Description | Shipped From Abroad
Delivery & Availability:
Typically 10-21 working days – excluding furniture and heavy/bulky equipment. Please contact us for further information.
| Shipped From Abroad
Features:
1)19 inches standard design of rack mount, compact structure.
2)Sin wave output provides best power supply guarantee.
3)Zero transfer time between mains mode and battery mode.
4)Detection function of input neutral wire and live wire.
5)Having voltage surge protection function and strong anti-interference function.
6)Equipped with correction function of input power factor
7) Supporting mobile smart monitoring card , users can real-time monitor every data of the UPS by mobile APP.
Delivery & Availability:
Typically 10-21 working days – excluding furniture and heavy/bulky equipment. Please contact us for further information.
| Shipped From Abroad
Features:
- Optional 7 ” touch LCD
- Online double-conversionDSP technology guarantees high reliability
- True galvanic isolation transformer designControl designed to withstand all kinds of loads
- Intelligent battery management to prolong battery lifecycle
- Redundant fan design and independent ventilation enhance durable operation under harsh environment
- Adiustable battery numbers
- Accept dual-mains input
- Parallel operation with up to 4 units ( option )
- Variety of communication options available
- Reverse phase frequency operation and supportsnon-neutral input
Delivery & Availability:
Typically 10-21 working days – excluding furniture and heavy/bulky equipment. Please contact us for further information.
| Shipped From Abroad
Features:
- Pure sine wave output
- DSP digital control
- Boost and buck AVR for voltage stabilization
- Cold start function
- Intelligent battery management
- Short circuit and overload protection
- Off-mode charging
- Offering LED and LCD panels for selection
- Optional USB/RS232/RJ45/SNMP communication port
Delivery & Availability:
Typically 10-21 working days – excluding furniture and heavy/bulky equipment. Please contact us for further information.
| Shipped From Abroad
Features:
- 50KW single power module in 3U
- N+1or N+X parallel redundancy for power guarantee
- Supports horizontal expansion by 1+1 cabinet paralleloperation.
- Hot-swappable modular design decreases MTTR
- High scalability
- Built-in maintenance bypass switch for easy maintenance without interruptible
- High efficiency double conversion online UPS
- Flexible battery configuration and adjustable charging current
- High overload capability
- Power walk-in function
- Built-in dynamic password protection
- Built-in ultra communication slot
Delivery & Availability:
Typically 10-21 working days – excluding furniture and heavy/bulky equipment. Please contact us for further information.
| Shipped From Abroad
Features:
- Intelligent CPU control
- Automatic power on when the the main power recovers
- Cold start function
- Power off charging function
- USB/RS232/RJ-11/RJ-45 communication port (optional)
- Offering LED and LCD panels for selection
Delivery & Availability:
Typically 10-21 working days – excluding furniture and heavy/bulky equipment. Please contact us for further information.
