3 Phase Low Frequency Online UPS LD31 Series

$0.00

Shipped From Abroad

Delivery & Availability:
Typically 10-21 working days – excluding furniture and heavy/bulky equipment. Please contact us for further information.
SF1033560130139-2
Brands:: Reeco Power

Description

Description

HIGH INTELLIGENCE AND RELIABLE POWER SUPPLY

IGBT Technology
Full microprocessor control with no-break static and manual bypasses.
Online double conversion technology (VFl) with isolation transformer on theinverter output.
Extremely high short-circuit current to ensure compatibility with the most diffificult transformer applications (lighting, drives and industrial processes) and an isolation transformer on the inverter output.
Compatibled with Watch & Save 3000 software as standard and can be remotely monitored using the Power NetGuard system from anywhere in the world.

SIMPLE TO INSTALL

Capability to install the UPS into any distribution system(neutral not required on rectifier input).
Capability to separate the rectifier/bypass power networks and to power them from two separate sources, without Galvanic isolation(Necessary on UPS without an output transformer

MAXIMUM BATTERY CARE

Battery deep discharge protection;
Temperature compensating charger;
Built-in automatic and manual battery test feature.

OTHER CHARACTERISTICS

0.8/0.9 power factor suitable for powering ICT and lndustrial loads.
BACK FEED protection: to avoid energy feeding back into the mains supply cause a fault occur.

MAXIMUM RELIABILITY AND AVAILABILITY

Connect up to 6 units in parallel or N+1 redundancy, even of different power ratings.
The UPS continue to work in parallel even if one of theinterconnecting communication cables is disconnected(CLOSED LOOP)

LOW CONSUMPTION LEVELS

LF31 Series UPS can achieve efficiencies >98% thanks to selectable Economy Mode which can be used in stable electrical environments to provide power supply continuity when the mains fail.

ADVANCE COMMUNICATION:

RS485/RS232/Dry Contact/SNMP(Optional)

 

Specifications
Model 10KVA 15KVA 20KVA 30KVA 40KVA 60KVA    80KVA 100KVA
Capacity 8KW 12 KW 16 KW 24 KW 32 KW 48 KW    64 KW    80 KW
INPUT
Rated voltage 380/400/415 VAC  Three-phase
Voltage range ±20%
Frequency range 45-65Hz
Power factor >0.92 with harmonic filter
Current harmonic distortion <5% with harmonic filter
Soft Start 0 -100% in 10″
BYPASS INPUT
Rated voltage 230VAC   Single Phase
Permitted voltage range ±15%  (selectable from ±10% to ±25% from front panel)
Rated frequency 50/60Hz
Permitted frequency range ±2%    (selectable from ±1% to ±5% from front panel)
Standard features Back Feed portection; split bypass line
BATTERY
Type VRLA AGM / GEL;NICd
Battery Voltage 384VDC
Maximum recharge current(A) 0.2 X C10
AC ripple voltage <1%
INVERTER OUTPUT
Rated power(kVA) 10KVA 15KVA 20KVA 30KVA 40KVA 60KVA     80KVA 100KVA
Active power(kW)  8KW 12 KW 16 KW 24 KW 32 KW 48 KW     64 KW 80 KW
Number of phases 1
Rated voltage(V) 230VAC  Single Phase
Regulation of the output voltage 220 ~ 244VAC  phase/neutral (from control panel)
Crest factor(Ipeak/Irms) 3:1
Static stability ±1%
Dynamic stability ±5%
Frequency 50/60Hz configurable
Overload 110% 125% 150% of the rated current for 5h/10’/1′
Frequency stability ±0.05% on mains failure
System 10KVA 15KVA 20KVA 30KVA 40KVA 60KVA     80KVA 100KVA
Remote signaling Volt free contacts
Remote controls EPO and Bypass
Communication RS232 + Romote Contacts
Operation temperature 0℃ to  ~ 40℃
Relative humidity <95% non condensing
Colour Light grey ( RAL 7035)
Noise 54dBA at 1m 60dBA at 1m   65dBA at 1m
Protection degree IP20
Efficiency Smart Mode Up to 98%
Compliance Safety:EN 62040-1-1(Directive 2006/95/EC); EMC:6200-2(Directive 2004/108/EC)
Weight(KG)N.W 176 220 205 213 295 440 520 770
Dimensions:(WxDxH)mm 555*730*1210 800*730*1400 1115*730*1400
Internal batteries optional optional optional No      No No No No

Reviews

There are no reviews yet.

