High Frequency Modular UPS RM Plus Series 300 KW-500KW

$0.00

Shipped From Abroad

Features:
  • 50KW single power module in 3U
  • N+1or N+X parallel redundancy for power guarantee
  • Supports horizontal expansion by 1+1 cabinet paralleloperation.
  • Hot-swappable modular design decreases MTTR
  • High scalability
  • Built-in maintenance bypass switch for easy maintenance without interruptible
  • High efficiency double conversion online UPS
  • Flexible battery configuration and adjustable charging current
  • High overload capability
  • Power walk-in function
  • Built-in dynamic password protection
  • Built-in ultra communication slot
Delivery & Availability:
Typically 10-21 working days – excluding furniture and heavy/bulky equipment. Please contact us for further information.
SF1033560130139-8
Brands:: Reeco Power

Description

Features:
  • 50KW single power module in 3U
  • N+1or N+X parallel redundancy for power guarantee
  • Supports horizontal expansion by 1+1 cabinet paralleloperation.
  • Hot-swappable modular design decreases MTTR
  • High scalability
  • Built-in maintenance bypass switch for easy maintenance without interruptible
  • High efficiency double conversion online UPS
  • Flexible battery configuration and adjustable charging current
  • High overload capability
  • Power walk-in function
  • Built-in dynamic password protection
  • Built-in ultra communication slot

 

Specifications:
MODEL RM Plus 300K RM Plus 350K RM Plus 400K RM Plus 500K
Phase 3 Phase in / 3 Phase out
Cabinet Capacity* 300 KW 350 KW 400KW 500KW
Battery  Type Extemal Battery
One Power Module Capacity 50KVA/50KW
Max.   Power Module  No. 6 7 8 10
INPUT
Nominal Voltage 3×380/400/415 VAC (3Ph+N)
Voltage Range ’-20%~+15%
Nominal Frequency 50/60Hz(Auto Sensing)
Frequency Range 40Hz~70Hz
Power Factor >0.99  @100%  Load, >0.98@50%  Load
Harmonic  Distortion   (THDi) <4% @ 100%  load
OUTPUT
Nominal Voltage 3×380/400/415 VAC (3Ph+N)
Voltage  Regulation(Steady  State) ≤ ±1% Typical (balanced load); ~≤ ±2% Typical (unbalanced load)
Nominal Frequency 50/60Hz
Frequency Range(Synchronized) 46Hz~54Hz or 56Hz~64Hz
Overload Capability 1 hour for ≤110%,10 mins for 111%~125%,1 min for 126%~150% and 200ms for >150%
Haronic Distortion ≤2% THD (Linear Load); ≤4% THD (Non-linear Load)
Eficiency 95.50%
BATTERY / CHARGER
Nominal Voltage ‘+/- 192V~+/- 240V (Selectable)
Maximum Voltage ’+/- 240V (12V×40PCS)
Minimum Voltage ‘+/- 192V(12V×32PCS)
Floating Charge Voltage 2.28V/Cell (2.25~2.33 Selectable)
Boost Charging Voltage 2.35V/Cell
Temperature Compensation Yes
Maximum Charging Current
(Per Power Module)
12A (Adjustable)
PHYSICAL
Cabinet Dimension (DxWxH)mm 1065x600x2000 1065x600x2000 1065x1000x2000 1065x1000x2000
Net Weight (Kg) 545 654 932 1020
Power Module (PM-50) Net Weight 44KGS
ENVIRONMENT
Operating Temperature 0~40℃
Relative Humidity 0~95% non-condensing
Altitude* <1000m for Nominal power
IP  Protection IP 20
MANAGEMENT
Smart  RS-232/USB Supports Windows⑧ Family, Linux and MAC
Optional SNMP Power management from SNMP manager and web browser
STANDARDS
Safety IEC/EN 62040-1
EMC IEC/EN 62040-2 Category C3

Reviews

There are no reviews yet.

Be the first to review “High Frequency Modular UPS RM Plus Series 300 KW-500KW”

Your email address will not be published. Required fields are marked *

Quick Comparison

SettingsHigh Frequency Modular UPS RM Plus Series 300 KW-500KW removeHigh Frequency Modular UPS RM Pro Series remove3 Phase Low Frequency Solar Inverter DX Series removeHigh Frequency Rack Mount UPS 33RM Series removeHigh Frequency Rack Mount UPS RTX Series remove3 Phase High Frequency Online UPS remove
NameHigh Frequency Modular UPS RM Plus Series 300 KW-500KW removeHigh Frequency Modular UPS RM Pro Series remove3 Phase Low Frequency Solar Inverter DX Series removeHigh Frequency Rack Mount UPS 33RM Series removeHigh Frequency Rack Mount UPS RTX Series remove3 Phase High Frequency Online UPS remove
Image
SKUSF1033560130139-8SF1033560130139-10SF1033560130139-5SF1033560130139-12SF1033560130139-13SF1033560130139-1
Rating
Price

