Features:
- 60KW single power module in 3U
- N+1or N+X parallel redundancy for power guarantee
- Supports horizontal expansion by 1+1 cabinet paralleloperation.
- Hot-swappable modular design decreases MTTR
- High scalability
- Built-in maintenance bypass switch for easy maintenance without interruptible
- High efficiency double conversion online UPS
- Flexible battery configuration and adjustable charging current
- High overload capability
- Power walk-in function
- Built-in dynamic password protection
- Built-in ultra communication slot
Delivery & Availability:
Typically 10-21 working days – excluding furniture and heavy/bulky equipment. Please contact us for further information.
| Shipped From Abroad
Features:
- DSP digital control technology enables UPS more stable performance-+
- Environment friendly eco-designed
- Active input power factor correction
- Wide range of input voltage and frequency
- Zero power switch delay
- Adaptive Load Management.
- Sufficient Expansion Slots: USB ,RS485 ,AS400 SNMP cards(Optional)
- Support the generator
Delivery & Availability:
Typically 10-21 working days – excluding furniture and heavy/bulky equipment. Please contact us for further information.
| Shipped From Abroad
Features:
1)19 inches standard design of rack mount, compact structure.
2)Sin wave output provides best power supply guarantee.
3)Zero transfer time between mains mode and battery mode.
4)Detection function of input neutral wire and live wire.
5)Having voltage surge protection function and strong anti-interference function.
6)Equipped with correction function of input power factor
7) Supporting mobile smart monitoring card , users can real-time monitor every data of the UPS by mobile APP.
Delivery & Availability:
Typically 10-21 working days – excluding furniture and heavy/bulky equipment. Please contact us for further information.
|
Content | `Features:
1)Adopts compact frame structure design.
2)Pure Sine wave output no matter in AC mode or battery mode can provide sine wave power source with low distortion.
3)Zero Transfer time: when the utility power is cut off or recover, there is absolutely no time between the transfer of AC mode and battery mode.
4)Detect function for the nneutral wire and wire wire are wrongly connected.
5)Avoids wrong connection of neutral wire and live wire of UPS AC power input.
6)Voltage breakthrough protection and strong anti-interference function.
7)Input power factor correction: UPS can correct the input power factor. Under full load, the input power factor can reach over 0.95.
Applications:
- Mammogram
- Ultrasound Equipments
- Radiology rooms
Technical Specifications
Model |
RT 1K |
RT 1KL |
RT 2K |
RT 2KL |
RT 3K |
RT 3KL |
RT 6KL |
RT 10KL |
Input |
Rated capacity |
1KVA/900W |
2KVA/1800W |
3KVA/2700W |
6KVA/5.4KW |
10KVA/9KW |
Voltage |
90 ± 5-300 ± 5VAC |
120〜274Vac |
Frequency |
40 〜60Hz |
Power factor |
0.99 |
Output |
Voltage |
220Vac (1 ± 2%) |
220Vac (1 ±1%) |
Current |
4.55A |
9.1A |
13.6A |
27.3A |
45A |
Frequency |
(50 ± 2)Hz |
(50±1)Hz |
Power factor |
0.9 |
Waveform |
Pure Sine wave |
Waveform distortion |
Linear ≤7% when RCD 100% loading(Non-line)
Linear ≤3% when R 100% loading(line) |
Overload protection |
>105% <125% – 50s
>125% v 150% – 25s
>150% – 300ms |
100%-125%, 1 minutes to transfer to bypass;
> 150%, 300ms to transfer to bypass |
Transfer time |
0ms |
Type of battery |
VRLA |
External battery voltage |
24VDC |
36VDC |
4x7Ah |
72VDC |
6x7Ah |
96VDC |
192VDC/240VDC |
Working Environment |
Temperatures |
0 〜40°C |
Humidity |
0 〜90(%) |
Altitude |
<1500m |
Communication |
RS232 |
Size (WXDXH)mm |
482x450x88 |
482x650x132 |
Weight (kg) |
12.3 |
8 |
9.5 |
10 |
10 |
10.5 |
20 |
21.5 |
| Features:
Three Phase Hybrid Solar Inverter
Off grid three phase solar hybrid inverter with pwm/mppt can be used in single-phase and three-phase ac load with total power not exceeding 100kva/120kva/125kva/150kva/160kva,384vdc to 380vac.