Be the first to review “3 Phase Low Frequency Online UPS LD31 Series”

Your email address will not be published. Required fields are marked *

Quick Comparison

Settings3 Phase Low Frequency Online UPS LD31 Series remove3 Phase Low Frequency Online UPS LD33 Series removeSingle Phase High Frequency Online UPS VT Series 6KVA-20KVA removeHigh Frequency Modular UPS RM Pro Series removeHigh Frequency Modular UPS RM Plus Series 300 KW-500KW removeLead Acid Gel Battery 33AH-250AH remove
Name3 Phase Low Frequency Online UPS LD31 Series remove3 Phase Low Frequency Online UPS LD33 Series removeSingle Phase High Frequency Online UPS VT Series 6KVA-20KVA removeHigh Frequency Modular UPS RM Pro Series removeHigh Frequency Modular UPS RM Plus Series 300 KW-500KW removeLead Acid Gel Battery 33AH-250AH remove
Image
SKUSF1033560130139-2SF1033560130139-3SF1033560130139-26SF1033560130139-10SF1033560130139-8SF1033560130139-14
Rating
Price

$0.00

$0.00

$0.00

$0.00

$0.00

$0.00

Stock
Availability
Add to cart

DescriptionShipped From Abroad
Delivery & Availability: Typically 10-21 working days – excluding furniture and heavy/bulky equipment. Please contact us for further information.
Shipped From Abroad
Delivery & Availability: Typically 10-21 working days – excluding furniture and heavy/bulky equipment. Please contact us for further information.
Shipped From Abroad
Features:
  • True Double conversion Technology
  • DSP digital control technology enable UPS more stable performance.
  • Three Level inverter control technology
  • Large screen LCD display
  • N+X Parallel Redundancy function (3 units parallel)
  • EPO emergency stop function
  • Smart expansion Slots (optional)
  • Support Generator
Delivery & Availability: Typically 10-21 working days – excluding furniture and heavy/bulky equipment. Please contact us for further information.
Shipped From Abroad
Features:
  • 60KW single power module in 3U
  • N+1or N+X parallel redundancy for power guarantee
  • Supports horizontal expansion by 1+1 cabinet paralleloperation.
  • Hot-swappable modular design decreases MTTR
  • High scalability
  • Built-in maintenance bypass switch for easy maintenance without interruptible
  • High efficiency double conversion online UPS
  • Flexible battery configuration and adjustable charging current
  • High overload capability
  • Power walk-in function
  • Built-in dynamic password protection
  • Built-in ultra communication slot
Delivery & Availability: Typically 10-21 working days – excluding furniture and heavy/bulky equipment. Please contact us for further information.
Shipped From Abroad
Features:
  • 50KW single power module in 3U
  • N+1or N+X parallel redundancy for power guarantee
  • Supports horizontal expansion by 1+1 cabinet paralleloperation.
  • Hot-swappable modular design decreases MTTR
  • High scalability
  • Built-in maintenance bypass switch for easy maintenance without interruptible
  • High efficiency double conversion online UPS
  • Flexible battery configuration and adjustable charging current
  • High overload capability
  • Power walk-in function
  • Built-in dynamic password protection
  • Built-in ultra communication slot
Delivery & Availability: Typically 10-21 working days – excluding furniture and heavy/bulky equipment. Please contact us for further information.
Shipped From Abroad
Features:
  • Valve sealed design, no free electrolyte, Maintenance -free
  • Designed floating service life:15 years @ 25 °C/68 °F.
  • Wide operating temperature range from -15°C to 35°C
  • Nanometer gel electrolytes eliminate the acid stratification and prolong cycle life
  • Low self-discharge rate: ≤3%/month.
Delivery & Availability: Typically 10-21 working days – excluding furniture and heavy/bulky equipment. Please contact us for further information.
Content
Description
