3 Phase Low Frequency Online UPS LD31 Series

$0.00

Shipped From Abroad

Delivery & Availability:
Typically 10-21 working days – excluding furniture and heavy/bulky equipment. Please contact us for further information.
SF1033560130139-2
Brands:: Reeco Power

Description

Description

HIGH INTELLIGENCE AND RELIABLE POWER SUPPLY

IGBT Technology
Full microprocessor control with no-break static and manual bypasses.
Online double conversion technology (VFl) with isolation transformer on theinverter output.
Extremely high short-circuit current to ensure compatibility with the most diffificult transformer applications (lighting, drives and industrial processes) and an isolation transformer on the inverter output.
Compatibled with Watch & Save 3000 software as standard and can be remotely monitored using the Power NetGuard system from anywhere in the world.

SIMPLE TO INSTALL

Capability to install the UPS into any distribution system(neutral not required on rectifier input).
Capability to separate the rectifier/bypass power networks and to power them from two separate sources, without Galvanic isolation(Necessary on UPS without an output transformer

MAXIMUM BATTERY CARE

Battery deep discharge protection;
Temperature compensating charger;
Built-in automatic and manual battery test feature.

OTHER CHARACTERISTICS

0.8/0.9 power factor suitable for powering ICT and lndustrial loads.
BACK FEED protection: to avoid energy feeding back into the mains supply cause a fault occur.

MAXIMUM RELIABILITY AND AVAILABILITY

Connect up to 6 units in parallel or N+1 redundancy, even of different power ratings.
The UPS continue to work in parallel even if one of theinterconnecting communication cables is disconnected(CLOSED LOOP)

LOW CONSUMPTION LEVELS

LF31 Series UPS can achieve efficiencies >98% thanks to selectable Economy Mode which can be used in stable electrical environments to provide power supply continuity when the mains fail.

ADVANCE COMMUNICATION:

RS485/RS232/Dry Contact/SNMP(Optional)

 

Specifications
Model 10KVA 15KVA 20KVA 30KVA 40KVA 60KVA    80KVA 100KVA
Capacity 8KW 12 KW 16 KW 24 KW 32 KW 48 KW    64 KW    80 KW
INPUT
Rated voltage 380/400/415 VAC  Three-phase
Voltage range ±20%
Frequency range 45-65Hz
Power factor >0.92 with harmonic filter
Current harmonic distortion <5% with harmonic filter
Soft Start 0 -100% in 10″
BYPASS INPUT
Rated voltage 230VAC   Single Phase
Permitted voltage range ±15%  (selectable from ±10% to ±25% from front panel)
Rated frequency 50/60Hz
Permitted frequency range ±2%    (selectable from ±1% to ±5% from front panel)
Standard features Back Feed portection; split bypass line
BATTERY
Type VRLA AGM / GEL;NICd
Battery Voltage 384VDC
Maximum recharge current(A) 0.2 X C10
AC ripple voltage <1%
INVERTER OUTPUT
Rated power(kVA) 10KVA 15KVA 20KVA 30KVA 40KVA 60KVA     80KVA 100KVA
Active power(kW)  8KW 12 KW 16 KW 24 KW 32 KW 48 KW     64 KW 80 KW
Number of phases 1
Rated voltage(V) 230VAC  Single Phase
Regulation of the output voltage 220 ~ 244VAC  phase/neutral (from control panel)
Crest factor(Ipeak/Irms) 3:1
Static stability ±1%
Dynamic stability ±5%
Frequency 50/60Hz configurable
Overload 110% 125% 150% of the rated current for 5h/10’/1′
Frequency stability ±0.05% on mains failure
System 10KVA 15KVA 20KVA 30KVA 40KVA 60KVA     80KVA 100KVA
Remote signaling Volt free contacts
Remote controls EPO and Bypass
Communication RS232 + Romote Contacts
Operation temperature 0℃ to  ~ 40℃
Relative humidity <95% non condensing
Colour Light grey ( RAL 7035)
Noise 54dBA at 1m 60dBA at 1m   65dBA at 1m
Protection degree IP20
Efficiency Smart Mode Up to 98%
Compliance Safety:EN 62040-1-1(Directive 2006/95/EC); EMC:6200-2(Directive 2004/108/EC)
Weight(KG)N.W 176 220 205 213 295 440 520 770
Dimensions:(WxDxH)mm 555*730*1210 800*730*1400 1115*730*1400
Internal batteries optional optional optional No      No No No No

Reviews

There are no reviews yet.