|
Content | Features:
- True double-conversion
- LCD screen auto-rotation with Rack position ( only for 10K-20K models)
- DSP technology guarantees high performance
- Output power factor 1
- Support 1/1;3/1;3/3 Phase Adjustable
- Active power factor correction in all phases
- 50HZ / 60HZ frequency converter mode
- ECO mode operation for energy saving ( ECO)
- Emergency power off function ( EPO)
- Generator compatible
- Supports dual AC inputs
- 3-stage extendable charging design for optimized battery performance
- Adjustable battery numbers for long-run model
- Supporting Parallel sharing of battery packs
- Optional isolation transformer offers full isolation and complete common mode noise rejection
- Support with SNMP,USB, RS232 communication
Technical Specifications
MODEL |
33RM 10KL |
33RM 15KL |
33RM 20KL |
33RM 30KL |
33RM 40KL |
33RM 60KL |
CAPACITY |
10KVA/10KW |
15KVA/15KW |
20KVA/20KW |
30KVA/30KW |
40KVA/40KW |
60KVA/60KW |
PHASE |
3 Phase input / 3 Phase output |
PARALLEL CAPABILITY |
4 Max |
INPUT |
Nominal Voltage |
3×380 VAC (3Ph+N) |
Voltage Range |
190-520 VAC (3 Phase) @ 50% load , 305-478 VAC (3 Phase) @ 100% load |
Frequency Range |
46-54 Hz or 56~64Hz |
Power Factor |
≥ 0.99 @ 100% load |
OUTPUT |
Output Voltage |
3 x 360*/380/400/415 VAC (3Ph+N) |
AC Voltage Regulation (Batt. Mode) |
± 1% |
Frequency Range (Synchronized Range) |
46~54Hz or 56~64Hz |
Frequency Range (Batt. Mode) |
50 Hz ±0.1 Hz or 60 Hz ±0.1 Hz |
Current Crest Ratio |
3:1 (max.) |
Harmonic Distortion |
≤1 % THD (Linear Load), ≤3% THD (Non-linear Load) |
Transfer Time |
AC mode to Battery mode |
zero |
Inverter to Bypass |
zero |
Waveform (Batt. Mode) |
Pure Sine Wave |
Overload |
AC Mode |
100-110% for 60 min, 110-125% for 10 min, 125%~150% for 1 min; >150% immediately Protection |
Battery Mode |
100-110% for 60 min, 110-125% for 10 min, 125%~150% for 1 min; >150% immediately Protection |
EFFICIENCY |
AC Mode |
95.5% |
ECO Mode |
98.5% |
Battery Mode |
94.5% |
BATTERY |
Battery Type |
Depending on the applications |
Numbers |
20 pcs |
32-40 pcs (Adjustable) |
Charging Current (max.) |
1A~ 12A (Adjustable) |
1A~ 16A (Adjustable) |
1A 〜18A (Adjustable) |
Charging Voltage |
±13.65 VDCx N (N=10) |
±13.65VxN (N=16〜20) |
PHYSICAL |
Dimension, D * W * H (mm) |
680*438*133 [3U] |
797*438*176 [4U] |
Net Weight (kgs) |
27 |
30 |
40 |
45 |
ENVIRONMENT |
Operation Temperture |
0-40°C |
Operation Humidity |
0-95% and non-condersing |
Noise Level |
Less than 62dB @ 1 Meter |
Less than 65dB @ 1 Meter |
Less than 70dB @ 1 Meter |
MANAGEMENT |
Smart RS-232/USB |
Supports Windows® Family, Linux and MAC |
Optional SNMP |
Power management from SNMP manager and web browser |
| Features:
1)19 inches standard design of rack mount, compact structure.
2)Sin wave output provides best power supply guarantee.
3)Zero transfer time between mains mode and battery mode.
4)Detection function of input neutral wire and live wire.
5)Having voltage surge protection function and strong anti-interference function.
6)Equipped with correction function of input power factor
7) Supporting mobile smart monitoring card , users can real-time monitor every data of the UPS by mobile APP.