HIGH INTELLIGENCE AND RELIABLE POWER SUPPLY IGBT Technology Full microprocessor control with no-break static and manual bypasses. Online double conversion technology (VFl) with isolation transformer on theinverter output. Extremely high short-circuit current to ensure compatibility with the most diffificult transformer applications (lighting, drives and industrial processes) and an isolation transformer on the inverter output. Compatibled with Watch & Save 3000 software as standard and can be remotely monitored using the Power NetGuard system from anywhere in the world. SIMPLE TO INSTALL Capability to install the UPS into any distribution system(neutral not required on rectifier input). Capability to separate the rectifier/bypass power networks and to power them from two separate sources, without Galvanic isolation(Necessary on UPS without an output transformer MAXIMUM BATTERY CARE Battery deep discharge protection; Temperature compensating charger; Built-in automatic and manual battery test feature. OTHER CHARACTERISTICS 0.8/0.9 power factor suitable for powering ICT and lndustrial loads. BACK FEED protection: to avoid energy feeding back into the mains supply cause a fault occur. MAXIMUM RELIABILITY AND AVAILABILITY Connect up to 6 units in parallel or N+1 redundancy, even of different power ratings. The UPS continue to work in parallel even if one of theinterconnecting communication cables is disconnected(CLOSED LOOP) LOW CONSUMPTION LEVELS LF31 Series UPS can achieve efficiencies >98% thanks to selectable Economy Mode which can be used in stable electrical environments to provide power supply continuity when the mains fail. ADVANCE COMMUNICATION: RS485/RS232/Dry Contact/SNMP(Optional)  
Specifications
Model 10KVA 15KVA 20KVA 30KVA 40KVA 60KVA    80KVA 100KVA
Capacity 8KW 12 KW 16 KW 24 KW 32 KW 48 KW    64 KW    80 KW
INPUT
Rated voltage 380/400/415 VAC  Three-phase
Voltage range ±20%
Frequency range 45-65Hz
Power factor >0.92 with harmonic filter
Current harmonic distortion <5% with harmonic filter
Soft Start 0 -100% in 10″
BYPASS INPUT
Rated voltage 230VAC   Single Phase
Permitted voltage range ±15%  (selectable from ±10% to ±25% from front panel)
Rated frequency 50/60Hz
Permitted frequency range ±2%    (selectable from ±1% to ±5% from front panel)
Standard features Back Feed portection; split bypass line
BATTERY
Type VRLA AGM / GEL;NICd
Battery Voltage 384VDC
Maximum recharge current(A) 0.2 X C10
AC ripple voltage <1%
INVERTER OUTPUT
Rated power(kVA) 10KVA 15KVA 20KVA 30KVA 40KVA 60KVA     80KVA 100KVA
Active power(kW)  8KW 12 KW 16 KW 24 KW 32 KW 48 KW     64 KW 80 KW
Number of phases 1
Rated voltage(V) 230VAC  Single Phase
Regulation of the output voltage 220 ~ 244VAC  phase/neutral (from control panel)
Crest factor(Ipeak/Irms) 3:1
Static stability ±1%
Dynamic stability ±5%
Frequency 50/60Hz configurable
Overload 110% 125% 150% of the rated current for 5h/10’/1′
Frequency stability ±0.05% on mains failure
System 10KVA 15KVA 20KVA 30KVA 40KVA 60KVA     80KVA 100KVA
Remote signaling Volt free contacts
Remote controls EPO and Bypass
Communication RS232 + Romote Contacts
Operation temperature 0℃ to  ~ 40℃
Relative humidity <95% non condensing
Colour Light grey ( RAL 7035)
Noise 54dBA at 1m 60dBA at 1m   65dBA at 1m
Protection degree IP20
Efficiency Smart Mode Up to 98%
Compliance Safety:EN 62040-1-1(Directive 2006/95/EC); EMC:6200-2(Directive 2004/108/EC)
Weight(KG)N.W 176 220 205 213 295 440 520 770
Dimensions:(WxDxH)mm 555*730*1210 800*730*1400 1115*730*1400
Internal batteries optional optional optional No      No No No No
Description