Be the first to review “3 Phase Low Frequency Online UPS LD31 Series”

Your email address will not be published. Required fields are marked *

Quick Comparison

Settings3 Phase Low Frequency Online UPS LD31 Series remove3 Phase Low Frequency Online UPS LF33 Series removeOPzV Tubular Gel Battery 60AH-3000AH removeHigh Frequency Modular UPS RM Pro Series removePortable Power Station PX Series 500W removeLine Interactive UPS AP Series 1000VA-3000VA remove
Name3 Phase Low Frequency Online UPS LD31 Series remove3 Phase Low Frequency Online UPS LF33 Series removeOPzV Tubular Gel Battery 60AH-3000AH removeHigh Frequency Modular UPS RM Pro Series removePortable Power Station PX Series 500W removeLine Interactive UPS AP Series 1000VA-3000VA remove
Image
SKUSF1033560130139-2SF1033560130139-4SF1033560130139-18SF1033560130139-10SF1033560130139-24SF1033560130139-16
Rating
Price

$0.00

$0.00

$0.00

$0.00

$0.00

$0.00

Stock
Availability
Add to cart

DescriptionShipped From Abroad
Delivery & Availability: Typically 10-21 working days – excluding furniture and heavy/bulky equipment. Please contact us for further information.
Shipped From Abroad
Features:
  • Optional 7 ” touch LCD
  • Online double-conversionDSP technology guarantees high reliability
  • True galvanic isolation transformer designControl designed to withstand all kinds of loads
  • Intelligent battery management to prolong battery lifecycle
  • Redundant fan design and independent ventilation enhance durable operation under harsh environment
  • Adiustable battery numbers
  • Accept dual-mains input
  • Parallel operation with up to 4 units ( option )
  • Variety of communication options available
  • Reverse phase frequency operation and supportsnon-neutral input
Delivery & Availability: Typically 10-21 working days – excluding furniture and heavy/bulky equipment. Please contact us for further information.
Shipped From Abroad
Delivery & Availability: Typically 10-21 working days – excluding furniture and heavy/bulky equipment. Please contact us for further information.
Shipped From Abroad
Features:
  • 60KW single power module in 3U
  • N+1or N+X parallel redundancy for power guarantee
  • Supports horizontal expansion by 1+1 cabinet paralleloperation.
  • Hot-swappable modular design decreases MTTR
  • High scalability
  • Built-in maintenance bypass switch for easy maintenance without interruptible
  • High efficiency double conversion online UPS
  • Flexible battery configuration and adjustable charging current
  • High overload capability
  • Power walk-in function
  • Built-in dynamic password protection
  • Built-in ultra communication slot
Delivery & Availability: Typically 10-21 working days – excluding furniture and heavy/bulky equipment. Please contact us for further information.
Shipped From Abroad
Features:
  • Pure sine wave output
  • DSP digital control
  • Boost and buck AVR for voltage stabilization
  • Cold start function
  • Intelligent battery management
  • Short circuit and overload protection
  • Off-mode charging
  • Offering LED and LCD panels for selection
  • Optional USB/RS232/RJ45/SNMP communication port
Delivery & Availability: Typically 10-21 working days – excluding furniture and heavy/bulky equipment. Please contact us for further information.
Content
Description