•Pure sine wave output.
•Low DC voltage, saving system cost.
•Three phase solar inverter with built-in PWM or MPPT charge controller.
•AC charge current 0-45A adjustable.
•Wide LCD screen, clearly and precisely shows icon data.
•100%imbalance loading design, 3 times peak power.
•Setting different working modes based on variable usage requirements.
•DC first/AC first optional.
•Various communication ports and remote controls
Specifications
MODEL |
DX100KVA |
DX120KVA |
DX125KVA |
DX150KVA |
DX160KVA |
190KVA |
200KVA |
Rated Power |
80KW |
96KW |
100KW |
120KW |
128KW |
150KW |
160KW |
Peak Power(20ms) |
240KVA |
288KVA |
300KVA |
360KVA |
384KVA |
450KVA |
480KVA |
Start Motor |
40HP |
50HP |
50HP |
60HP |
60HP |
80HP |
80HP |
Battery Voltage |
384VDC |
Size(L*W*Hmm) |
875*720*1380 |
1123*900*1605 |
Packing Size(L*W*Hmm) |
980*825*1560 |
1185*960*1750 |
N.W.(kg) |
512 |
592 |
612 |
612 |
642 |
705 |
755 |
G.W.(kg)(Wooden Packing) |
552 |
632 |
652 |
652 |
692 |
755 |
805 |
INPUT |
DC Input Voltage Range |
10.5VDC-15VDC(Single battery voltage) |
AC Input Voltage Range |
380Vac/400Vac±10%(customized 190Vac/200Vac) |
AC Input Frequency Range |
45Hz-55Hz(50Hz)/ 55Hz-65Hz(60Hz) |
Max AC charging current |
0-45A(Depending on the model) |
AC charging method |
Three-stage (constant current, constant voltage, floating charge) |
Phase |
3 PHASE |
OUTPUT |
Efficiency(Battery Mode) |
≥85% |
Output Voltage(Battery Mode) |
380Vac/400Vac±10%(customized 190Vac/200Vac) |
Output Frequency(Battery Mode) |
50/60Hz ±1% |
Output Wave(Battery Mode) |
Pure Sine Wave |
Output waveform distortion |
Linear load≤3% |
Efficiency(AC Mode) |
>99% |
Output Voltage(AC Mode) |
Conforming to AC input |
Output Frequency(AC Mode) |
Conforming to AC input |
No load loss(Battery Mode) |
≤1% rated power |
No load loss(AC Mode) |
≤2%rated power( charger does not work in AC mode) |
No load loss
(Energy saving Mode) |
≤10W |
Phase |
3 PHASE |
BATTERY |
VRLA Battery |
Charge Voltage :13.8V; Float Voltage:13.7V(Single battery voltage) |
Customize battery |
Charging and discharging parameters of different types of batteries can be customized according to user requirements |
(charging and discharging parameters of different types of batteries can be set through the operation panel) |
Protection |
Battery undervoltage alarm |
11V(Single battery voltage) |
Battery undervoltage protection |
10.5V(Single battery voltage) |
Battery overvoltage alarm |
15V(Single battery voltage) |
Battery overvoltage protection |
17V(Single battery voltage) |
Battery overvoltage recovery voltage |
14.5V(Single battery voltage) |
Overload power protection |
Automatic protection (battery mode), circuit breaker or insurance (AC mode) |
Inverter output short circuit protection |
Automatic protection (battery mode), circuit breaker or insurance (AC mode) |
Temperature protection |
>90°C(Shut down output) |
Alarm |
A |
Normal working condition, buzzer has no alarm sound |
B |
Buzzer sounds 4 times per second when battery failure, voltage abnormality, overload protection |
C |
When the machine is turned on for the first time, the buzzer will prompt 5
when the machine is normal |
Inside Solar controller |
Charging Mode |
MPPT or PWM |
(Optional) |
Charging current |
PWM: 100A-200A / MPPT: 50A/100A |
|
PV Input Voltage Range |
PWM: 480V-704V / MPPT: 480V-640V |
|
Max PV Input Voltage(Voc) |
PWM: 750V / MPPT: 800V |
|
(At the lowest temperature) |
|
PV Array Maximum Power |
PWM: 44.8KW(100A)/33.6KW*2(150A)/44.8KW*2(200A)) / (MPPT: 22.4KW(50A)/22.4KW*2(100A) |
|
Standby loss |
≤3W |
|
Maximum conversion efficiency |
>95% |
Working Mode |
Battery First/AC First/Saving Energy Mode |
Transfer Time |
≤4ms |
Display |
LCD |
Thermal method |
Forced Air Cooling |
Communication(Optional) |
RS485/APP(WIFI monitoring or GPRS monitoring) |
Environment |
Operating temperature |
-10℃~40℃ |
Storage temperature |
-15℃~60℃ |
Noise |
2000m(More than derating) |
Elevation |
≤65dB |
Humidity |
0%~95% ,No condensation |
| Features:
Digital Control
All parts of this series of UPS adopt digital control, each performance index of UPS is very excellent, and the control system is morestableand reliable.Each module has built-in
automatic bypass switch and corresponding bypass current equalizing inductor, providing good bypass power supply equalization performance.