HIGH INTELLIGENCE AND RELIABLE POWER SUPPLY IGBT Technology Full microprocessor control with no-break static and manual bypasses. Online double conversion technology (VFl) with isolation transformer on theinverter output. Extremely high short-circuit current to ensure compatibility with the most diffificult transformer applications (lighting, drives and industrial processes) and an isolation transformer on the inverter output. Compatibled with Watch & Save 3000 software as standard and can be remotely monitored using the Power NetGuard system from anywhere in the world. SIMPLE TO INSTALL Capability to install the UPS into any distribution system(neutral not required on rectifier input). Capability to separate the rectifier/bypass power networks and to power them from two separate sources, without Galvanic isolation(Necessary on UPS without an output transformer MAXIMUM BATTERY CARE Battery deep discharge protection; Temperature compensating charger; Built-in automatic and manual battery test feature. OTHER CHARACTERISTICS 0.8/0.9 power factor suitable for powering ICT and lndustrial loads. BACK FEED protection: to avoid energy feeding back into the mains supply cause a fault occur. MAXIMUM RELIABILITY AND AVAILABILITY Connect up to 6 units in parallel or N+1 redundancy, even of different power ratings. The UPS continue to work in parallel even if one of theinterconnecting communication cables is disconnected(CLOSED LOOP) LOW CONSUMPTION LEVELS LF33 Series UPS can achieve efficiencies >98% thanks to selectable Economy Mode which can be used in stable electrical environments to provide power supply continuity when the mains fail. ADVANCE COMMUNICATION: RS485/RS232/Dry Contact/SNMP(Optional)  
Specifications
Model 10KVA 20KVA 30KVA 40KVA 60KVA 80KVA 100KVA 120KVA 160KVA 200KVA 250KVA 300KVA 400KVA 500KVA 600KVA
Capacity 8KW 16 KW 24 KW 32 KW  48 KW 64 KW  80 KW 96 KW 128 KW 160 KW 200KW 240KW 320KW 400KW  480KW
INPUT
Rated voltage 400 VAC  Three-Phase
Voltage range 380/400/415VAC(+25%,Can be set through the LCD panel)
Frequency range 40-70Hz(Automatically select synchronization range according to grid frequency)
Range(HZ) 50±5%(±10%) Bypass synchronization tracking
Rectifying pulse number 6 pulse rectification 6/12 pulse rectification 12 pulse rectifier
Phase system 3φ4W+PE(Three phase five wire system)
Battery voltage 384VDC 480VDC
Battery Quantity Standard with 32 Cells(30~34, can be set through the LCD panel)  Standard 40 Cells(38~42 knots,can be set by LCD panel)
OUTPUT
Power factor 0.8/0.9 (Optional)
Voltage(V) L-N: 220±1%   L-L: 380±1%
Three-phase 100% load unbalance voltage stability ≤2%,Allow 100% imbalance
Frequency(HZ) Normal power, tracking the frequency of power, Grid abnormal. 50±0.2%
Transfer time(ms) 0ms
Parallel operation mode (parallel type) Max 8 Parallel
Waveform distortion Linear loadTHD<3% ; Nonlinear loadTHD<5%
Overload capacity 125% full load for 10 minutes, maintain 150 % full load for 1 minute and then switch to bypass power supply, after reducing the loadcan automatically restore the inverter
Crest factor 3:1
Others
Index Standard with no transfer time maintenance bypass switch
Communication function RS232/RS485/Dry Contact/SNMP (Optional)
Panel display LED displays working status and fault indication; LCD displays three-phase input voltage, input frequency, three-phase output voltage, load,battery voltage, battery charge and discharge current, etc
Display  7″ Touchable LCD screen display
The audio noise(dB) <65(within 1 meter)
Alarm function Battery low voltage, abnormal power supply, overload, UPS failure, over temperature protection
Protection Input over voltage, battery under voltage, overload, short circuit, over temperature protection
Cooling way Forced cooling
Operating temperature 0℃ to  ~ 40℃
Humidity 0~95%, non-condensing
electromagnetic compatibility Conform GB7260.2
Size(W*D*H)(mm) 540*660*1135 1100*800*1800 800*800*1900 1200*850*1900 2600*1100*2000
Weight 196     233 276 329 461 547.5 643 754 1375
Features:
  • True Double conversion Technology
  • DSP digital control technology enable UPS more stable performance.
  • Three Level inverter control technology
  • Large screen LCD display
  • N+X Parallel Redundancy function (3 units parallel)
  • EPO emergency stop function
  • Smart expansion Slots (optional)
  • Support Generator
 