Technical Specifications
Model |
RTX3110KL |
RTX3115KL |
RTX3120KL |
Rated Power |
10kVA/9kW |
15kVA/13.5kW |
20kVA/18kW |
INPUT |
Voltage Range |
207-475Vac3P4W+G |
Working Frequency Range |
40-70HZ (settable) |
Input Power Factor |
>0.95 |
OUTPUT |
Rated Voltage and Accuracy |
220Vac(l±l%)lP2W+G |
Output Frequency |
46-54Hz synchronize with mains power; 50Hz (Mains power between 40-46Hz and 54-60Hz); 50Hz(Battery) |
Rated Current |
45A |
68A |
91A |
Output Power Factor |
0.9 |
Output Harmonic Wave |
W3% |
Crest Factor |
3:1 |
Output Overload |
105%±5%<Load≤125%±5%: Convert to bypass output and alarm after 1 min;
125%±5%<Load ≤50%±5%: Convert to bypass output and alarm after 30s;
Load>150%±5%: Convert to bypass output and alarm after 300ms. |
Transfer Time |
0ms |
Efficiency |
>92% |
BATTERY |
Rated Voltage |
192Vdc |
Quantity |
16 |
Charging Current |
5.5A |
Dimension (LxWxH) mm |
665*482.6*132.5 |
655*482.6*265 |
Weight |
23kg |
34kg |
35kg |
Working Temperature |
0°〜40°C |
Working Humidity |
20% 〜95% |
Noise |
≤60dB |
| Features:
- Optional 7 ” touch LCD
- Online double-conversionDSP technology guarantees high reliability
- True galvanic isolation transformer designControl designed to withstand all kinds of loads
- Intelligent battery management to prolong battery lifecycle
- Redundant fan design and independent ventilation enhance durable operation under harsh environment
- Adiustable battery numbers
- Accept dual-mains input
- Parallel operation with up to 4 units ( option )
- Variety of communication options available
- Reverse phase frequency operation and supportsnon-neutral input
Specifications
MODEL |
LF33 10K |
LF33 20K |
LF33 30K |
LF33 40K |
LF33 60K |
LF33 80K |
LF33 100K |
LF33 120K |
LF33 160K |
LF33 200K |
CAPACITY |
10KVA /8KW |
20KVA /16KW |
30KVA /24KW |
40KVA /32KW |
60KVA /48KW |
80KVA /64KW |
100KVA /80KW |
120KVA /96KW |
160KVA /128KW |
200KVA /160KW |
INPUT |
Nominal Voltage |
3 x 380VAC/400VAC (3Ph + N) |
Acceptable Voltage Range |
305VAC ~ 460VAC |
Frequency |
46-54Hzor56-64Hz |
INVERTER |
Nominal Voltage |
3 x 380VAC/400VAC (3Ph + N) |
Precision |
Stationary: ±1% Transitory: ±5% (load variations 100-0-100%) |
Frequency |
50/60 Hz synchronised ±1 % With mains absent ±0.1 Hz |
Max. Synchronisation Speed |
±1 Hz/s |
Waveform |
Pure Sinewave |
Total Harmonic Distortion (THDv) |
<2% (Linear Load) ; <5% (Non-linear Load) |
Phase Displacement |
120° ±1 % (balanced load); 120° ±2% (imbalances 50% of the load) |
Dynamic Recovery Time |
Restore to 90% of rated value in 3 cycles |
Overload capacity |
110% for 10min; 150% for 60sec; >160% for 200ms |
Admissible Crest Factor |
3:1 |
Admissible Power Factor |
0.6-1 (inductive or capacitive) |
Imbalance Output Voltage @ 100% Unbalanced Load |
<1% |
Current Limit |
High overload, short-circuit: RMS Voltage Limit; High Crest-Factor current: Peak Voltage Limit |
STATIC BYPASS |
Type |
Solid state |
Voltage |
3 x 380VAC/400VAC (3Ph + N) |
Frequency |
50/60 Hz |
Activation Criterion |
Microprocessor control |
Transfer Time |
Zero |
Admissible Overload |
150% for 1 hour; 180% for 30sec; >200% for 200ms |
Transfer to Bypass |
Immediate, for overloads above 160% |
Retransfer |
Automatic after alarm clear |
MAINTENANCE BYPASS |