HIGH INTELLIGENCE AND RELIABLE POWER SUPPLY IGBT Technology Full microprocessor control with no-break static and manual bypasses. Online double conversion technology (VFl) with isolation transformer on theinverter output. Extremely high short-circuit current to ensure compatibility with the most diffificult transformer applications (lighting, drives and industrial processes) and an isolation transformer on the inverter output. Compatibled with Watch & Save 3000 software as standard and can be remotely monitored using the Power NetGuard system from anywhere in the world. SIMPLE TO INSTALL Capability to install the UPS into any distribution system(neutral not required on rectifier input). Capability to separate the rectifier/bypass power networks and to power them from two separate sources, without Galvanic isolation(Necessary on UPS without an output transformer MAXIMUM BATTERY CARE Battery deep discharge protection; Temperature compensating charger; Built-in automatic and manual battery test feature. OTHER CHARACTERISTICS 0.8/0.9 power factor suitable for powering ICT and lndustrial loads. BACK FEED protection: to avoid energy feeding back into the mains supply cause a fault occur. MAXIMUM RELIABILITY AND AVAILABILITY Connect up to 6 units in parallel or N+1 redundancy, even of different power ratings. The UPS continue to work in parallel even if one of theinterconnecting communication cables is disconnected(CLOSED LOOP) LOW CONSUMPTION LEVELS LF31 Series UPS can achieve efficiencies >98% thanks to selectable Economy Mode which can be used in stable electrical environments to provide power supply continuity when the mains fail. ADVANCE COMMUNICATION: RS485/RS232/Dry Contact/SNMP(Optional)  
Specifications
Model 10KVA 15KVA 20KVA 30KVA 40KVA 60KVA    80KVA 100KVA
Capacity 8KW 12 KW 16 KW 24 KW 32 KW 48 KW    64 KW    80 KW
INPUT
Rated voltage 380/400/415 VAC  Three-phase
Voltage range ±20%
Frequency range 45-65Hz
Power factor >0.92 with harmonic filter
Current harmonic distortion <5% with harmonic filter
Soft Start 0 -100% in 10″
BYPASS INPUT
Rated voltage 230VAC   Single Phase
Permitted voltage range ±15%  (selectable from ±10% to ±25% from front panel)
Rated frequency 50/60Hz
Permitted frequency range ±2%    (selectable from ±1% to ±5% from front panel)
Standard features Back Feed portection; split bypass line
BATTERY
Type VRLA AGM / GEL;NICd
Battery Voltage 384VDC
Maximum recharge current(A) 0.2 X C10
AC ripple voltage <1%
INVERTER OUTPUT
Rated power(kVA) 10KVA 15KVA 20KVA 30KVA 40KVA 60KVA     80KVA 100KVA
Active power(kW)  8KW 12 KW 16 KW 24 KW 32 KW 48 KW     64 KW 80 KW
Number of phases 1
Rated voltage(V) 230VAC  Single Phase
Regulation of the output voltage 220 ~ 244VAC  phase/neutral (from control panel)
Crest factor(Ipeak/Irms) 3:1
Static stability ±1%
Dynamic stability ±5%
Frequency 50/60Hz configurable
Overload 110% 125% 150% of the rated current for 5h/10’/1′
Frequency stability ±0.05% on mains failure
System 10KVA 15KVA 20KVA 30KVA 40KVA 60KVA     80KVA 100KVA
Remote signaling Volt free contacts
Remote controls EPO and Bypass
Communication RS232 + Romote Contacts
Operation temperature 0℃ to  ~ 40℃
Relative humidity <95% non condensing
Colour Light grey ( RAL 7035)
Noise 54dBA at 1m 60dBA at 1m   65dBA at 1m
Protection degree IP20
Efficiency Smart Mode Up to 98%
Compliance Safety:EN 62040-1-1(Directive 2006/95/EC); EMC:6200-2(Directive 2004/108/EC)
Weight(KG)N.W 176 220 205 213 295 440 520 770
Dimensions:(WxDxH)mm 555*730*1210 800*730*1400 1115*730*1400
Internal batteries optional optional optional No      No No No No
Features:
  • Optional 7 ” touch LCD
  • Online double-conversionDSP technology guarantees high reliability
  • True galvanic isolation transformer designControl designed to withstand all kinds of loads
  • Intelligent battery management to prolong battery lifecycle
  • Redundant fan design and independent ventilation enhance durable operation under harsh environment
  • Adiustable battery numbers
  • Accept dual-mains input
  • Parallel operation with up to 4 units ( option )
  • Variety of communication options available
  • Reverse phase frequency operation and supportsnon-neutral input
 
