1 hour for ≤110%,10 mins for 111%~125%,1 min for 126%~150% and 200ms for >150%
Haronic Distortion
≤2% THD (Linear Load); ≤4% THD (Non-linear Load)
Eficiency
96%
BATTERY / CHARGER
Nominal Voltage
’+/- 192V~+/- 240V(Selectable)
Maximum Voltage
’+/- 240V (12V×40 PCS)
Minimum Voltage
‘+/-192V (12V×32 PCS)
Floating Charge Voltage
2.28V/Cell (2.25~2.33 Selectable)
Boost Charging Voltage
2.35V/Cell
Temperature Compensation
Yes
Maximum Charging Current
(Per Power Module)
18A(Adjustable)
PHYSICAL
Cabinet Dimension (DxWxH)mm
1100x600x1475
1100x600x1475
1100x600x2010
1100×600×2010
1065x1000x2000
1065×1000×2000
Net Weight (Kg)
308
352
516
654
932
1020
Power Module (PM-60) Net Weight
44KGS
ENVIRONMENT
Operating Temperature
0~40℃
Relative Humidity
0~95% non-condensing
Altitude*
<1000m for Nominal power
IP Protection
IP 20
MANAGEMENT
Smart RS-232/USB
Supports Windows⑧ Family, Linux and MAC
Optional SNMP
Power management from SNMP manager and web browser
STANDARDS
Safety
IEC/EN62040-1
EMC
IEC/EN 62040-2 Category C3
Features:
Pure sine wave output
DSP digital control
Boost and buck AVR for voltage stabilization
Cold start function
Intelligent battery management
Short circuit and overload protection
Off-mode charging
Offering LED and LCD panels for selection
Optional USB/RS232/RJ45/SNMP communication port
Technical Specifications
MODEL
UPS-AP1K ( L )
UPS-AP2K ( L )
UPS-AP3K ( L )
Capacity
1000VA/700W
2000VA/1400W
3000VA/2100W
INPUT
Voltage range
145~275VAC±5V
Frequency range
50Hz-60Hz
OUTPUT
Output voltage
220VAC
AC voltage range
±10%
Frequency range(batt.mode)
50Hz ± 0.25Hz or 60Hz ± 0.3Hz
Overload
105%-110%: UPS beep alarm, do not shut down.
110%-130%: auto shut down after 30 seconds
> 130%: auto shut down immediately
Transfer time
<typical 4ms
Waveform(batt.mode)
Pure sine wave
BATTERY
Standard model
Battery type
12V7Ah
Numbers
2
4
6
Charging current(Max.)
Assume: 1A± 10%; Max: 1A or 2A for option
Charging voltage
27.3VDC±1%
54.7VDC±1%
82.0VDC±1%
Long-run model
Battery type
12V, AH depending on applicant
Numbers
3
6
8
Charging current(Max.)
> 5A
Charging voltage
27.4VDC±1%
82.1VDC±1%
109.4VDC±1%
PHYSICAL
Standard model
Dimension, LxWxH(mm)
360x147x220
440x192x340
440x192x340
Net weight(kgs)
11.9
22
27.9
Long-run model
Dimension, LxWxH(mm)
360x147x220
440x192x340
440x192x340
Net weight(kgs)
8.5
16
18.2
ENVIRONMENT
Humidity
20-90%RH @0-40°C (non-condensing)
Noise level
Less than 55dBA@1 Meter
MANAGEMENT
Smart RS-232
Support windows 2000/2003/XP/Vista/2008, Windows7/8, Linux, Unix, and MAC
Optional SNMP
Power management from SNMP Management and web browser
Description
HIGH INTELLIGENCE AND RELIABLE POWER SUPPLYIGBT Technology
Full microprocessor control with no-break static and manual bypasses.
Online double conversion technology (VFl) with isolation transformer on theinverter output.
Extremely high short-circuit current to ensure compatibility with the most diffificult transformer applications (lighting, drives and industrial processes) and an isolation transformer on the inverter output.
Compatibled with Watch & Save 3000 software as standard and can be remotely monitored using the Power NetGuard system from anywhere in the world.
SIMPLE TO INSTALL
Capability to install the UPS into any distribution system(neutral not required on rectifier input).
Capability to separate the rectifier/bypass power networks and to power them from two separate sources, without Galvanic isolation(Necessary on UPS without an output transformer
MAXIMUM BATTERY CARE
Battery deep discharge protection;
Temperature compensating charger;
Built-in automatic and manual battery test feature.
OTHER CHARACTERISTICS
0.8/0.9 power factor suitable for powering ICT and lndustrial loads.
BACK FEED protection: to avoid energy feeding back into the mains supply cause a fault occur.