Type |
Without interruption |
Voltage |
3 * 400V (3Ph + N) |
Frequency |
50/60 Hz |
Overall Efficiency |
Line Mode |
90% |
91% |
92% |
93% |
Battery Mode |
90% |
91% |
93% |
93% |
BATTERY & CHARGER |
Battery Type and Numbers |
12VDC * 32 pcs (29-32 pcs adjustable) |
Nominal Battery Voltage |
384 VDC (Based on 32pcs batteries) |
Charging Method |
CC/CV |
Precision |
±1% |
Charging Current |
Max.: 40 A |
Charging Voltage |
432 VDC (Based on 32pcs batteries) |
PHYSICAL |
Dimensions, D x W x H(mm) |
656 x 405 x 817 |
656 x 405 x 941 |
840x432x1140 |
975x554x1286 |
1200x910x1680 |
1500x1140x1800 |
Net Weight (Kgs) |
180 |
205 |
295 |
330 |
451 |
519 |
950 |
1350 |
| Features:
- Pure sine wave output
- DSP digital control
- Boost and buck AVR for voltage stabilization
- Cold start function
- Intelligent battery management
- Short circuit and overload protection
- Off-mode charging
- Offering LED and LCD panels for selection
- Optional USB/RS232/RJ45/SNMP communication port
Technical Specifications
MODEL |
UPS-AP1K ( L ) |
UPS-AP2K ( L ) |
UPS-AP3K ( L ) |
Capacity |
1000VA/700W |
2000VA/1400W |
3000VA/2100W |
INPUT |
Voltage range |
145~275VAC±5V |
Frequency range |
50Hz-60Hz |
OUTPUT |
Output voltage |
220VAC |
AC voltage range |
±10% |
Frequency range(batt.mode) |
50Hz ± 0.25Hz or 60Hz ± 0.3Hz |
Overload |
105%-110%: UPS beep alarm, do not shut down. |
110%-130%: auto shut down after 30 seconds |
> 130%: auto shut down immediately |
Transfer time |
<typical 4ms |
Waveform(batt.mode) |
Pure sine wave |
BATTERY |
Standard model |
Battery type |
12V7Ah |
Numbers |
2 |
4 |
6 |
Charging current(Max.) |
Assume: 1A± 10%; Max: 1A or 2A for option |
Charging voltage |
27.3VDC±1% |
54.7VDC±1% |
82.0VDC±1% |
Long-run model |
Battery type |
12V, AH depending on applicant |
Numbers |
3 |
6 |
8 |
Charging current(Max.) |
> 5A |
Charging voltage |
27.4VDC±1% |
82.1VDC±1% |
109.4VDC±1% |
PHYSICAL |
Standard model |
Dimension, LxWxH(mm) |
360x147x220 |
440x192x340 |
440x192x340 |
Net weight(kgs) |
11.9 |
22 |
27.9 |
Long-run model |
Dimension, LxWxH(mm) |
360x147x220 |
440x192x340 |
440x192x340 |
Net weight(kgs) |
8.5 |
16 |
18.2 |
ENVIRONMENT |
Humidity |
20-90%RH @0-40°C (non-condensing) |
Noise level |
Less than 55dBA@1 Meter |
MANAGEMENT |
Smart RS-232 |
Support windows 2000/2003/XP/Vista/2008, Windows7/8, Linux, Unix, and MAC |
Optional SNMP |
Power management from SNMP Management and web browser |
| Features:
- 50KW single power module in 3U
- N+1or N+X parallel redundancy for power guarantee
- Supports horizontal expansion by 1+1 cabinet paralleloperation.
- Hot-swappable modular design decreases MTTR
- High scalability
- Built-in maintenance bypass switch for easy maintenance without interruptible
- High efficiency double conversion online UPS
- Flexible battery configuration and adjustable charging current
- High overload capability
- Power walk-in function
- Built-in dynamic password protection
- Built-in ultra communication slot
Specifications:
MODEL |
RM Plus 300K |
RM Plus 350K |
RM Plus 400K |
RM Plus 500K |
Phase |
3 Phase in / 3 Phase out |
Cabinet Capacity* |
300 KW |
350 KW |
400KW |
500KW |
Battery Type |
Extemal Battery |
One Power Module Capacity |
50KVA/50KW |