Intelligent Battery Management
Users can set the charging current, constant current, constant voltage and floatingcharging modescan be automatically and smoothly switched; Battery voltage can beset
±192Vdc/±240Vdc/±216Vdc/±228Vdc/±240Vdc (32/34/36/38/40 pcs optional)
High Power Density Modular Design
The capacity of each single module is30kVA, and the height is3U; UPS modulescan be added and removed onlineto achieve zero maintenance time.
N+x Parallel Redundancy
The quantity of redundant module can be set accordingly, When the redundant module reaches more than 2 hours, the system availability achieves 99.99%,
MTBF(Mean Time Between Failures) lasts more than 250,000 hours; Supporting parallel connection between cabinets.
A maximum of four cabinets can be parallel,and battery pack can be shared when UPS cabinet in parallel.
Touchable LCD Display Screen
Super large LCD display with touching function.
Standard Cabinet Design
The appearance ofthe standard cabinet is beautiful and generous, which can perfectly match the use environment ofthe computer room and save the space.
Safe and Easy to Maintain
When an emergency occurs, users can switch to the maintenance bypass to supply power, and maintenance personnel can safely perform online maintenance;
Press EPO button to shutdown in emergentsituation, and also have REPO function.
Intelligent Management
Centralized monitoring module (with hot-swap function), RS232/RS485 communication interface/SNMPcard (optional), can realize remote monitoringof UPS, relay card is optional.
Technical Specifications
Model |
VM 90K |
VM150K |
VM300K |
Capacity |
UPS Cabinet |
30-90KVA |
30-150KVA |
30-300KVA |
Power Module |
30kVA |
INPUT |
Input Form |
3P4W+G |
Rated Voltage |
380/400/415Vac |
Voltage Range |
207~478Vac |
Frequency Range |
40~70Hz |
Input Power Factor |
≥0.99 |
Bypass Range |
380 upper limit: 25% (optional +10%s +15%、+20%)
400 upper limit: 20% (optional +10%、+15%)
415 upper limit: 15% (optional +10%) Lower limit: -45% (optional -20%s -30%)
Bypass frequency protection range: ± 10% |
Input Current Harmonic Wave |
≤3% (100% non-linear) |
OUTPUT |
Output Form |
3P4W+G |
Rated Voltage |
380/400/415Vac |
Output Power Factor |
0.9 or 1 |
Voltage Accuracy |
±1% |
Output Frequency |
Mains Mode |
Synchronization with input; when mains frequency exceeds maximum value ±10%
(can be set ±1%、 ±2%、±4%、±5%), output frequency 50X(±0.2%)Hz |
Battery Mode |
(50/60±0.2%) Hz |
Crest Factor |
3:1 |
Conversion Time |
Mains mode — bypass mode: 0ms (tracking); Mains mode— battery mode: 0ms |
Overload Capacity |
Load≤110%: 60 mins;
Load≤125%: 10 mins;
Load≤150%: 1 min;
Load≥150%, shutdown immediately |
Output Voltage Harmonic Wave |
≤2% (100% linear) |
Efficiency |
In normal mode 95% |
Communication Port |
RS232、RS485、 Intelligent Slot*2 、 Dry connect port |
BATTERY |
Battery Voltage |
±192Vdc/±204Vdc/±216Vdc/±228Vdc/±240Vdc; (32/34/36/38/40pcs Optional) |
Charging Current |
UPS Cabinet |
30A Max |
50A Max |
100A Max |
Power Module |
10A Max |
Environment |
Operating Temperature |
0〜40°C |
Relative Humidity |
0-95% (non-condensing) |
Storage Temperature |
-25-55°C (excluded battery) |
Altitude |
< 1500m (derating if exceeding 1500m) |
Physical Characteristic |
Outer Dimension (LxWxH) mm |
Cabinet |
840X600X1400 |
1100X600X2000 |
Module |
580 X 443 X 131 |
Weight
(Net Weight) KG |
Cabinet |
158 |
170 |
305 |
Module |
33.5 |
Operative Standard |
YD/T 2165-2010 |
| Features:
- 60KW single power module in 3U
- N+1or N+X parallel redundancy for power guarantee
- Supports horizontal expansion by 1+1 cabinet paralleloperation.
