105%±5%< Load<125%±5% :1 min transfer to bypass
125% ±5% < Load<135 % ±5 % :30s transfer to bypass
Load > 135 % ± 5 %: 300s transfer to bypass
Communication
SNMP,RS-232,USB+lntelligent Slot
Operating Environment
Temperature
0°C~40°C
Humidity
15%~90%
Dimension
Width (mm)
260
260
260
260
260
Depth (mm)
560
533
560
533
560
Height (mm)
717
501
717
501
717
Net Weight(Kg)
55
12.2
62
21
23
32
33
Description
HIGH INTELLIGENCE AND RELIABLE POWER SUPPLYIGBT Technology
Full microprocessor control with no-break static and manual bypasses.
Online double conversion technology (VFl) with isolation transformer on theinverter output.
Extremely high short-circuit current to ensure compatibility with the most diffificult transformer applications (lighting, drives and industrial processes) and an isolation transformer on the inverter output.
Compatibled with Watch & Save 3000 software as standard and can be remotely monitored using the Power NetGuard system from anywhere in the world.
SIMPLE TO INSTALL
Capability to install the UPS into any distribution system(neutral not required on rectifier input).
Capability to separate the rectifier/bypass power networks and to power them from two separate sources, without Galvanic isolation(Necessary on UPS without an output transformer
MAXIMUM BATTERY CARE
Battery deep discharge protection;
Temperature compensating charger;
Built-in automatic and manual battery test feature.
OTHER CHARACTERISTICS
0.8/0.9 power factor suitable for powering ICT and lndustrial loads.
BACK FEED protection: to avoid energy feeding back into the mains supply cause a fault occur.
MAXIMUM RELIABILITY AND AVAILABILITY
Connect up to 6 units in parallel or N+1 redundancy, even of different power ratings.
The UPS continue to work in parallel even if one of theinterconnecting communication cables is disconnected(CLOSED LOOP)
LOW CONSUMPTION LEVELS
LF33 Series UPS can achieve efficiencies >98% thanks to selectable Economy Mode which can be used in stable electrical environments to provide power supply continuity when the mains fail.
ADVANCE COMMUNICATION:
RS485/RS232/Dry Contact/SNMP(Optional)
Specifications
Model
10KVA
20KVA
30KVA
40KVA
60KVA
80KVA
100KVA
120KVA
160KVA
200KVA
250KVA
300KVA
400KVA
500KVA
600KVA
Capacity
8KW
16 KW
24 KW
32 KW
48 KW
64 KW
80 KW
96 KW
128 KW
160 KW
200KW
240KW
320KW
400KW
480KW
INPUT
Rated voltage
400 VAC Three-Phase
Voltage range
380/400/415VAC(+25%,Can be set through the LCD panel)
Frequency range
40-70Hz(Automatically select synchronization range according to grid frequency)
Range(HZ)
50±5%(±10%) Bypass synchronization tracking
Rectifying pulse number
6 pulse rectification
6/12 pulse rectification
12 pulse rectifier
Phase system
3φ4W+PE(Three phase five wire system)
Battery voltage
384VDC
480VDC
Battery Quantity
Standard with 32 Cells(30~34, can be set through the LCD panel) Standard 40 Cells(38~42 knots,can be set by LCD panel)
OUTPUT
Power factor
0.8/0.9 (Optional)
Voltage(V)
L-N: 220±1% L-L: 380±1%
Three-phase 100% load
unbalance voltage stability
≤2%,Allow 100% imbalance
Frequency(HZ)
Normal power, tracking the frequency of power, Grid abnormal. 50±0.2%
Transfer time(ms)
0ms
Parallel operation mode
(parallel type)
Max 8 Parallel
Waveform distortion
Linear loadTHD<3% ; Nonlinear loadTHD<5%
Overload capacity
125% full load for 10 minutes, maintain 150 % full load for 1 minute and then switch to bypass power supply,
after reducing the loadcan automatically restore the inverter
Crest factor
3:1
Others
Index
Standard with no transfer time maintenance bypass switch
Communication function
RS232/RS485/Dry Contact/SNMP (Optional)
Panel display
LED displays working status and fault indication; LCD displays three-phase input voltage,
input frequency, three-phase output voltage, load,battery voltage, battery charge and discharge current, etc
Display
7″ Touchable LCD screen display
The audio noise(dB)
<65(within 1 meter)
Alarm function
Battery low voltage, abnormal power supply, overload, UPS failure, over temperature protection
Protection
Input over voltage, battery under voltage, overload, short circuit, over temperature protection
Cooling way
Forced cooling
Operating temperature
0℃ to ~ 40℃
Humidity
0~95%, non-condensing
electromagnetic compatibility
Conform GB7260.2
Size(W*D*H)(mm)
540*660*1135
1100*800*1800
800*800*1900
1200*850*1900
2600*1100*2000
Weight
196
233
276
329
461
547.5
643
754
1375
Features:
The battery cabinet is made of metal material, strong and can bear up to 500KG.
