Single Phase Low Frequency Pure Sine Wave Inverter VH Series

$0.00

Shipped From Abroad

Delivery & Availability:
Typically 10-21 working days – excluding furniture and heavy/bulky equipment. Please contact us for further information.
SF1033560130139-30
Brands:: Reeco Power

Description

Features:

• Pure sine wave output.Rated power: 1KW to 12KW(12V/24V/48V/96V)
• Big AC Charging current 5-35A,5-40A,5-50A,5-60A(optional)
• Have UPS function AC to DC automatic conversion
• Wide AC voltage& frequency for AC and generator input
• Can adjust battery voltage for different types of batteriesfsuch as Lead-acid battery (default)/Gel battery/Lithium battery.
• DC Start & Automatic Self-Diagnostic function ,5 working modes can choose
(01 City power priority /02 Energy saving /03: Battery priority 04 City power priority Unattended mode /05 Battery priority Unattended)
• High Efficiency Design & “Power Saving Mode” to Conserve Energy
• Smart LCD display and setting(Working modes, Charge Current,Charge Voltage,AC range input, battrty voltage,Battery low voltage shutdown etc.)
• High-low voltage protection,overload, short-circuit Protection under-voltage and over-temperature protection,over voltage,battery reverse connection(optional)etc.
• Support RS485 monitoring function with program,remote monitoring (optional)

 

Technical Specifications
Model VH
1000W
VH
1500W
VH
2000W
VH
3000W
VH
4000W
VH
5000W
VH
6000W
VH
8000W
VH
10000W
 VH
12000W
INPUT Rated Capacity 1000W 1500W 2000W 3000W 4000W 5000W 6000W 8000W 10000W 12000W
Peak Power 3000W 4500W 6000W 9000W 12000W 15000W 18000W 24000W 30000W 36000W
Power Range 110VAC:83V-137VAC 120VAC :90 V-150 VAC
220VAC:165V-275VAC 230VAC:173V-287VAC
110VAC:88V-132VAC
120VAC:96V-144VAC
220VAC:176V-264VAC
230VAC:184V-276VAC
AC frequency range 45-65HZ
Efficiency >85%
BATTERY Type Lead Acid battery / GEL battery / Lithium battery
DC Voltage 12VDC/24VDC 24VDC/48VDC 48VDC/96VDC
Input voltage range 12VDC:10.5-15VDC 24VDC:21-30VDC 48VDC:42-60VDC 96VDC:84-120VDC
Floating charge set 12V:12.9 〜13.6 V   24V:25.8V〜27.2V    48V:51.6V〜54.4V   96V: 103.2V〜108.8V
Low voltage restored 12VDC:12.6-14.4VDC 24VDC:25.2-28.8VDC 48VDC:50.4-57.6VDC 96VDC:100.8-115.2VDC
Low voltage shutdown set 12VDC: 10-10.9V       24VDC:20-21.8V    48VDC:40-43.6V  96VDC:80V-87.2V
over voltage protection 12VDC:16.7VDC 24VDC:33.4V 48VDC:66.8V
over voltage alarm 12VDC:15VDC 24VDC:30V    48VDC:60V
AC Charging 5A-35A(40A, 50A, 60A.70A Optional)
OUTPUT Capable of starting
electric motor
0.5HP 1HP 1.5HP 2HP 3HP
AVR Voltage Range 110/120/220/230/240VAC ±110% (Auto-sensing) Without
Power Factor 100%
Transfer Time Typical: 5ms(lncluding detection time)
Temperature Protection >85°C alarm >90°C machine shut off
Overload IPS automatically shut down if overload exceeds 110%-120% of normal value for 30 seconds,
IPS automatically resume work if overload comes to rated load.
Wave form Pure sine wave
Frequency Commercial power supply: shared frequency with the commercial inversion state:60/50±0.5
Output frequency range (electric supply mode) Tracking automatically
Protection Overload, short circuit, battery high and low voltage, AC input high and low voltage protection
Conversion Method Interactive
Temperature Operating Temperature 0°C~70°C
Thermal method Cooling fan in intelligent control<42°C fan rotates slowly to >45°C fan rotates fast
Appearance External Size(mm) (L*W*H) 510*325*215mm 645*325*215mm 765*320*250mm
Gross Size(mm)
(L*W*H)
560*380*280mm 730*400*290mm 840*405*320mm
Net weight(kg) 14 15 18 20 31 34 35 52 54 56
Gross weight(kg) 16 17 20 22 35 37 38 56 58 60

