1)Adopts compact frame structure design.
2)Pure Sine wave output no matter in AC mode or battery mode can provide sine wave power source with low distortion.
3)Zero Transfer time: when the utility power is cut off or recover, there is absolutely no time between the transfer of AC mode and battery mode.
4)Detect function for the nneutral wire and wire wire are wrongly connected.
5)Avoids wrong connection of neutral wire and live wire of UPS AC power input.
6)Voltage breakthrough protection and strong anti-interference function.
7)Input power factor correction: UPS can correct the input power factor. Under full load, the input power factor can reach over 0.95.
Applications:
Mammogram
Ultrasound Equipments
Radiology rooms
Technical Specifications
Model
RT 1K
RT 1KL
RT 2K
RT 2KL
RT 3K
RT 3KL
RT 6KL
RT 10KL
Input
Rated capacity
1KVA/900W
2KVA/1800W
3KVA/2700W
6KVA/5.4KW
10KVA/9KW
Voltage
90 ± 5-300 ± 5VAC
120〜274Vac
Frequency
40 〜60Hz
Power factor
0.99
Output
Voltage
220Vac (1 ± 2%)
220Vac (1 ±1%)
Current
4.55A
9.1A
13.6A
27.3A
45A
Frequency
(50 ± 2)Hz
(50±1)Hz
Power factor
0.9
Waveform
Pure Sine wave
Waveform distortion
Linear ≤7% when RCD 100% loading(Non-line)
Linear ≤3% when R 100% loading(line)
Delivery & Availability:Typically 10-21 working days – excluding furniture and heavy/bulky equipment. Please contact us for further information.
Shipped From Abroad
Features:
Optional 7 ” touch LCD
Online double-conversionDSP technology guarantees high reliability
True galvanic isolation transformer designControl designed to withstand all kinds of loads
Intelligent battery management to prolong battery lifecycle
Redundant fan design and independent ventilation enhance durable operation under harsh environment
Adiustable battery numbers
Accept dual-mains input
Parallel operation with up to 4 units ( option )
Variety of communication options available
Reverse phase frequency operation and supportsnon-neutral input
Delivery & Availability:Typically 10-21 working days – excluding furniture and heavy/bulky equipment. Please contact us for further information.
Shipped From AbroadFeatures:
DSP digital control technology enables UPS more stable performance-+
Environment friendly eco-designed
Active input power factor correction
Wide range of input voltage and frequency
Zero power switch delay
Adaptive Load Management.
Sufficient Expansion Slots: USB ,RS485 ,AS400 SNMP cards(Optional)
Support the generator
Delivery & Availability:Typically 10-21 working days – excluding furniture and heavy/bulky equipment. Please contact us for further information.
Shipped From Abroad
Delivery & Availability:Typically 10-21 working days – excluding furniture and heavy/bulky equipment. Please contact us for further information.
Shipped From Abroad
Delivery & Availability:Typically 10-21 working days – excluding furniture and heavy/bulky equipment. Please contact us for further information.
Content
`Features:
1)Adopts compact frame structure design.
2)Pure Sine wave output no matter in AC mode or battery mode can provide sine wave power source with low distortion.
3)Zero Transfer time: when the utility power is cut off or recover, there is absolutely no time between the transfer of AC mode and battery mode.
4)Detect function for the nneutral wire and wire wire are wrongly connected.
5)Avoids wrong connection of neutral wire and live wire of UPS AC power input.
6)Voltage breakthrough protection and strong anti-interference function.
7)Input power factor correction: UPS can correct the input power factor. Under full load, the input power factor can reach over 0.95.