The battery cabinet is assembled in the form of assembly, which is conven-ient for transportation and simple for assembly.
The surface of electrostatic spraying, strong rust resistance, color can be fixed spray.
Other sizes can be customized.
Technical Specifications
Model
Dimensions(W*D*H) (mm)
Battery Capacity
Battery Numbers
Weight(kg)
B-1B
280x190x220
24AH/17AH
2/3PCS
2.2
B-1
435x210x270
17AH/24AH/38AH
5/3/2 PCS
3.3
65AH/100AH
1PC
B-1A
540x210x230
17AH/24AH/38AH
6/4/3PCS
4.5
B-2
450x470x320
17AH/24AH/38AH
10/6/4 PCS
7
65AH/100AH
2PCS
B-3
585x470x320
17AH/24AH/38AH
14/8/6PCS
9
65AH/100AH
3PCS
B-4
450x470x615
17AH/24AH/38AH
20/12/8PCS
15
65AH/100AH
4PCS
B-6
585x470x615
17AH/24AH/38AH
28/16/12PCS
18
65AH/100AH
6PCS
B-8
780x470x615
17AH/24AH/38AH
44/28/20PCS
21
65AH/100AH
8PCS
B-10
950x470x615
17AH/24AH/38AH
44/28/20PCS
24
65AH/100AH
10PCS
B-12
780x470x910
24AH/38AH
30/24PCS
32
65AH/100AH
12PCS
B-16
780x470x1190
24AH/38AH
40/32PCS
45
65AH/100AH
16PCS
B-20
950x470x1190
24AH/38AH
56/40PCS
50
65AH/100AH
20PCS
B-24
1150x470x1190
65AH/100AH
24PCS
57
B-32
780x880x1190
65AH/100AH
32PCS
95
B-40
950x880x1190
65AH/100AH
40PCS
100
Features:
Capacity: 1200W 1008Wh /315000mAh
Input AC Output Power:Rated Power 1200W Peak Power 2400W
Input AC Charging:AC100~125V/AC184~264V Bidirectional Inverter 700W Max
Input Car Charging:DC12V~24V/10A 240W Max
Input Solar Charging:DC12V~60V/10A 400W Max
Output Voltage:230VAC±10%/110VAC±10%
Output Frequency: 50Hz±5%/60Hz±5%
USB Output:2*5V2.4A +2*QC18W+2*PD60W Max
DC Output:1*Cigarette Lighter+2*DC5521 Rated Output (13.8V/10A Max)
Output Waveform:Pure Sine Wave
LED:3 Levels(H/M/L)+SOS
UPS Function:Support(≤10mS)
Applications:
Mammogram
Ultrasound Equipments
Radiology rooms
Features:
50KW single power module in 3U
N+1or N+X parallel redundancy for power guarantee
Supports horizontal expansion by 1+1 cabinet paralleloperation.
Hot-swappable modular design decreases MTTR
High scalability
Built-in maintenance bypass switch for easy maintenance without interruptible
High efficiency double conversion online UPS
Flexible battery configuration and adjustable charging current
Reviews