Max. Power Module No. |
6 |
7 |
8 |
10 |
INPUT |
Nominal Voltage |
3×380/400/415 VAC (3Ph+N) |
Voltage Range |
’-20%~+15% |
Nominal Frequency |
50/60Hz(Auto Sensing) |
Frequency Range |
40Hz~70Hz |
Power Factor |
>0.99 @100% Load, >0.98@50% Load |
Harmonic Distortion (THDi) |
<4% @ 100% load |
OUTPUT |
Nominal Voltage |
3×380/400/415 VAC (3Ph+N) |
Voltage Regulation(Steady State) |
≤ ±1% Typical (balanced load); ~≤ ±2% Typical (unbalanced load) |
Nominal Frequency |
50/60Hz |
Frequency Range(Synchronized) |
46Hz~54Hz or 56Hz~64Hz |
Overload Capability |
1 hour for ≤110%,10 mins for 111%~125%,1 min for 126%~150% and 200ms for >150% |
Haronic Distortion |
≤2% THD (Linear Load); ≤4% THD (Non-linear Load) |
Eficiency |
95.50% |
BATTERY / CHARGER |
Nominal Voltage |
‘+/- 192V~+/- 240V (Selectable) |
Maximum Voltage |
’+/- 240V (12V×40PCS) |
Minimum Voltage |
‘+/- 192V(12V×32PCS) |
Floating Charge Voltage |
2.28V/Cell (2.25~2.33 Selectable) |
Boost Charging Voltage |
2.35V/Cell |
Temperature Compensation |
Yes |
Maximum Charging Current
(Per Power Module) |
12A (Adjustable) |
PHYSICAL |
Cabinet Dimension (DxWxH)mm |
1065x600x2000 |
1065x600x2000 |
1065x1000x2000 |
1065x1000x2000 |
Net Weight (Kg) |
545 |
654 |
932 |
1020 |
Power Module (PM-50) Net Weight |
44KGS |
ENVIRONMENT |
Operating Temperature |
0~40℃ |
Relative Humidity |
0~95% non-condensing |
Altitude* |
<1000m for Nominal power |
IP Protection |
IP 20 |
MANAGEMENT |
Smart RS-232/USB |
Supports Windows⑧ Family, Linux and MAC |
Optional SNMP |
Power management from SNMP manager and web browser |
STANDARDS |
Safety |
IEC/EN 62040-1 |
EMC |
IEC/EN 62040-2 Category C3 |
| Features:
- Intelligent CPU control
- Automatic power on when the the main power recovers
- Cold start function
- Power off charging function
- USB/RS232/RJ-11/RJ-45 communication port (optional)
- Offering LED and LCD panels for selection
Application:
- Personal Computer
- Printer
- POS(Point of sales)Terminals
- Security System
- Fax Machine
- Modem, WiFi Router
Technical Specifications:
Model |
DP600 |
DP1000 |
DP1200 |
DP2000 |
DP3000 |
Capacity |
600VA/360W |
1000VA/600W |
1200VA/720W |
2000VA/1200W |
3000VA/1800W |
INPUT |
Voltage |
110/120VAA or 220/230/240VAC |
Voltage Range |
67-137VAC/135-275VAC |
Frequency Range |
50Hz Or 60Hz(Auto-Sensing) |
OUTPUT |
Output Voltage |
110/120VAA or 220/230/240VAC |
AC Voltage Regulation |
± 10% |
Frequency Range
(Batt. Mode) |
50 HZ or 60 Hz ± 10% |
Transfer Time |
Typical 6-10 ms |
Waveform
(Battery Mode) |
Simulated Sine Wave |
BATTERY |
Battery Voltage |
12V/7AH*1 |
12V/9AH*1 |
12V/7AH*2 |
12V/9AH*2 |
12V/7AH*4 |
Charge Time |
8 hours up to 80-90% |
PROTECTION |
Full Protection |
Auto Detection, discharge protection,output Short circuit, Over load, Battery low voltage protection |
Communication Port |
USB/RS232/RJ11/RJ45 (Optional) |
Display |
LED/LCD |
Alarm |
Battery Mode |
Every 4 Seconds one beep |
Low Battery Capacity |
Every 1 Seconds one beep |
Overload |
Every 1 Seconds one beep |
Fault |
Keep beeping |
ENVIRONMENT |
Humidity |
0-90% Rh @ 0-40℃ (Non-Condensing) |
Noise Level |
40dB |
Dimension(mm) |
320*90*140 |
330* 100*150 |
365*140*165 |
365*140*165 |
395*145*210 |
N.W.(kg) |
5.2 |
6 |
10 |
12.6 |
21 |
|
Reviews