Specifications
MODEL LF33 10K LF33 20K LF33 30K LF33 40K LF33  60K LF33  80K LF33 100K LF33 120K LF33 160K LF33 200K
CAPACITY 10KVA /8KW 20KVA /16KW 30KVA /24KW 40KVA /32KW 60KVA /48KW 80KVA /64KW 100KVA /80KW 120KVA /96KW 160KVA /128KW 200KVA /160KW
INPUT
Nominal Voltage 3 x 380VAC/400VAC (3Ph + N)
Acceptable Voltage Range 305VAC ~ 460VAC
Frequency 46-54Hzor56-64Hz
INVERTER
Nominal Voltage 3 x 380VAC/400VAC (3Ph + N)
Precision Stationary: ±1% Transitory: ±5% (load variations 100-0-100%)
Frequency 50/60 Hz synchronised ±1 % With mains absent ±0.1 Hz
Max. Synchronisation Speed ±1 Hz/s
Waveform Pure Sinewave
Total Harmonic Distortion (THDv) <2% (Linear Load) ; <5% (Non-linear Load)
Phase Displacement 120° ±1 % (balanced load); 120° ±2% (imbalances 50% of the load)
Dynamic Recovery Time Restore to 90% of rated value in 3 cycles
Overload capacity 110% for 10min; 150% for 60sec; >160% for 200ms
Admissible Crest Factor 3:1
Admissible Power Factor 0.6-1 (inductive or capacitive)
Imbalance Output Voltage @ 100% Unbalanced Load                    <1%
Current Limit High overload, short-circuit: RMS Voltage Limit; High Crest-Factor current: Peak Voltage Limit
STATIC BYPASS
Type Solid state
Voltage 3 x 380VAC/400VAC (3Ph + N)
Frequency 50/60 Hz
Activation Criterion Microprocessor control
Transfer Time Zero
Admissible Overload 150% for 1 hour; 180% for 30sec; >200% for 200ms
Transfer to Bypass Immediate, for overloads above 160%
Retransfer Automatic after alarm clear
MAINTENANCE BYPASS
Type Without interruption
Voltage 3 * 400V (3Ph + N)
Frequency 50/60 Hz
Overall Efficiency Line Mode 90% 91% 92% 93%
Battery Mode 90% 91% 93% 93%
BATTERY & CHARGER
Battery Type and Numbers 12VDC * 32 pcs (29-32 pcs adjustable)
Nominal Battery Voltage 384 VDC (Based on 32pcs batteries)
Charging Method CC/CV
Precision ±1%
Charging Current Max.: 40 A
Charging Voltage 432 VDC (Based on 32pcs batteries)
PHYSICAL
Dimensions, D x W x H(mm) 656 x 405 x 817 656 x 405 x 941 840x432x1140 975x554x1286 1200x910x1680 1500x1140x1800
Net Weight (Kgs) 180 205 295 330 451 519 950 1350
Features:
  • OPzV Tubular Gel Battery ( solid-state) 60AH-3000AH
  • Voltage class: 12V/2V
  • Capacity range: 60Ah~3000Ah

OPzV batteries offer high capacity reserve power and true deep cycling performance. With a design life of 20 years and a maintenance-free operation, OPzV battery are perfect for regions with an unstable supply of electricity. OPzV battery are also completely spill-proof, which makes them safe to install anywhere, even in remote environments with minimal supervision.