Reviews

There are no reviews yet.

Be the first to review “Single Phase Low Frequency Pure Sine Wave Inverter VH Series”

Your email address will not be published. Required fields are marked *

Quick Comparison

Single Phase Low Frequency Pure Sine Wave Inverter VH Series remove3 Phase Low Frequency Online UPS LF33 Series removeBattery Cabinet battery Rack B1-B40 (Support Customized Size) removeHigh Frequency Modular UPS VM Series removeHigh Frequency Rack Mount UPS RTX Series remove3 Phase Low Frequency Online UPS LD33 Series remove
NameSingle Phase Low Frequency Pure Sine Wave Inverter VH Series remove3 Phase Low Frequency Online UPS LF33 Series removeBattery Cabinet battery Rack B1-B40 (Support Customized Size) removeHigh Frequency Modular UPS VM Series removeHigh Frequency Rack Mount UPS RTX Series remove3 Phase Low Frequency Online UPS LD33 Series remove
Image
SKUSF1033560130139-30SF1033560130139-4SF1033560130139-9SF1033560130139-11SF1033560130139-13SF1033560130139-3
Rating
Price

$0.00

$0.00

$0.00

$0.00

$0.00

$0.00

Stock
Availability
Add to cart

DescriptionShipped From Abroad
Delivery & Availability: Typically 10-21 working days – excluding furniture and heavy/bulky equipment. Please contact us for further information.
Shipped From Abroad
Features:
  • Optional 7 ” touch LCD
  • Online double-conversionDSP technology guarantees high reliability
  • True galvanic isolation transformer designControl designed to withstand all kinds of loads
  • Intelligent battery management to prolong battery lifecycle
  • Redundant fan design and independent ventilation enhance durable operation under harsh environment
  • Adiustable battery numbers
  • Accept dual-mains input
  • Parallel operation with up to 4 units ( option )
  • Variety of communication options available
  • Reverse phase frequency operation and supportsnon-neutral input
Delivery & Availability: Typically 10-21 working days – excluding furniture and heavy/bulky equipment. Please contact us for further information.
Shipped From Abroad
Features:
  • The battery cabinet is made of metal material, strong and can bear up to 500KG.
  • The battery cabinet is assembled in the form of assembly, which is conven-ient for transportation and simple for assembly.
  • The surface of electrostatic spraying, strong rust resistance, color can be fixed spray.
  • Other sizes can be customized.
Delivery & Availability: Typically 10-21 working days – excluding furniture and heavy/bulky equipment. Please contact us for further information.
Shipped From Abroad
Delivery & Availability: Typically 10-21 working days – excluding furniture and heavy/bulky equipment. Please contact us for further information.
Shipped From Abroad
Features:
1)19 inches standard design of rack mount, compact structure. 2)Sin wave output provides best power supply guarantee. 3)Zero transfer time between mains mode and battery mode. 4)Detection function of input neutral wire and live wire. 5)Having voltage surge protection function and strong anti-interference function. 6)Equipped with correction function of input power factor 7) Supporting mobile smart monitoring card , users can real-time monitor every data of the UPS by mobile APP.
Delivery & Availability: Typically 10-21 working days – excluding furniture and heavy/bulky equipment. Please contact us for further information.
Shipped From Abroad
Delivery & Availability: Typically 10-21 working days – excluding furniture and heavy/bulky equipment. Please contact us for further information.
Content
Features:
• Pure sine wave output.Rated power: 1KW to 12KW(12V/24V/48V/96V) • Big AC Charging current 5-35A,5-40A,5-50A,5-60A(optional) • Have UPS function AC to DC automatic conversion • Wide AC voltage& frequency for AC and generator input • Can adjust battery voltage for different types of batteriesfsuch as Lead-acid battery (default)/Gel battery/Lithium battery. • DC Start & Automatic Self-Diagnostic function ,5 working modes can choose (01 City power priority /02 Energy saving /03: Battery priority 04 City power priority Unattended mode /05 Battery priority Unattended) • High Efficiency Design & “Power Saving Mode” to Conserve Energy • Smart LCD display and setting(Working modes, Charge Current,Charge Voltage,AC range input, battrty voltage,Battery low voltage shutdown etc.) • High-low voltage protection,overload, short-circuit Protection under-voltage and over-temperature protection,over voltage,battery reverse connection(optional)etc. • Support RS485 monitoring function with program,remote monitoring (optional)  
Technical Specifications
Model VH 1000W VH 1500W VH 2000W VH 3000W VH 4000W VH 5000W VH 6000W VH 8000W VH 10000W  VH 12000W
INPUT Rated Capacity 1000W 1500W 2000W 3000W 4000W 5000W 6000W 8000W 10000W 12000W
Peak Power 3000W 4500W 6000W 9000W 12000W 15000W 18000W 24000W 30000W 36000W
Power Range 110VAC:83V-137VAC 120VAC :90 V-150 VAC 220VAC:165V-275VAC 230VAC:173V-287VAC 110VAC:88V-132VAC 120VAC:96V-144VAC 220VAC:176V-264VAC 230VAC:184V-276VAC
AC frequency range 45-65HZ
Efficiency >85%
BATTERY Type Lead Acid battery / GEL battery / Lithium battery
DC Voltage 12VDC/24VDC 24VDC/48VDC 48VDC/96VDC
Input voltage range 12VDC:10.5-15VDC 24VDC:21-30VDC 48VDC:42-60VDC 96VDC:84-120VDC
Floating charge set 12V:12.9 〜13.6 V   24V:25.8V〜27.2V    48V:51.6V〜54.4V   96V: 103.2V〜108.8V
Low voltage restored 12VDC:12.6-14.4VDC 24VDC:25.2-28.8VDC 48VDC:50.4-57.6VDC 96VDC:100.8-115.2VDC
Low voltage shutdown set 12VDC: 10-10.9V       24VDC:20-21.8V    48VDC:40-43.6V  96VDC:80V-87.2V
over voltage protection 12VDC:16.7VDC 24VDC:33.4V 48VDC:66.8V
over voltage alarm 12VDC:15VDC 24VDC:30V    48VDC:60V
AC Charging 5A-35A(40A, 50A, 60A.70A Optional)
OUTPUT Capable of starting electric motor 0.5HP 1HP 1.5HP 2HP 3HP
AVR Voltage Range 110/120/220/230/240VAC ±110% (Auto-sensing) Without
Power Factor 100%
Transfer Time Typical: 5ms(lncluding detection time)
Temperature Protection >85°C alarm >90°C machine shut off
Overload IPS automatically shut down if overload exceeds 110%-120% of normal value for 30 seconds, IPS automatically resume work if overload comes to rated load.
Wave form Pure sine wave
Frequency Commercial power supply: shared frequency with the commercial inversion state:60/50±0.5
Output frequency range (electric supply mode) Tracking automatically
Protection Overload, short circuit, battery high and low voltage, AC input high and low voltage protection
Conversion Method Interactive
Temperature Operating Temperature 0°C~70°C
Thermal method Cooling fan in intelligent control<42°C fan rotates slowly to >45°C fan rotates fast
Appearance External Size(mm) (L*W*H) 510*325*215mm 645*325*215mm 765*320*250mm
Gross Size(mm) (L*W*H) 560*380*280mm 730*400*290mm 840*405*320mm
Net weight(kg) 14 15 18 20 31 34 35 52 54 56
Gross weight(kg) 16 17 20 22 35 37 38 56 58 60
Features:
  • Optional 7 ” touch LCD
  • Online double-conversionDSP technology guarantees high reliability
  • True galvanic isolation transformer designControl designed to withstand all kinds of loads
  • Intelligent battery management to prolong battery lifecycle
  • Redundant fan design and independent ventilation enhance durable operation under harsh environment
  • Adiustable battery numbers
  • Accept dual-mains input
  • Parallel operation with up to 4 units ( option )
  • Variety of communication options available
  • Reverse phase frequency operation and supportsnon-neutral input
 