$0.00

$0.00

$0.00

$0.00

$0.00

$0.00

Stock
Availability
Add to cart

DescriptionShipped From Abroad
Features:
  • 50KW single power module in 3U
  • N+1or N+X parallel redundancy for power guarantee
  • Supports horizontal expansion by 1+1 cabinet paralleloperation.
  • Hot-swappable modular design decreases MTTR
  • High scalability
  • Built-in maintenance bypass switch for easy maintenance without interruptible
  • High efficiency double conversion online UPS
  • Flexible battery configuration and adjustable charging current
  • High overload capability
  • Power walk-in function
  • Built-in dynamic password protection
  • Built-in ultra communication slot
Delivery & Availability: Typically 10-21 working days – excluding furniture and heavy/bulky equipment. Please contact us for further information.
Shipped From Abroad
Features:
  • 60KW single power module in 3U
  • N+1or N+X parallel redundancy for power guarantee
  • Supports horizontal expansion by 1+1 cabinet paralleloperation.
  • Hot-swappable modular design decreases MTTR
  • High scalability
  • Built-in maintenance bypass switch for easy maintenance without interruptible
  • High efficiency double conversion online UPS
  • Flexible battery configuration and adjustable charging current
  • High overload capability
  • Power walk-in function
  • Built-in dynamic password protection
  • Built-in ultra communication slot
Delivery & Availability: Typically 10-21 working days – excluding furniture and heavy/bulky equipment. Please contact us for further information.
Shipped From Abroad
Delivery & Availability: Typically 10-21 working days – excluding furniture and heavy/bulky equipment. Please contact us for further information.
Shipped From Abroad
Features:
1)19 inches standard design of rack mount, compact structure. 2)Sin wave output provides best power supply guarantee. 3)Zero transfer time between mains mode and battery mode. 4)Detection function of input neutral wire and live wire. 5)Having voltage surge protection function and strong anti-interference function. 6)Equipped with correction function of input power factor 7) Supporting mobile smart monitoring card , users can real-time monitor every data of the UPS by mobile APP.
Delivery & Availability: Typically 10-21 working days – excluding furniture and heavy/bulky equipment. Please contact us for further information.
Shipped From Abroad Features:
  • DSP digital control technology enables UPS more stable performance-+
  • Environment friendly eco-designed
  • Active input power factor correction
  • Wide range of input voltage and frequency
  • Zero power switch delay
  • Adaptive Load Management.
  • Sufficient Expansion Slots: USB ,RS485 ,AS400 SNMP cards(Optional)
  • Support the generator
Delivery & Availability: Typically 10-21 working days – excluding furniture and heavy/bulky equipment. Please contact us for further information.
Content
Features:
  • 50KW single power module in 3U
  • N+1or N+X parallel redundancy for power guarantee
  • Supports horizontal expansion by 1+1 cabinet paralleloperation.
  • Hot-swappable modular design decreases MTTR
  • High scalability
  • Built-in maintenance bypass switch for easy maintenance without interruptible
  • High efficiency double conversion online UPS
  • Flexible battery configuration and adjustable charging current
  • High overload capability
  • Power walk-in function
  • Built-in dynamic password protection
  • Built-in ultra communication slot
 
Specifications:
MODEL RM Plus 300K RM Plus 350K RM Plus 400K RM Plus 500K
Phase 3 Phase in / 3 Phase out
Cabinet Capacity* 300 KW 350 KW 400KW 500KW
Battery  Type Extemal Battery
One Power Module Capacity 50KVA/50KW
Max.   Power Module  No. 6 7 8 10
INPUT
Nominal Voltage 3×380/400/415 VAC (3Ph+N)
Voltage Range ’-20%~+15%
Nominal Frequency 50/60Hz(Auto Sensing)
Frequency Range 40Hz~70Hz
Power Factor >0.99  @100%  Load, >0.98@50%  Load
Harmonic  Distortion   (THDi) <4% @ 100%  load
OUTPUT
Nominal Voltage 3×380/400/415 VAC (3Ph+N)
Voltage  Regulation(Steady  State) ≤ ±1% Typical (balanced load); ~≤ ±2% Typical (unbalanced load)
Nominal Frequency 50/60Hz
Frequency Range(Synchronized) 46Hz~54Hz or 56Hz~64Hz
Overload Capability 1 hour for ≤110%,10 mins for 111%~125%,1 min for 126%~150% and 200ms for >150%
Haronic Distortion ≤2% THD (Linear Load); ≤4% THD (Non-linear Load)
Eficiency 95.50%
BATTERY / CHARGER
Nominal Voltage ‘+/- 192V~+/- 240V (Selectable)
Maximum Voltage ’+/- 240V (12V×40PCS)
Minimum Voltage ‘+/- 192V(12V×32PCS)
Floating Charge Voltage 2.28V/Cell (2.25~2.33 Selectable)
Boost Charging Voltage 2.35V/Cell
Temperature Compensation Yes
Maximum Charging Current (Per Power Module) 12A (Adjustable)
PHYSICAL
Cabinet Dimension (DxWxH)mm 1065x600x2000 1065x600x2000 1065x1000x2000 1065x1000x2000
Net Weight (Kg) 545 654 932 1020
Power Module (PM-50) Net Weight 44KGS
ENVIRONMENT
Operating Temperature 0~40℃
Relative Humidity 0~95% non-condensing
Altitude* <1000m for Nominal power
IP  Protection IP 20
MANAGEMENT
Smart  RS-232/USB Supports Windows⑧ Family, Linux and MAC
Optional SNMP Power management from SNMP manager and web browser
STANDARDS
Safety IEC/EN 62040-1
EMC IEC/EN 62040-2 Category C3
Features:
  • 60KW single power module in 3U
  • N+1or N+X parallel redundancy for power guarantee
  • Supports horizontal expansion by 1+1 cabinet paralleloperation.
  • Hot-swappable modular design decreases MTTR
  • High scalability
  • Built-in maintenance bypass switch for easy maintenance without interruptible
  • High efficiency double conversion online UPS
  • Flexible battery configuration and adjustable charging current
  • High overload capability
  • Power walk-in function
  • Built-in dynamic password protection
  • Built-in ultra communication slot
 