Applications:
  • Mammogram
  • Ultrasound Equipments
  • Radiology rooms
 
Technical Specifications
Model VT6K VT6KL VT10K VT10KL 31VT10KL 31VT15KL 31VT20KL
Capacity 6KVA/5400W 10KVA/9000W 15KVA/13.5KW 20KVA/18KW
Input Nominal Voltage 220/230/240Vac 380/400/415Vac
Voltage Range 120-275VAC(1P2W+G) 207-475VAC(3P4W+G)
Current 31A (max) 50A(max) 50A (max) 75A(max) 100A(max)
Frequency 46-54Hz Synchronous mains power; 50Hz( Frequency Range 40-46Hz ~54-60Hz);50Hz(Battery mode)
Power Factor ≥0.99·
Output Voltage 220/230/240±2%Vac (1P2W+G)
Frequency 50/60 Hz(adjustable) 50/60Hz± 5% (Line mode) 50/60Hz ± 0.05Hz ( Battery mode)
Current 27.3A 45A 68A 91A
Power Factor 0.9
Waveform Pure Sine Wave
Waveform Distortion Line load <2% Line load <3%
Back-up Time Full Load ≥7′ Depends on external batteries bank’s Capacity ≥5′ Depends on external batteries bank’s Capacity
Half Load ≥20 ≥13′
Battery Nominal Voltage 192/240Vdc
Transfer Time 0ms
Overload Capacity 105%±5%< Load<125%±5% :1 min transfer to bypass 125% ±5% < Load<135 % ±5 % :30s transfer to bypass Load > 135 % ± 5 %: 300s transfer to bypass
Communication SNMP,RS-232,USB+lntelligent Slot
Operating Environment Temperature 0°C~40°C
Humidity 15%~90%
Dimension Width (mm) 260 260 260 260 260
Depth (mm) 560 533 560 533 560
Height (mm) 717 501 717 501 717
Net Weight(Kg) 55 12.2 62 21 23 32 33
Features:
  • 60KW single power module in 3U
  • N+1or N+X parallel redundancy for power guarantee
  • Supports horizontal expansion by 1+1 cabinet paralleloperation.
  • Hot-swappable modular design decreases MTTR
  • High scalability
  • Built-in maintenance bypass switch for easy maintenance without interruptible
  • High efficiency double conversion online UPS
  • Flexible battery configuration and adjustable charging current
  • High overload capability
  • Power walk-in function
  • Built-in dynamic password protection
  • Built-in ultra communication slot
 