 
Technical Specifications
Model Nominal Voltage Capacity Dimension Terminal
C10/1.80VPC (Ah) Length Width Height Total Height
(V) mm mm mm mm
OPzV6-200 6 200 322 177.5 226 231 F16(M8) F14(M8)
OPzV12-60 12 60 260 169 211 216  F11(M6)
OPzV12-80 12 80 328 172 215 220  F12(M8)
OPzV12-100 12 100 407 177 225 225  F12(M8)
OPzV12-120 12 120 483 170 241 241  F12(M8)
OPzV12-140 12 140 532 207 214 219  F12(M8)
OPzV12-160 12 160 532 207 214 219 F12(M8)
OPzV12-180 12 180 522 240 219 224  F10(M8)
OPzV12-200 12 200 521 268 220 225 F14(M8)
OPzV2-200 2 200 103 206 355 390 F10(M8)
OPzV2-250 2 250 124 206 355 390 F10(M8)
OPzV2-300 2 300 145 206 355 390 F10(M8)
OPzV2-350 2 350 124 206 470 505 F10(M8)
OPzV2-420 2 420 145 206 470 505 F10(M8)
OPzV2-500 2 490 166 206 470 505 F10(M8)
OPzV2-770 2 770 210 254 470 505 F10(M8)
OPzV2-600 2 600 145 206 645 680 F10(M8)
OPzV2-800 2 800 191 210 645 680 F10(M8)
OPzV2-1000 2 1000 233 210 645 680 F10(M8)
OPzV2-1200 2 1200 276 210 645 680 F10(M8)
OPzV2-1500 2 1500 275 210 795 830 F10(M8)
OPzV2-2000 2 2000 399 214 770 805 F10(M8)
OPzV2-2500 2 2500 487 212 770 805 F10(M8)
OPzV2-3000 2 3000 576 212 770 805 F10(M8)
Features:
  • 60KW single power module in 3U
  • N+1or N+X parallel redundancy for power guarantee
  • Supports horizontal expansion by 1+1 cabinet paralleloperation.
  • Hot-swappable modular design decreases MTTR
  • High scalability
  • Built-in maintenance bypass switch for easy maintenance without interruptible
  • High efficiency double conversion online UPS
  • Flexible battery configuration and adjustable charging current
  • High overload capability
  • Power walk-in function
  • Built-in dynamic password protection
  • Built-in ultra communication slot
 
Technical Specifications
MODEL RM Pro 120K RM Pro 180K RM Pro 300K RM Pro 420K RM Pro 480K RM Pro 600K
Phase 3 Phase in / 3 Phase out
Cabinet Capacity* 120 KW 180 KW 300KW 420KW 480KW 600KW
Battery  Type Extemal Battery
One Power Module Capacity 60KVA/60KW
Max.   Power Module  No. 2 3 5 7 8 10
INPUT
Nominal Voltage 3×380/400/415   VAC(3Ph+N)
Voltage Range -30%~+20%
Nominal Frequency 50/60Hz(Auto Sensing)
Frequency Range 40Hz~70Hz
Power Factor >0.99  @100%  Load, >0.98 @ 50%  Load
Harmonic  Distortion   (THDi) <3%@  100%  load
OUTPUT
Nominal Voltage 3×380/400/415 VAC (3Ph+N)
Voltage  Regulation(Steady  State) ≤±1% Typical(balanced load); ≤±2% Typical(unbalanced load)
Nominal Frequency 50/60Hz
Frequency Range(Synchronized) 46Hz~54Hz or 56Hz~64Hz
Overload Capability 1 hour for ≤110%,10 mins for 111%~125%,1 min for 126%~150% and 200ms for >150%
Haronic Distortion ≤2% THD (Linear Load);  ≤4% THD (Non-linear Load)
Eficiency 96%
BATTERY / CHARGER
Nominal Voltage ’+/- 192V~+/- 240V(Selectable)
Maximum Voltage ’+/- 240V (12V×40 PCS)
Minimum Voltage ‘+/-192V (12V×32 PCS)
Floating Charge Voltage 2.28V/Cell (2.25~2.33 Selectable)
Boost Charging Voltage 2.35V/Cell
Temperature Compensation Yes
Maximum Charging Current (Per Power Module) 18A(Adjustable)
PHYSICAL
Cabinet Dimension (DxWxH)mm 1100x600x1475 1100x600x1475 1100x600x2010 1100×600×2010 1065x1000x2000 1065×1000×2000
Net Weight (Kg) 308 352 516 654 932 1020
Power Module (PM-60) Net Weight 44KGS
ENVIRONMENT
Operating Temperature 0~40℃
Relative Humidity 0~95% non-condensing
Altitude* <1000m for Nominal power
IP  Protection IP 20
MANAGEMENT
Smart  RS-232/USB Supports Windows⑧ Family, Linux and MAC
Optional SNMP Power management from SNMP manager and web browser
STANDARDS
Safety IEC/EN62040-1
EMC IEC/EN 62040-2 Category C3
Features:
  • Rated Power: 500W
  • Rated Capacity: 519 . 48wh
  • Standard Capacity: 3.7V/140400mah
  • Overload Protecion: 550W + 40W
  • AC Output: AC 110V+10%/60HZ 230V+10%/50HZ
  • Output Wave: Pure sine wave
  • USB Output: QC 18W*2
  • Type-c Output: PD 60W*2
  • Cigarret Lighter Output: 14V/8A
  • DC5525 Output: 14V/8A
  • Wireless Charging: 15W
  • Charging Input: 12-26 V/100W Max
  • WorkingTemperature: -10-40 °C
  • Weight(Net Weight): 6.8kg
  • Weight(With Accessories): 8.5kg
  • Dimension: 345*227*203mm
 