Applications:
Mammogram
Ultrasound Equipments
Radiology rooms
Technical Specifications
Model
RT 1K
RT 1KL
RT 2K
RT 2KL
RT 3K
RT 3KL
RT 6KL
RT 10KL
Input
Rated capacity
1KVA/900W
2KVA/1800W
3KVA/2700W
6KVA/5.4KW
10KVA/9KW
Voltage
90 ± 5-300 ± 5VAC
120〜274Vac
Frequency
40 〜60Hz
Power factor
0.99
Output
Voltage
220Vac (1 ± 2%)
220Vac (1 ±1%)
Current
4.55A
9.1A
13.6A
27.3A
45A
Frequency
(50 ± 2)Hz
(50±1)Hz
Power factor
0.9
Waveform
Pure Sine wave
Waveform distortion
Linear ≤7% when RCD 100% loading(Non-line)
Linear ≤3% when R 100% loading(line)
100%-125%, 1 minutes to transfer to bypass;
> 150%, 300ms to transfer to bypass
Transfer time
0ms
Type of battery
VRLA
External battery voltage
24VDC
36VDC
4x7Ah
72VDC
6x7Ah
96VDC
192VDC/240VDC
Working Environment
Temperatures
0 〜40°C
Humidity
0 〜90(%)
Altitude
<1500m
Communication
RS232
Size (WXDXH)mm
482x450x88
482x650x132
Weight (kg)
12.3
8
9.5
10
10
10.5
20
21.5
Features:
Three Phase Hybrid Solar Inverter
Off grid three phase solar hybrid inverter with pwm/mppt can be used in single-phase and three-phase ac load with total power not exceeding 100kva/120kva/125kva/150kva/160kva,384vdc to 380vac.
•Pure sine wave output.
•Low DC voltage, saving system cost.
•Three phase solar inverter with built-in PWM or MPPT charge controller.
•AC charge current 0-45A adjustable.
•Wide LCD screen, clearly and precisely shows icon data.
•100%imbalance loading design, 3 times peak power.
•Setting different working modes based on variable usage requirements.
•DC first/AC first optional.
•Various communication ports and remote controls
50/60 Hz synchronised ±1 % With mains absent ±0.1 Hz
Max. Synchronisation Speed
±1 Hz/s
Waveform
Pure Sinewave
Total Harmonic Distortion (THDv)
<2% (Linear Load) ; <5% (Non-linear Load)
Phase Displacement
120° ±1 % (balanced load); 120° ±2% (imbalances 50% of the load)
Dynamic Recovery Time
Restore to 90% of rated value in 3 cycles
Overload capacity
110% for 10min; 150% for 60sec; >160% for 200ms
Admissible Crest Factor
3:1
Admissible Power Factor
0.6-1 (inductive or capacitive)
Imbalance Output Voltage @ 100% Unbalanced Load
<1%
Current Limit
High overload, short-circuit: RMS Voltage Limit; High Crest-Factor current: Peak Voltage Limit
STATIC BYPASS
Type
Solid state
Voltage
3 x 380VAC/400VAC (3Ph + N)
Frequency
50/60 Hz
Activation Criterion
Microprocessor control
Transfer Time
Zero
Admissible Overload
150% for 1 hour; 180% for 30sec; >200% for 200ms
Transfer to Bypass
Immediate, for overloads above 160%
Retransfer
Automatic after alarm clear
MAINTENANCE BYPASS
Type
Without interruption
Voltage
3 * 400V (3Ph + N)
Frequency
50/60 Hz
Overall Efficiency
Line Mode
90%
91%
92%
93%
Battery Mode
90%
91%
93%
93%
BATTERY & CHARGER
Battery Type and Numbers
12VDC * 32 pcs (29-32 pcs adjustable)
Nominal Battery Voltage
384 VDC (Based on 32pcs batteries)
Charging Method
CC/CV
Precision
±1%
Charging Current
Max.: 40 A
Charging Voltage
432 VDC (Based on 32pcs batteries)
PHYSICAL
Dimensions, D x W x H(mm)
656 x 405 x 817
656 x 405 x 941
840x432x1140
975x554x1286
1200x910x1680
1500x1140x1800
Net Weight (Kgs)
180
205
295
330
451
519
950
1350
Features:
DSP digital control technology enables UPS more stable performance-+
Environment friendly eco-designed
Active input power factor correction
Wide range of input voltage and frequency
Zero power switch delay
Adaptive Load Management.
