50/60 Hz synchronised ±1 % With mains absent ±0.1 Hz
Max. Synchronisation Speed
±1 Hz/s
Waveform
Pure Sinewave
Total Harmonic Distortion (THDv)
<2% (Linear Load) ; <5% (Non-linear Load)
Phase Displacement
120° ±1 % (balanced load); 120° ±2% (imbalances 50% of the load)
Dynamic Recovery Time
Restore to 90% of rated value in 3 cycles
Overload capacity
110% for 10min; 150% for 60sec; >160% for 200ms
Admissible Crest Factor
3:1
Admissible Power Factor
0.6-1 (inductive or capacitive)
Imbalance Output Voltage @ 100% Unbalanced Load
<1%
Current Limit
High overload, short-circuit: RMS Voltage Limit; High Crest-Factor current: Peak Voltage Limit
STATIC BYPASS
Type
Solid state
Voltage
3 x 380VAC/400VAC (3Ph + N)
Frequency
50/60 Hz
Activation Criterion
Microprocessor control
Transfer Time
Zero
Admissible Overload
150% for 1 hour; 180% for 30sec; >200% for 200ms
Transfer to Bypass
Immediate, for overloads above 160%
Retransfer
Automatic after alarm clear
MAINTENANCE BYPASS
Type
Without interruption
Voltage
3 * 400V (3Ph + N)
Frequency
50/60 Hz
Overall Efficiency
Line Mode
90%
91%
92%
93%
Battery Mode
90%
91%
93%
93%
BATTERY & CHARGER
Battery Type and Numbers
12VDC * 32 pcs (29-32 pcs adjustable)
Nominal Battery Voltage
384 VDC (Based on 32pcs batteries)
Charging Method
CC/CV
Precision
±1%
Charging Current
Max.: 40 A
Charging Voltage
432 VDC (Based on 32pcs batteries)
PHYSICAL
Dimensions, D x W x H(mm)
656 x 405 x 817
656 x 405 x 941
840x432x1140
975x554x1286
1200x910x1680
1500x1140x1800
Net Weight (Kgs)
180
205
295
330
451
519
950
1350
Features:
OPzV Tubular Gel Battery ( solid-state) 60AH-3000AH
Voltage class: 12V/2V
Capacity range: 60Ah~3000Ah
OPzV batteries offer high capacity reserve power and true deep cycling performance. With a design life of 20 years and a maintenance-free operation,
OPzV battery are perfect for regions with an unstable supply of electricity. OPzV battery are also completely spill-proof, which makes them safe to install anywhere,
even in remote environments with minimal supervision.
Technical Specifications
Model
Nominal Voltage
Capacity
Dimension
Terminal
C10/1.80VPC (Ah)
Length
Width
Height
Total Height
(V)
mm
mm
mm
mm
OPzV6-200
6
200
322
177.5
226
231
F16(M8)
F14(M8)
OPzV12-60
12
60
260
169
211
216
F11(M6)
OPzV12-80
12
80
328
172
215
220
F12(M8)
OPzV12-100
12
100
407
177
225
225
F12(M8)
OPzV12-120
12
120
483
170
241
241
F12(M8)
OPzV12-140
12
140
532
207
214
219
F12(M8)
OPzV12-160
12
160
532
207
214
219
F12(M8)
OPzV12-180
12
180
522
240
219
224
F10(M8)
OPzV12-200
12
200
521
268
220
225
F14(M8)
OPzV2-200
2
200
103
206
355
390
F10(M8)
OPzV2-250
2
250
124
206
355
390
F10(M8)
OPzV2-300
2
300
145
206
355
390
F10(M8)
OPzV2-350
2
350
124
206
470
505
F10(M8)
OPzV2-420
2
420
145
206
470
505
F10(M8)
OPzV2-500
2
490
166
206
470
505
F10(M8)
OPzV2-770
2
770
210
254
470
505
F10(M8)
OPzV2-600
2
600
145
206
645
680
F10(M8)
OPzV2-800
2
800
191
210
645
680
F10(M8)
OPzV2-1000
2
1000
233
210
645
680
F10(M8)
OPzV2-1200
2
1200
276
210
645
680
F10(M8)
OPzV2-1500
2
1500
275
210
795
830
F10(M8)
OPzV2-2000
2
2000
399
214
770
805
F10(M8)
OPzV2-2500
2
2500
487
212
770
805
F10(M8)
OPzV2-3000
2
3000
576
212
770
805
F10(M8)
Features:
Capacity: 1200W 1008Wh /315000mAh
Input AC Output Power:Rated Power 1200W Peak Power 2400W