Technical Specifications
MODEL RM Pro 120K RM Pro 180K RM Pro 300K RM Pro 420K RM Pro 480K RM Pro 600K
Phase 3 Phase in / 3 Phase out
Cabinet Capacity* 120 KW 180 KW 300KW 420KW 480KW 600KW
Battery  Type Extemal Battery
One Power Module Capacity 60KVA/60KW
Max.   Power Module  No. 2 3 5 7 8 10
INPUT
Nominal Voltage 3×380/400/415   VAC(3Ph+N)
Voltage Range -30%~+20%
Nominal Frequency 50/60Hz(Auto Sensing)
Frequency Range 40Hz~70Hz
Power Factor >0.99  @100%  Load, >0.98 @ 50%  Load
Harmonic  Distortion   (THDi) <3%@  100%  load
OUTPUT
Nominal Voltage 3×380/400/415 VAC (3Ph+N)
Voltage  Regulation(Steady  State) ≤±1% Typical(balanced load); ≤±2% Typical(unbalanced load)
Nominal Frequency 50/60Hz
Frequency Range(Synchronized) 46Hz~54Hz or 56Hz~64Hz
Overload Capability 1 hour for ≤110%,10 mins for 111%~125%,1 min for 126%~150% and 200ms for >150%
Haronic Distortion ≤2% THD (Linear Load);  ≤4% THD (Non-linear Load)
Eficiency 96%
BATTERY / CHARGER
Nominal Voltage ’+/- 192V~+/- 240V(Selectable)
Maximum Voltage ’+/- 240V (12V×40 PCS)
Minimum Voltage ‘+/-192V (12V×32 PCS)
Floating Charge Voltage 2.28V/Cell (2.25~2.33 Selectable)
Boost Charging Voltage 2.35V/Cell
Temperature Compensation Yes
Maximum Charging Current (Per Power Module) 18A(Adjustable)
PHYSICAL
Cabinet Dimension (DxWxH)mm 1100x600x1475 1100x600x1475 1100x600x2010 1100×600×2010 1065x1000x2000 1065×1000×2000
Net Weight (Kg) 308 352 516 654 932 1020
Power Module (PM-60) Net Weight 44KGS
ENVIRONMENT
Operating Temperature 0~40℃
Relative Humidity 0~95% non-condensing
Altitude* <1000m for Nominal power
IP  Protection IP 20
MANAGEMENT
Smart  RS-232/USB Supports Windows⑧ Family, Linux and MAC
Optional SNMP Power management from SNMP manager and web browser
STANDARDS
Safety IEC/EN62040-1
EMC IEC/EN 62040-2 Category C3
Features:
  • 50KW single power module in 3U
  • N+1or N+X parallel redundancy for power guarantee
  • Supports horizontal expansion by 1+1 cabinet paralleloperation.
  • Hot-swappable modular design decreases MTTR
  • High scalability
  • Built-in maintenance bypass switch for easy maintenance without interruptible
  • High efficiency double conversion online UPS
  • Flexible battery configuration and adjustable charging current
  • High overload capability
  • Power walk-in function
  • Built-in dynamic password protection
  • Built-in ultra communication slot
 