- Hot-swappable modular design decreases MTTR
- High scalability
- Built-in maintenance bypass switch for easy maintenance without interruptible
- High efficiency double conversion online UPS
- Flexible battery configuration and adjustable charging current
- High overload capability
- Power walk-in function
- Built-in dynamic password protection
- Built-in ultra communication slot
Technical Specifications
MODEL |
RM Pro 120K |
RM Pro 180K |
RM Pro 300K |
RM Pro 420K |
RM Pro 480K |
RM Pro 600K |
Phase |
3 Phase in / 3 Phase out |
Cabinet Capacity* |
120 KW |
180 KW |
300KW |
420KW |
480KW |
600KW |
Battery Type |
Extemal Battery |
One Power Module Capacity |
60KVA/60KW |
Max. Power Module No. |
2 |
3 |
5 |
7 |
8 |
10 |
INPUT |
Nominal Voltage |
3×380/400/415 VAC(3Ph+N) |
Voltage Range |
-30%~+20% |
Nominal Frequency |
50/60Hz(Auto Sensing) |
Frequency Range |
40Hz~70Hz |
Power Factor |
>0.99 @100% Load, >0.98 @ 50% Load |
Harmonic Distortion (THDi) |
<3%@ 100% load |
OUTPUT |
Nominal Voltage |
3×380/400/415 VAC (3Ph+N) |
Voltage Regulation(Steady State) |
≤±1% Typical(balanced load); ≤±2% Typical(unbalanced load) |
Nominal Frequency |
50/60Hz |
Frequency Range(Synchronized) |
46Hz~54Hz or 56Hz~64Hz |
Overload Capability |
1 hour for ≤110%,10 mins for 111%~125%,1 min for 126%~150% and 200ms for >150% |
Haronic Distortion |
≤2% THD (Linear Load); ≤4% THD (Non-linear Load) |
Eficiency |
96% |
BATTERY / CHARGER |
Nominal Voltage |
’+/- 192V~+/- 240V(Selectable) |
Maximum Voltage |
’+/- 240V (12V×40 PCS) |
Minimum Voltage |
‘+/-192V (12V×32 PCS) |
Floating Charge Voltage |
2.28V/Cell (2.25~2.33 Selectable) |
Boost Charging Voltage |
2.35V/Cell |
Temperature Compensation |
Yes |
Maximum Charging Current
(Per Power Module) |
18A(Adjustable) |
PHYSICAL |
Cabinet Dimension (DxWxH)mm |
1100x600x1475 |
1100x600x1475 |
1100x600x2010 |
1100×600×2010 |
1065x1000x2000 |
1065×1000×2000 |
Net Weight (Kg) |
308 |
352 |
516 |
654 |
932 |
1020 |
Power Module (PM-60) Net Weight |
44KGS |
ENVIRONMENT |
Operating Temperature |
0~40℃ |
Relative Humidity |
0~95% non-condensing |
Altitude* |
<1000m for Nominal power |
IP Protection |
IP 20 |
MANAGEMENT |
Smart RS-232/USB |
Supports Windows⑧ Family, Linux and MAC |
Optional SNMP |
Power management from SNMP manager and web browser |
STANDARDS |
Safety |
IEC/EN62040-1 |
EMC |
IEC/EN 62040-2 Category C3 |
| Features:
- DSP digital control technology enables UPS more stable performance-+
- Environment friendly eco-designed
- Active input power factor correction
- Wide range of input voltage and frequency
- Zero power switch delay
- Adaptive Load Management.