MAXIMUM RELIABILITY AND AVAILABILITY
Connect up to 6 units in parallel or N+1 redundancy, even of different power ratings.
The UPS continue to work in parallel even if one of theinterconnecting communication cables is disconnected(CLOSED LOOP)
LOW CONSUMPTION LEVELS
LF33 Series UPS can achieve efficiencies >98% thanks to selectable Economy Mode which can be used in stable electrical environments to provide power supply continuity when the mains fail.
ADVANCE COMMUNICATION:
RS485/RS232/Dry Contact/SNMP(Optional)
Specifications
Model
10KVA
20KVA
30KVA
40KVA
60KVA
80KVA
100KVA
120KVA
160KVA
200KVA
250KVA
300KVA
400KVA
500KVA
600KVA
Capacity
8KW
16 KW
24 KW
32 KW
48 KW
64 KW
80 KW
96 KW
128 KW
160 KW
200KW
240KW
320KW
400KW
480KW
INPUT
Rated voltage
400 VAC Three-Phase
Voltage range
380/400/415VAC(+25%,Can be set through the LCD panel)
Frequency range
40-70Hz(Automatically select synchronization range according to grid frequency)
Range(HZ)
50±5%(±10%) Bypass synchronization tracking
Rectifying pulse number
6 pulse rectification
6/12 pulse rectification
12 pulse rectifier
Phase system
3φ4W+PE(Three phase five wire system)
Battery voltage
384VDC
480VDC
Battery Quantity
Standard with 32 Cells(30~34, can be set through the LCD panel) Standard 40 Cells(38~42 knots,can be set by LCD panel)
OUTPUT
Power factor
0.8/0.9 (Optional)
Voltage(V)
L-N: 220±1% L-L: 380±1%
Three-phase 100% load
unbalance voltage stability
≤2%,Allow 100% imbalance
Frequency(HZ)
Normal power, tracking the frequency of power, Grid abnormal. 50±0.2%
Transfer time(ms)
0ms
Parallel operation mode
(parallel type)
Max 8 Parallel
Waveform distortion
Linear loadTHD<3% ; Nonlinear loadTHD<5%
Overload capacity
125% full load for 10 minutes, maintain 150 % full load for 1 minute and then switch to bypass power supply,
after reducing the loadcan automatically restore the inverter
Crest factor
3:1
Others
Index
Standard with no transfer time maintenance bypass switch
Communication function
RS232/RS485/Dry Contact/SNMP (Optional)
Panel display
LED displays working status and fault indication; LCD displays three-phase input voltage,
input frequency, three-phase output voltage, load,battery voltage, battery charge and discharge current, etc
Display
7″ Touchable LCD screen display
The audio noise(dB)
<65(within 1 meter)
Alarm function
Battery low voltage, abnormal power supply, overload, UPS failure, over temperature protection
Protection
Input over voltage, battery under voltage, overload, short circuit, over temperature protection
Cooling way
Forced cooling
Operating temperature
0℃ to ~ 40℃
Humidity
0~95%, non-condensing
electromagnetic compatibility
Conform GB7260.2
Size(W*D*H)(mm)
540*660*1135
1100*800*1800
800*800*1900
1200*850*1900
2600*1100*2000
Weight
196
233
276
329
461
547.5
643
754
1375
Features:
DSP digital control technology enables UPS more stable performance-+
Environment friendly eco-designed
Active input power factor correction
Wide range of input voltage and frequency
Zero power switch delay
Adaptive Load Management.
Sufficient Expansion Slots: USB ,RS485 ,AS400 SNMP cards(Optional)
Support the generator
Specifications:
Model
33VT 10K
33VT 10KL
33VT 20K
33VT 20KL
33VT 30KL
33VT 40KL
Capacity
10KVA/9000W
20KVA/18KW
30KVA/27KW
40KVA/36KW
Input
Nominal Voltage
380/400/415Vac
Voltage Range
207-475VAC(3P4W+G)
Current
14A
28A
42A
67A
Frequency
40-70Hz (Adjustable)
Power Factor
≥0.99
Output
Voltage
380VAC 1±1% (3P4W+G)
Frequency
46-54Hz Synchronous mains power; 50Hz( Frequency Range 40-46Hz -54-60Hz);50Hz(Battery mode)
Current
15A
30A
45A
61A
Power Factor
0.9
Crest Factor
3:1
THD
Line load <3%
Chrage Current
5.5A
1A
7.5A
1A
5.5A
Battery Nominal Voltage
192VDC
±192VDC
Transfer Time
0ms
Overload Capacity
105%±5%< Load<125%±5% :1 min transfer to bypass
125% ±5% < Load<135 % ±5 % :30s transfer to bypass
Load > 135 % ± 5 %: 300s transfer to bypass