Input AC Charging:AC100~125V/AC184~264V Bidirectional Inverter 700W Max
Input Car Charging:DC12V~24V/10A 240W Max
Input Solar Charging:DC12V~60V/10A 400W Max
Output Voltage:230VAC±10%/110VAC±10%
Output Frequency: 50Hz±5%/60Hz±5%
USB Output:2*5V2.4A +2*QC18W+2*PD60W Max
DC Output:1*Cigarette Lighter+2*DC5521 Rated Output (13.8V/10A Max)
Output Waveform:Pure Sine Wave
LED:3 Levels(H/M/L)+SOS
UPS Function:Support(≤10mS)
Applications:
Mammogram
Ultrasound Equipments
Radiology rooms
Description
HIGH INTELLIGENCE AND RELIABLE POWER SUPPLYIGBT Technology
Full microprocessor control with no-break static and manual bypasses.
Online double conversion technology (VFl) with isolation transformer on theinverter output.
Extremely high short-circuit current to ensure compatibility with the most diffificult transformer applications (lighting, drives and industrial processes) and an isolation transformer on the inverter output.
Compatibled with Watch & Save 3000 software as standard and can be remotely monitored using the Power NetGuard system from anywhere in the world.
SIMPLE TO INSTALL
Capability to install the UPS into any distribution system(neutral not required on rectifier input).
Capability to separate the rectifier/bypass power networks and to power them from two separate sources, without Galvanic isolation(Necessary on UPS without an output transformer
MAXIMUM BATTERY CARE
Battery deep discharge protection;
Temperature compensating charger;
Built-in automatic and manual battery test feature.
OTHER CHARACTERISTICS
0.8/0.9 power factor suitable for powering ICT and lndustrial loads.
BACK FEED protection: to avoid energy feeding back into the mains supply cause a fault occur.
MAXIMUM RELIABILITY AND AVAILABILITY
Connect up to 6 units in parallel or N+1 redundancy, even of different power ratings.
The UPS continue to work in parallel even if one of theinterconnecting communication cables is disconnected(CLOSED LOOP)
LOW CONSUMPTION LEVELS
LF31 Series UPS can achieve efficiencies >98% thanks to selectable Economy Mode which can be used in stable electrical environments to provide power supply continuity when the mains fail.
ADVANCE COMMUNICATION:
RS485/RS232/Dry Contact/SNMP(Optional)
Specifications
Model
10KVA
15KVA
20KVA
30KVA
40KVA
60KVA
80KVA
100KVA
Capacity
8KW
12 KW
16 KW
24 KW
32 KW
48 KW
64 KW
80 KW
INPUT
Rated voltage
380/400/415 VAC Three-phase
Voltage range
±20%
Frequency range
45-65Hz
Power factor
>0.92 with harmonic filter
Current harmonic distortion
<5% with harmonic filter
Soft Start
0 -100% in 10″
BYPASS INPUT
Rated voltage
230VAC Single Phase
Permitted voltage range
±15% (selectable from ±10% to ±25% from front panel)
Three Phase Hybrid Solar Inverter
Off grid three phase solar hybrid inverter with pwm/mppt can be used in single-phase and three-phase ac load with total power not exceeding 100kva/120kva/125kva/150kva/160kva,384vdc to 380vac.
•Pure sine wave output.
•Low DC voltage, saving system cost.
•Three phase solar inverter with built-in PWM or MPPT charge controller.
•AC charge current 0-45A adjustable.
•Wide LCD screen, clearly and precisely shows icon data.
•100%imbalance loading design, 3 times peak power.
•Setting different working modes based on variable usage requirements.
•DC first/AC first optional.
•Various communication ports and remote controls