1 hour for ≤110%,10 mins for 111%~125%,1 min for 126%~150% and 200ms for >150%
Haronic Distortion
≤2% THD (Linear Load); ≤4% THD (Non-linear Load)
Eficiency
95.50%
BATTERY / CHARGER
Nominal Voltage
‘+/- 192V~+/- 240V (Selectable)
Maximum Voltage
’+/- 240V (12V×40PCS)
Minimum Voltage
‘+/- 192V(12V×32PCS)
Floating Charge Voltage
2.28V/Cell (2.25~2.33 Selectable)
Boost Charging Voltage
2.35V/Cell
Temperature Compensation
Yes
Maximum Charging Current
(Per Power Module)
12A (Adjustable)
PHYSICAL
Cabinet Dimension (DxWxH)mm
1065x600x2000
1065x600x2000
1065x1000x2000
1065x1000x2000
Net Weight (Kg)
545
654
932
1020
Power Module (PM-50) Net Weight
44KGS
ENVIRONMENT
Operating Temperature
0~40℃
Relative Humidity
0~95% non-condensing
Altitude*
<1000m for Nominal power
IP Protection
IP 20
MANAGEMENT
Smart RS-232/USB
Supports Windows⑧ Family, Linux and MAC
Optional SNMP
Power management from SNMP manager and web browser
STANDARDS
Safety
IEC/EN 62040-1
EMC
IEC/EN 62040-2 Category C3
Description
HIGH INTELLIGENCE AND RELIABLE POWER SUPPLYIGBT Technology
Full microprocessor control with no-break static and manual bypasses.
Online double conversion technology (VFl) with isolation transformer on theinverter output.
Extremely high short-circuit current to ensure compatibility with the most diffificult transformer applications (lighting, drives and industrial processes) and an isolation transformer on the inverter output.
Compatibled with Watch & Save 3000 software as standard and can be remotely monitored using the Power NetGuard system from anywhere in the world.
SIMPLE TO INSTALL
Capability to install the UPS into any distribution system(neutral not required on rectifier input).
Capability to separate the rectifier/bypass power networks and to power them from two separate sources, without Galvanic isolation(Necessary on UPS without an output transformer
MAXIMUM BATTERY CARE
Battery deep discharge protection;
Temperature compensating charger;
Built-in automatic and manual battery test feature.
OTHER CHARACTERISTICS
0.8/0.9 power factor suitable for powering ICT and lndustrial loads.
BACK FEED protection: to avoid energy feeding back into the mains supply cause a fault occur.
MAXIMUM RELIABILITY AND AVAILABILITY
Connect up to 6 units in parallel or N+1 redundancy, even of different power ratings.
The UPS continue to work in parallel even if one of theinterconnecting communication cables is disconnected(CLOSED LOOP)
LOW CONSUMPTION LEVELS
LF33 Series UPS can achieve efficiencies >98% thanks to selectable Economy Mode which can be used in stable electrical environments to provide power supply continuity when the mains fail.
ADVANCE COMMUNICATION:
RS485/RS232/Dry Contact/SNMP(Optional)
Specifications
Model
10KVA
20KVA
30KVA
40KVA
60KVA
80KVA
100KVA
120KVA
160KVA
200KVA
250KVA
300KVA
400KVA
500KVA
600KVA
Capacity
8KW
16 KW
24 KW
32 KW
48 KW
64 KW
80 KW
96 KW
128 KW
160 KW
200KW
240KW
320KW
400KW
480KW
INPUT
Rated voltage
400 VAC Three-Phase
Voltage range
380/400/415VAC(+25%,Can be set through the LCD panel)
Frequency range
40-70Hz(Automatically select synchronization range according to grid frequency)
Range(HZ)
50±5%(±10%) Bypass synchronization tracking
Rectifying pulse number
6 pulse rectification
6/12 pulse rectification
12 pulse rectifier
Phase system
3φ4W+PE(Three phase five wire system)
Battery voltage
384VDC
480VDC
Battery Quantity
Standard with 32 Cells(30~34, can be set through the LCD panel) Standard 40 Cells(38~42 knots,can be set by LCD panel)
OUTPUT
Power factor
0.8/0.9 (Optional)
Voltage(V)
L-N: 220±1% L-L: 380±1%
Three-phase 100% load
unbalance voltage stability
≤2%,Allow 100% imbalance
Frequency(HZ)
Normal power, tracking the frequency of power, Grid abnormal. 50±0.2%
Transfer time(ms)
0ms
Parallel operation mode
(parallel type)
Max 8 Parallel
Waveform distortion
Linear loadTHD<3% ; Nonlinear loadTHD<5%
Overload capacity
125% full load for 10 minutes, maintain 150 % full load for 1 minute and then switch to bypass power supply,
after reducing the loadcan automatically restore the inverter
Crest factor
3:1
Others
Index
Standard with no transfer time maintenance bypass switch
Communication function
RS232/RS485/Dry Contact/SNMP (Optional)
Panel display
LED displays working status and fault indication; LCD displays three-phase input voltage,
input frequency, three-phase output voltage, load,battery voltage, battery charge and discharge current, etc
Display
7″ Touchable LCD screen display
The audio noise(dB)
<65(within 1 meter)
Alarm function
Battery low voltage, abnormal power supply, overload, UPS failure, over temperature protection
Protection
Input over voltage, battery under voltage, overload, short circuit, over temperature protection
Cooling way
Forced cooling
Operating temperature
0℃ to ~ 40℃
Humidity
0~95%, non-condensing
electromagnetic compatibility
Conform GB7260.2
Size(W*D*H)(mm)
540*660*1135
1100*800*1800
800*800*1900
1200*850*1900
2600*1100*2000
Weight
196
233
276
329
461
547.5
643
754
1375
Features:
Three Phase Hybrid Solar Inverter
Off grid three phase solar hybrid inverter with pwm/mppt can be used in single-phase and three-phase ac load with total power not exceeding 100kva/120kva/125kva/150kva/160kva,384vdc to 380vac.
•Pure sine wave output.
•Low DC voltage, saving system cost.
•Three phase solar inverter with built-in PWM or MPPT charge controller.
•AC charge current 0-45A adjustable.
•Wide LCD screen, clearly and precisely shows icon data.
•100%imbalance loading design, 3 times peak power.
•Setting different working modes based on variable usage requirements.
•DC first/AC first optional.
•Various communication ports and remote controls
OPzV Tubular Gel Battery ( solid-state) 60AH-3000AH
Voltage class: 12V/2V
Capacity range: 60Ah~3000Ah
OPzV batteries offer high capacity reserve power and true deep cycling performance. With a design life of 20 years and a maintenance-free operation,
OPzV battery are perfect for regions with an unstable supply of electricity. OPzV battery are also completely spill-proof, which makes them safe to install anywhere,
even in remote environments with minimal supervision.
Reviews