Specifications
MODEL LF33 10K LF33 20K LF33 30K LF33 40K LF33  60K LF33  80K LF33 100K LF33 120K LF33 160K LF33 200K
CAPACITY 10KVA /8KW 20KVA /16KW 30KVA /24KW 40KVA /32KW 60KVA /48KW 80KVA /64KW 100KVA /80KW 120KVA /96KW 160KVA /128KW 200KVA /160KW
INPUT
Nominal Voltage 3 x 380VAC/400VAC (3Ph + N)
Acceptable Voltage Range 305VAC ~ 460VAC
Frequency 46-54Hzor56-64Hz
INVERTER
Nominal Voltage 3 x 380VAC/400VAC (3Ph + N)
Precision Stationary: ±1% Transitory: ±5% (load variations 100-0-100%)
Frequency 50/60 Hz synchronised ±1 % With mains absent ±0.1 Hz
Max. Synchronisation Speed ±1 Hz/s
Waveform Pure Sinewave
Total Harmonic Distortion (THDv) <2% (Linear Load) ; <5% (Non-linear Load)
Phase Displacement 120° ±1 % (balanced load); 120° ±2% (imbalances 50% of the load)
Dynamic Recovery Time Restore to 90% of rated value in 3 cycles
Overload capacity 110% for 10min; 150% for 60sec; >160% for 200ms
Admissible Crest Factor 3:1
Admissible Power Factor 0.6-1 (inductive or capacitive)
Imbalance Output Voltage @ 100% Unbalanced Load                    <1%
Current Limit High overload, short-circuit: RMS Voltage Limit; High Crest-Factor current: Peak Voltage Limit
STATIC BYPASS
Type Solid state
Voltage 3 x 380VAC/400VAC (3Ph + N)
Frequency 50/60 Hz
Activation Criterion Microprocessor control
Transfer Time Zero
Admissible Overload 150% for 1 hour; 180% for 30sec; >200% for 200ms
Transfer to Bypass Immediate, for overloads above 160%
Retransfer Automatic after alarm clear
MAINTENANCE BYPASS
Type Without interruption
Voltage 3 * 400V (3Ph + N)
Frequency 50/60 Hz
Overall Efficiency Line Mode 90% 91% 92% 93%
Battery Mode 90% 91% 93% 93%
BATTERY & CHARGER
Battery Type and Numbers 12VDC * 32 pcs (29-32 pcs adjustable)
Nominal Battery Voltage 384 VDC (Based on 32pcs batteries)
Charging Method CC/CV
Precision ±1%
Charging Current Max.: 40 A
Charging Voltage 432 VDC (Based on 32pcs batteries)
PHYSICAL
Dimensions, D x W x H(mm) 656 x 405 x 817 656 x 405 x 941 840x432x1140 975x554x1286 1200x910x1680 1500x1140x1800
Net Weight (Kgs) 180 205 295 330 451 519 950 1350
Features:
  • The battery cabinet is made of metal material, strong and can bear up to 500KG.
  • The battery cabinet is assembled in the form of assembly, which is conven-ient for transportation and simple for assembly.
  • The surface of electrostatic spraying, strong rust resistance, color can be fixed spray.
  • Other sizes can be customized.
 