Sufficient Expansion Slots: USB ,RS485 ,AS400 SNMP cards(Optional)
Support the generator
Specifications:
Model
33VT 10K
33VT 10KL
33VT 20K
33VT 20KL
33VT 30KL
33VT 40KL
Capacity
10KVA/9000W
20KVA/18KW
30KVA/27KW
40KVA/36KW
Input
Nominal Voltage
380/400/415Vac
Voltage Range
207-475VAC(3P4W+G)
Current
14A
28A
42A
67A
Frequency
40-70Hz (Adjustable)
Power Factor
≥0.99
Output
Voltage
380VAC 1±1% (3P4W+G)
Frequency
46-54Hz Synchronous mains power; 50Hz( Frequency Range 40-46Hz -54-60Hz);50Hz(Battery mode)
Current
15A
30A
45A
61A
Power Factor
0.9
Crest Factor
3:1
THD
Line load <3%
Chrage Current
5.5A
1A
7.5A
1A
5.5A
Battery Nominal Voltage
192VDC
±192VDC
Transfer Time
0ms
Overload Capacity
105%±5%< Load<125%±5% :1 min transfer to bypass
125% ±5% < Load<135 % ±5 % :30s transfer to bypass
Load > 135 % ± 5 %: 300s transfer to bypass
Communication
SNMP,RS-232,USB+lntelligent Slot
Operating Environment
Temperature
0°C~40°C
Humidity
20%~95%
Dimension
Width (mm)
260
260
260
260
Depth (mm)
560
533
710
560
Height (mm)
717
501
717
717
Net Weight(Kg)
26
72
57.5
98
58.5
62
Features:
Capacity: 1200W 1008Wh /315000mAh
Input AC Output Power:Rated Power 1200W Peak Power 2400W
Input AC Charging:AC100~125V/AC184~264V Bidirectional Inverter 700W Max
Input Car Charging:DC12V~24V/10A 240W Max
Input Solar Charging:DC12V~60V/10A 400W Max
Output Voltage:230VAC±10%/110VAC±10%
Output Frequency: 50Hz±5%/60Hz±5%
USB Output:2*5V2.4A +2*QC18W+2*PD60W Max
DC Output:1*Cigarette Lighter+2*DC5521 Rated Output (13.8V/10A Max)
Output Waveform:Pure Sine Wave
LED:3 Levels(H/M/L)+SOS
UPS Function:Support(≤10mS)
Applications:
Mammogram
Ultrasound Equipments
Radiology rooms
Description
HIGH INTELLIGENCE AND RELIABLE POWER SUPPLYIGBT Technology
Full microprocessor control with no-break static and manual bypasses.
Online double conversion technology (VFl) with isolation transformer on theinverter output.
Extremely high short-circuit current to ensure compatibility with the most diffificult transformer applications (lighting, drives and industrial processes) and an isolation transformer on the inverter output.
Compatibled with Watch & Save 3000 software as standard and can be remotely monitored using the Power NetGuard system from anywhere in the world.
SIMPLE TO INSTALL
Capability to install the UPS into any distribution system(neutral not required on rectifier input).
Capability to separate the rectifier/bypass power networks and to power them from two separate sources, without Galvanic isolation(Necessary on UPS without an output transformer
MAXIMUM BATTERY CARE
Battery deep discharge protection;
Temperature compensating charger;
Built-in automatic and manual battery test feature.
OTHER CHARACTERISTICS
0.8/0.9 power factor suitable for powering ICT and lndustrial loads.
BACK FEED protection: to avoid energy feeding back into the mains supply cause a fault occur.
MAXIMUM RELIABILITY AND AVAILABILITY
Connect up to 6 units in parallel or N+1 redundancy, even of different power ratings.
The UPS continue to work in parallel even if one of theinterconnecting communication cables is disconnected(CLOSED LOOP)
LOW CONSUMPTION LEVELS
LF31 Series UPS can achieve efficiencies >98% thanks to selectable Economy Mode which can be used in stable electrical environments to provide power supply continuity when the mains fail.
ADVANCE COMMUNICATION:
RS485/RS232/Dry Contact/SNMP(Optional)
Specifications
Model
10KVA
15KVA
20KVA
30KVA
40KVA
60KVA
80KVA
100KVA
Capacity
8KW
12 KW
16 KW
24 KW
32 KW
48 KW
64 KW
80 KW
INPUT
Rated voltage
380/400/415 VAC Three-phase
Voltage range
±20%
Frequency range
45-65Hz
Power factor
>0.92 with harmonic filter
Current harmonic distortion
<5% with harmonic filter
Soft Start
0 -100% in 10″
BYPASS INPUT
Rated voltage
230VAC Single Phase
Permitted voltage range
±15% (selectable from ±10% to ±25% from front panel)