- Sufficient Expansion Slots: USB ,RS485 ,AS400 SNMP cards(Optional)
- Support the generator
Specifications:
Model |
33VT 10K |
33VT 10KL |
33VT 20K |
33VT 20KL |
33VT 30KL |
33VT 40KL |
Capacity |
10KVA/9000W |
20KVA/18KW |
30KVA/27KW |
40KVA/36KW |
Input |
Nominal Voltage |
380/400/415Vac |
Voltage Range |
207-475VAC(3P4W+G) |
Current |
14A |
28A |
42A |
67A |
Frequency |
40-70Hz (Adjustable) |
Power Factor |
≥0.99 |
Output |
Voltage |
380VAC 1±1% (3P4W+G) |
Frequency |
46-54Hz Synchronous mains power; 50Hz( Frequency Range 40-46Hz -54-60Hz);50Hz(Battery mode) |
Current |
15A |
30A |
45A |
61A |
Power Factor |
0.9 |
Crest Factor |
3:1 |
THD |
Line load <3% |
Chrage Current |
5.5A |
1A |
7.5A |
1A |
5.5A |
Battery Nominal Voltage |
192VDC |
±192VDC |
Transfer Time |
0ms |
Overload Capacity |
105%±5%< Load<125%±5% :1 min transfer to bypass
125% ±5% < Load<135 % ±5 % :30s transfer to bypass
Load > 135 % ± 5 %: 300s transfer to bypass |
Communication |
SNMP,RS-232,USB+lntelligent Slot |
Operating Environment |
Temperature |
0°C~40°C |
Humidity |
20%~95% |
Dimension |
Width (mm) |
260 |
260 |
260 |
260 |
Depth (mm) |
560 |
533 |
710 |
560 |
Height (mm) |
717 |
501 |
717 |
717 |
Net Weight(Kg) |
26 |
72 |
57.5 |
98 |
58.5 |
62 |
| Features:
1)19 inches standard design of rack mount, compact structure.
2)Sin wave output provides best power supply guarantee.
3)Zero transfer time between mains mode and battery mode.
4)Detection function of input neutral wire and live wire.
5)Having voltage surge protection function and strong anti-interference function.
6)Equipped with correction function of input power factor
7) Supporting mobile smart monitoring card , users can real-time monitor every data of the UPS by mobile APP.
Technical Specifications
Model |
RTX3110KL |
RTX3115KL |
RTX3120KL |
Rated Power |
10kVA/9kW |
15kVA/13.5kW |
20kVA/18kW |
INPUT |
Voltage Range |
207-475Vac3P4W+G |
Working Frequency Range |
40-70HZ (settable) |
Input Power Factor |
>0.95 |
OUTPUT |
Rated Voltage and Accuracy |
220Vac(l±l%)lP2W+G |
Output Frequency |
46-54Hz synchronize with mains power; 50Hz (Mains power between 40-46Hz and 54-60Hz); 50Hz(Battery) |
Rated Current |
45A |
68A |
91A |
Output Power Factor |
0.9 |
Output Harmonic Wave |
W3% |
Crest Factor |
3:1 |
Output Overload |
105%±5%<Load≤125%±5%: Convert to bypass output and alarm after 1 min;
125%±5%<Load ≤50%±5%: Convert to bypass output and alarm after 30s;
Load>150%±5%: Convert to bypass output and alarm after 300ms. |
Transfer Time |
0ms |
Efficiency |
>92% |
BATTERY |
Rated Voltage |
192Vdc |
Quantity |
16 |
Charging Current |
5.5A |
Dimension (LxWxH) mm |
665*482.6*132.5 |
655*482.6*265 |
Weight |
23kg |
34kg |
35kg |
Working Temperature |
0°〜40°C |
Working Humidity |
20% 〜95% |
Noise |
≤60dB |
|