Technical Specifications
Model Dimensions(W*D*H) (mm) Battery Capacity Battery Numbers Weight(kg)
B-1B 280x190x220 24AH/17AH 2/3PCS 2.2
B-1 435x210x270 17AH/24AH/38AH 5/3/2 PCS 3.3
65AH/100AH 1PC
B-1A 540x210x230 17AH/24AH/38AH 6/4/3PCS 4.5
B-2 450x470x320 17AH/24AH/38AH 10/6/4 PCS 7
65AH/100AH 2PCS
B-3 585x470x320 17AH/24AH/38AH 14/8/6PCS 9
65AH/100AH 3PCS
B-4 450x470x615 17AH/24AH/38AH 20/12/8PCS 15
65AH/100AH 4PCS
B-6 585x470x615 17AH/24AH/38AH 28/16/12PCS 18
65AH/100AH 6PCS
B-8 780x470x615 17AH/24AH/38AH 44/28/20PCS 21
65AH/100AH 8PCS
B-10 950x470x615 17AH/24AH/38AH 44/28/20PCS 24
65AH/100AH 10PCS
B-12 780x470x910 24AH/38AH 30/24PCS 32
65AH/100AH 12PCS
B-16 780x470x1190 24AH/38AH 40/32PCS 45
65AH/100AH 16PCS
B-20 950x470x1190 24AH/38AH 56/40PCS 50
65AH/100AH 20PCS
B-24 1150x470x1190 65AH/100AH 24PCS 57
B-32 780x880x1190 65AH/100AH 32PCS 95
B-40 950x880x1190 65AH/100AH 40PCS 100
Features:
Digital Control All parts of this series of UPS adopt digital control, each performance index of UPS is very excellent, and the control system is morestableand reliable.Each module has built-in automatic bypass switch and corresponding bypass current equalizing inductor, providing good bypass power supply equalization performance. Intelligent Battery Management Users can set the charging current, constant current, constant voltage and floatingcharging modescan be automatically and smoothly switched; Battery voltage can beset ±192Vdc/±240Vdc/±216Vdc/±228Vdc/±240Vdc (32/34/36/38/40 pcs optional) High Power Density Modular Design The capacity of each single module is30kVA, and the height is3U; UPS modulescan be added and removed onlineto achieve zero maintenance time. N+x Parallel Redundancy The quantity of redundant module can be set accordingly, When the redundant module reaches more than 2 hours, the system availability achieves 99.99%, MTBF(Mean Time Between Failures) lasts more than 250,000 hours; Supporting parallel connection between cabinets. A maximum of four cabinets can be parallel,and battery pack can be shared when UPS cabinet in parallel. Touchable LCD Display Screen Super large LCD display with touching function. Standard Cabinet Design The appearance ofthe standard cabinet is beautiful and generous, which can perfectly match the use environment ofthe computer room and save the space.

Safe and Easy to Maintain When an emergency occurs, users can switch to the maintenance bypass to supply power, and maintenance personnel can safely perform online maintenance; Press EPO button to shutdown in emergentsituation, and also have REPO function. Intelligent Management Centralized monitoring module (with hot-swap function), RS232/RS485 communication interface/SNMPcard (optional), can realize remote monitoringof UPS, relay card is optional.