Applications:
  • Mammogram
  • Ultrasound Equipments
  • Radiology rooms
Features:
  • Pure sine wave output
  • DSP digital control
  • Boost and buck AVR for voltage stabilization
  • Cold start function
  • Intelligent battery management
  • Short circuit and overload protection
  • Off-mode charging
  • Offering LED and LCD panels for selection
  • Optional USB/RS232/RJ45/SNMP communication port
 
Technical Specifications
 
MODEL UPS-AP1K ( L ) UPS-AP2K ( L ) UPS-AP3K ( L )
Capacity 1000VA/700W 2000VA/1400W 3000VA/2100W
INPUT
Voltage range 145~275VAC±5V
Frequency range 50Hz-60Hz
OUTPUT
Output voltage 220VAC
AC voltage range ±10%
Frequency range(batt.mode) 50Hz ± 0.25Hz or 60Hz ± 0.3Hz
Overload 105%-110%: UPS beep alarm, do not shut down.
110%-130%: auto shut down after 30 seconds
> 130%: auto shut down immediately
Transfer time <typical 4ms
Waveform(batt.mode) Pure sine wave
BATTERY
Standard model Battery type 12V7Ah
Numbers 2 4 6
Charging current(Max.) Assume: 1A± 10%; Max: 1A or 2A for option
Charging voltage 27.3VDC±1% 54.7VDC±1% 82.0VDC±1%
Long-run model Battery type 12V, AH depending on applicant
Numbers 3 6 8
Charging current(Max.) > 5A
Charging voltage 27.4VDC±1% 82.1VDC±1% 109.4VDC±1%
PHYSICAL
Standard model Dimension, LxWxH(mm) 360x147x220 440x192x340 440x192x340
Net weight(kgs) 11.9 22 27.9
Long-run model Dimension, LxWxH(mm) 360x147x220 440x192x340 440x192x340
Net weight(kgs) 8.5 16 18.2
ENVIRONMENT
Humidity 20-90%RH @0-40°C (non-condensing)
Noise level Less than 55dBA@1 Meter
MANAGEMENT
Smart RS-232 Support windows 2000/2003/XP/Vista/2008, Windows7/8, Linux, Unix, and MAC
Optional SNMP Power management from SNMP Management and web browser
WeightN/AN/AN/AN/AN/AN/A
DimensionsN/AN/AN/AN/AN/AN/A
Additional information
Select the fields to be shown. Others will be hidden. Drag and drop to rearrange the order.
  • Image
  • Rating
  • Price
  • Description
Click outside to hide the comparison bar
Compare