Specifications:
MODEL RM Plus 300K RM Plus 350K RM Plus 400K RM Plus 500K
Phase 3 Phase in / 3 Phase out
Cabinet Capacity* 300 KW 350 KW 400KW 500KW
Battery  Type Extemal Battery
One Power Module Capacity 50KVA/50KW
Max.   Power Module  No. 6 7 8 10
INPUT
Nominal Voltage 3×380/400/415 VAC (3Ph+N)
Voltage Range ’-20%~+15%
Nominal Frequency 50/60Hz(Auto Sensing)
Frequency Range 40Hz~70Hz
Power Factor >0.99  @100%  Load, >0.98@50%  Load
Harmonic  Distortion   (THDi) <4% @ 100%  load
OUTPUT
Nominal Voltage 3×380/400/415 VAC (3Ph+N)
Voltage  Regulation(Steady  State) ≤ ±1% Typical (balanced load); ~≤ ±2% Typical (unbalanced load)
Nominal Frequency 50/60Hz
Frequency Range(Synchronized) 46Hz~54Hz or 56Hz~64Hz
Overload Capability 1 hour for ≤110%,10 mins for 111%~125%,1 min for 126%~150% and 200ms for >150%
Haronic Distortion ≤2% THD (Linear Load); ≤4% THD (Non-linear Load)
Eficiency 95.50%
BATTERY / CHARGER
Nominal Voltage ‘+/- 192V~+/- 240V (Selectable)
Maximum Voltage ’+/- 240V (12V×40PCS)
Minimum Voltage ‘+/- 192V(12V×32PCS)
Floating Charge Voltage 2.28V/Cell (2.25~2.33 Selectable)
Boost Charging Voltage 2.35V/Cell
Temperature Compensation Yes
Maximum Charging Current (Per Power Module) 12A (Adjustable)
PHYSICAL
Cabinet Dimension (DxWxH)mm 1065x600x2000 1065x600x2000 1065x1000x2000 1065x1000x2000
Net Weight (Kg) 545 654 932 1020
Power Module (PM-50) Net Weight 44KGS
ENVIRONMENT
Operating Temperature 0~40℃
Relative Humidity 0~95% non-condensing
Altitude* <1000m for Nominal power
IP  Protection IP 20
MANAGEMENT
Smart  RS-232/USB Supports Windows⑧ Family, Linux and MAC
Optional SNMP Power management from SNMP manager and web browser
STANDARDS
Safety IEC/EN 62040-1
EMC IEC/EN 62040-2 Category C3
Features:
  • Valve sealed design, no free electrolyte, Maintenance -free
  • Designed floating service life:15 years @ 25 °C/68 °F.
  • Wide operating temperature range from -15°C to 35°C
  • Nanometer gel electrolytes eliminate the acid stratification and prolong cycle life
  • Low self-discharge rate: ≤3%/month.
 
Application
  • UPS Systems
  • Portable Equipment
  • Renewable Energy Systems
  • Electric Utilities
  • Outdoor control Equipment
  • Railroad Utilities
  • Telecom Systems
 
Technical Specifications
Model Nominal Voltage Capacity Dimension LXWXH (mm) Total Height (mm) Weight (KG/IBS) Terminal
VG12-33 12V 33AH 195 130 167 167 10 22.05 M6
VG12-35 12V 35AH 195 130 167 167 11.5 25.35 M6
VG12-38 12V 38AH 197 165 172 172 12.5 27.56 M6
VG12-40 12V 40AH 197 165 172 172 13.2 29.1 M6
VG12-45 12V 45AH 197 165 172 172 15 33.07 M6
VG12-50 12V 50AH 229 138 205 208 15.5 34.17 M6
VG12-55 12V 55AH 229 138 205 208 16.5 36.38 M6
VG12-65 12V 65AH 350 166 175 175 21 46.3 M8
VG12-70 12V 70AH 260 168 208 211 21.8 48.06 M8
VG12-80 12V 80AH 260 168 208 211 24 52.91 M8
VG12-90 12V 90AH 330 171 216 219 27 59.52 M8
VG12-100 12V 100AH 330 171 216 219 29.5 65.04 M8
VG12-120 12V 120AH 407 173 237 237 35 77.16 M8
VG12-150 12V 150AH 484 170 241 241 45 99.21 M8
VG12-200 12V 200AH 522 240 219 222 61.5 135.58 M8
VG12-250 12V 250AH 520 268 220 223 71 156.53 M8
WeightN/AN/AN/AN/AN/AN/A
DimensionsN/AN/AN/AN/AN/AN/A
Additional information
Select the fields to be shown. Others will be hidden. Drag and drop to rearrange the order.
  • Image
  • Rating
  • Price
  • Description
Click outside to hide the comparison bar
Compare