 
Technical Specifications
Model VM 90K VM150K VM300K
Capacity UPS Cabinet 30-90KVA 30-150KVA 30-300KVA
Power Module 30kVA
INPUT Input Form 3P4W+G
Rated Voltage 380/400/415Vac
Voltage Range 207~478Vac
Frequency Range 40~70Hz
Input Power Factor ≥0.99
Bypass Range 380 upper limit: 25% (optional +10%s +15%、+20%) 400 upper limit: 20% (optional +10%、+15%) 415 upper limit: 15% (optional +10%) Lower limit: -45% (optional -20%s -30%) Bypass frequency protection range: ± 10%
Input Current Harmonic Wave ≤3% (100% non-linear)
OUTPUT Output Form 3P4W+G
Rated Voltage 380/400/415Vac
Output Power Factor 0.9 or 1
Voltage Accuracy ±1%
Output Frequency Mains Mode Synchronization with input; when mains frequency exceeds maximum value ±10% (can be set ±1%、 ±2%、±4%、±5%), output frequency 50X(±0.2%)Hz
Battery Mode (50/60±0.2%) Hz
Crest Factor 3:1
Conversion Time Mains mode — bypass mode: 0ms (tracking); Mains mode— battery mode: 0ms
Overload Capacity Load≤110%: 60 mins; Load≤125%: 10 mins; Load≤150%: 1 min; Load≥150%, shutdown immediately
Output Voltage Harmonic Wave ≤2% (100% linear)
Efficiency In normal mode 95%
Communication Port RS232、RS485、 Intelligent Slot*2 、 Dry connect port
BATTERY Battery Voltage ±192Vdc/±204Vdc/±216Vdc/±228Vdc/±240Vdc; (32/34/36/38/40pcs Optional)
Charging Current UPS Cabinet 30A Max 50A Max 100A Max
Power Module 10A Max
Environment Operating Temperature 0〜40°C
Relative Humidity 0-95% (non-condensing)
Storage Temperature -25-55°C (excluded battery)
Altitude < 1500m (derating if exceeding 1500m)
Physical Characteristic Outer Dimension (LxWxH) mm Cabinet 840X600X1400 1100X600X2000
Module 580 X 443 X 131
Weight (Net Weight) KG Cabinet 158 170 305
Module 33.5
Operative Standard YD/T 2165-2010
Features:
1)19 inches standard design of rack mount, compact structure. 2)Sin wave output provides best power supply guarantee. 3)Zero transfer time between mains mode and battery mode. 4)Detection function of input neutral wire and live wire. 5)Having voltage surge protection function and strong anti-interference function. 6)Equipped with correction function of input power factor 7) Supporting mobile smart monitoring card , users can real-time monitor every data of the UPS by mobile APP.  
Technical Specifications
Model RTX3110KL RTX3115KL RTX3120KL
Rated Power 10kVA/9kW 15kVA/13.5kW 20kVA/18kW
INPUT Voltage Range 207-475Vac3P4W+G
Working Frequency Range 40-70HZ (settable)
Input Power Factor >0.95
OUTPUT Rated Voltage and Accuracy 220Vac(l±l%)lP2W+G
Output Frequency 46-54Hz synchronize with mains power; 50Hz (Mains power between 40-46Hz and 54-60Hz); 50Hz(Battery)
Rated Current 45A 68A 91A
Output Power Factor 0.9
Output Harmonic Wave W3%
Crest Factor  3:1
Output Overload 105%±5%<Load≤125%±5%: Convert to bypass output and alarm after 1 min; 125%±5%<Load ≤50%±5%: Convert to bypass output and alarm after 30s; Load>150%±5%: Convert to bypass output and alarm after 300ms.
Transfer Time 0ms
Efficiency >92%
BATTERY Rated Voltage 192Vdc
Quantity 16
Charging Current 5.5A
Dimension (LxWxH) mm 665*482.6*132.5 655*482.6*265
Weight 23kg 34kg 35kg
Working Temperature 0°〜40°C
Working Humidity 20% 〜95%
Noise ≤60dB
Description
