 652 692 755 805
INPUT DC Input Voltage Range 10.5VDC-15VDC(Single battery voltage)
AC Input Voltage Range 380Vac/400Vac±10%(customized 190Vac/200Vac)
AC Input Frequency Range 45Hz-55Hz(50Hz)/ 55Hz-65Hz(60Hz)
Max AC charging current 0-45A(Depending on the model)
AC charging method Three-stage (constant current, constant voltage, floating charge)
Phase 3 PHASE
OUTPUT Efficiency(Battery Mode) ≥85%
Output Voltage(Battery Mode) 380Vac/400Vac±10%(customized 190Vac/200Vac)
Output Frequency(Battery Mode) 50/60Hz ±1%
Output Wave(Battery Mode) Pure Sine Wave
Output waveform distortion Linear load≤3%
Efficiency(AC Mode) >99%
Output Voltage(AC Mode) Conforming to AC input
Output Frequency(AC Mode) Conforming to AC input
No load loss(Battery Mode) ≤1% rated power
No load loss(AC Mode) ≤2%rated power( charger does not work in AC mode)
No load loss (Energy saving Mode) ≤10W
Phase 3 PHASE
BATTERY VRLA Battery Charge Voltage :13.8V; Float Voltage:13.7V(Single battery voltage)
Customize battery Charging and discharging parameters of different types of batteries can be customized according to user requirements
(charging and discharging parameters of different types of batteries can be set through the operation panel)
Protection Battery undervoltage alarm 11V(Single battery voltage)
Battery undervoltage protection 10.5V(Single battery voltage)
Battery overvoltage alarm 15V(Single battery voltage)
Battery overvoltage protection 17V(Single battery voltage)
Battery overvoltage recovery voltage 14.5V(Single battery voltage)
Overload power protection Automatic protection (battery mode), circuit breaker or insurance (AC mode)
Inverter output short circuit protection Automatic protection (battery mode), circuit breaker or insurance (AC mode)
Temperature protection >90°C(Shut down output)
Alarm A Normal working condition, buzzer has no alarm sound
B Buzzer sounds 4 times per second when battery failure, voltage abnormality, overload protection
C When the machine is turned on for the first time, the buzzer will prompt 5 when the machine is normal
Inside Solar controller Charging Mode MPPT or PWM
(Optional) Charging current PWM: 100A-200A / MPPT: 50A/100A
PV Input Voltage Range PWM: 480V-704V / MPPT: 480V-640V
Max PV Input Voltage(Voc) PWM: 750V / MPPT: 800V
(At the lowest temperature)
PV Array Maximum Power PWM: 44.8KW(100A)/33.6KW*2(150A)/44.8KW*2(200A)) / (MPPT: 22.4KW(50A)/22.4KW*2(100A)
Standby loss ≤3W
Maximum conversion efficiency >95%
Working Mode Battery First/AC First/Saving Energy Mode
Transfer Time ≤4ms
Display LCD
Thermal method Forced Air Cooling
Communication(Optional) RS485/APP(WIFI monitoring or GPRS monitoring)
Environment Operating temperature -10℃~40℃
Storage temperature -15℃~60℃
Noise 2000m(More than derating)
Elevation ≤65dB
Humidity 0%~95% ,No condensation
WeightN/AN/AN/AN/AN/AN/A
DimensionsN/AN/AN/AN/AN/AN/A