HIGH INTELLIGENCE AND RELIABLE POWER SUPPLY IGBT Technology Full microprocessor control with no-break static and manual bypasses. Online double conversion technology (VFl) with isolation transformer on theinverter output. Extremely high short-circuit current to ensure compatibility with the most diffificult transformer applications (lighting, drives and industrial processes) and an isolation transformer on the inverter output. Compatibled with Watch & Save 3000 software as standard and can be remotely monitored using the Power NetGuard system from anywhere in the world. SIMPLE TO INSTALL Capability to install the UPS into any distribution system(neutral not required on rectifier input). Capability to separate the rectifier/bypass power networks and to power them from two separate sources, without Galvanic isolation(Necessary on UPS without an output transformer MAXIMUM BATTERY CARE Battery deep discharge protection; Temperature compensating charger; Built-in automatic and manual battery test feature. OTHER CHARACTERISTICS 0.8/0.9 power factor suitable for powering ICT and lndustrial loads. BACK FEED protection: to avoid energy feeding back into the mains supply cause a fault occur. MAXIMUM RELIABILITY AND AVAILABILITY Connect up to 6 units in parallel or N+1 redundancy, even of different power ratings. The UPS continue to work in parallel even if one of theinterconnecting communication cables is disconnected(CLOSED LOOP) LOW CONSUMPTION LEVELS LF33 Series UPS can achieve efficiencies >98% thanks to selectable Economy Mode which can be used in stable electrical environments to provide power supply continuity when the mains fail. ADVANCE COMMUNICATION: RS485/RS232/Dry Contact/SNMP(Optional)  
Specifications
Model 10KVA 20KVA 30KVA 40KVA 60KVA 80KVA 100KVA 120KVA 160KVA 200KVA 250KVA 300KVA 400KVA 500KVA 600KVA
Capacity 8KW 16 KW 24 KW 32 KW  48 KW 64 KW  80 KW 96 KW 128 KW 160 KW 200KW 240KW 320KW 400KW  480KW
INPUT
Rated voltage 400 VAC  Three-Phase
Voltage range 380/400/415VAC(+25%,Can be set through the LCD panel)
Frequency range 40-70Hz(Automatically select synchronization range according to grid frequency)
Range(HZ) 50±5%(±10%) Bypass synchronization tracking
Rectifying pulse number 6 pulse rectification 6/12 pulse rectification 12 pulse rectifier
Phase system 3φ4W+PE(Three phase five wire system)
Battery voltage 384VDC 480VDC
Battery Quantity Standard with 32 Cells(30~34, can be set through the LCD panel)  Standard 40 Cells(38~42 knots,can be set by LCD panel)
OUTPUT
Power factor 0.8/0.9 (Optional)
Voltage(V) L-N: 220±1%   L-L: 380±1%
Three-phase 100% load unbalance voltage stability ≤2%,Allow 100% imbalance
Frequency(HZ) Normal power, tracking the frequency of power, Grid abnormal. 50±0.2%
Transfer time(ms) 0ms
Parallel operation mode (parallel type) Max 8 Parallel
Waveform distortion Linear loadTHD<3% ; Nonlinear loadTHD<5%
Overload capacity 125% full load for 10 minutes, maintain 150 % full load for 1 minute and then switch to bypass power supply, after reducing the loadcan automatically restore the inverter
Crest factor 3:1
Others
Index Standard with no transfer time maintenance bypass switch
Communication function RS232/RS485/Dry Contact/SNMP (Optional)
Panel display LED displays working status and fault indication; LCD displays three-phase input voltage, input frequency, three-phase output voltage, load,battery voltage, battery charge and discharge current, etc
Display  7″ Touchable LCD screen display
The audio noise(dB) <65(within 1 meter)
Alarm function Battery low voltage, abnormal power supply, overload, UPS failure, over temperature protection
Protection Input over voltage, battery under voltage, overload, short circuit, over temperature protection
Cooling way Forced cooling
Operating temperature 0℃ to  ~ 40℃
Humidity 0~95%, non-condensing
electromagnetic compatibility Conform GB7260.2
Size(W*D*H)(mm) 540*660*1135 1100*800*1800 800*800*1900 1200*850*1900 2600*1100*2000
Weight 196     233 276 329 461 547.5 643 754 1375
WeightN/AN/AN/AN/AN/AN/A
DimensionsN/AN/AN/AN/AN/AN/A
Additional information