Technical Specifications
MODEL RM Pro 120K RM Pro 180K RM Pro 300K RM Pro 420K RM Pro 480K RM Pro 600K
Phase 3 Phase in / 3 Phase out
Cabinet Capacity* 120 KW 180 KW 300KW 420KW 480KW 600KW
Battery  Type Extemal Battery
One Power Module Capacity 60KVA/60KW
Max.   Power Module  No. 2 3 5 7 8 10
INPUT
Nominal Voltage 3×380/400/415   VAC(3Ph+N)
Voltage Range -30%~+20%
Nominal Frequency 50/60Hz(Auto Sensing)
Frequency Range 40Hz~70Hz
Power Factor >0.99  @100%  Load, >0.98 @ 50%  Load
Harmonic  Distortion   (THDi) <3%@  100%  load
OUTPUT
Nominal Voltage 3×380/400/415 VAC (3Ph+N)
Voltage  Regulation(Steady  State) ≤±1% Typical(balanced load); ≤±2% Typical(unbalanced load)
Nominal Frequency 50/60Hz
Frequency Range(Synchronized) 46Hz~54Hz or 56Hz~64Hz
Overload Capability 1 hour for ≤110%,10 mins for 111%~125%,1 min for 126%~150% and 200ms for >150%
Haronic Distortion ≤2% THD (Linear Load);  ≤4% THD (Non-linear Load)
Eficiency 96%
BATTERY / CHARGER
Nominal Voltage ’+/- 192V~+/- 240V(Selectable)
Maximum Voltage ’+/- 240V (12V×40 PCS)
Minimum Voltage ‘+/-192V (12V×32 PCS)
Floating Charge Voltage 2.28V/Cell (2.25~2.33 Selectable)
Boost Charging Voltage 2.35V/Cell
Temperature Compensation Yes
Maximum Charging Current (Per Power Module) 18A(Adjustable)
PHYSICAL
Cabinet Dimension (DxWxH)mm 1100x600x1475 1100x600x1475 1100x600x2010 1100×600×2010 1065x1000x2000 1065×1000×2000
Net Weight (Kg) 308 352 516 654 932 1020
Power Module (PM-60) Net Weight 44KGS
ENVIRONMENT
Operating Temperature 0~40℃
Relative Humidity 0~95% non-condensing
Altitude* <1000m for Nominal power
IP  Protection IP 20
MANAGEMENT
Smart  RS-232/USB Supports Windows⑧ Family, Linux and MAC
Optional SNMP Power management from SNMP manager and web browser
STANDARDS
Safety IEC/EN62040-1
EMC IEC/EN 62040-2 Category C3
Features:
Three Phase Hybrid Solar Inverter Off grid three phase solar hybrid inverter with pwm/mppt can be used in single-phase and three-phase ac load with total power not exceeding  100kva/120kva/125kva/150kva/160kva,384vdc to 380vac. •Pure sine wave output. •Low DC voltage, saving system cost. •Three phase solar inverter with built-in PWM or MPPT charge controller. •AC charge current 0-45A adjustable. •Wide LCD screen, clearly and precisely shows icon data. •100%imbalance loading design, 3 times peak power. •Setting different working modes based on variable usage requirements. •DC first/AC first optional. •Various communication ports and remote controls  
Specifications
MODEL DX100KVA DX120KVA DX125KVA DX150KVA DX160KVA 190KVA 200KVA
Rated Power 80KW 96KW 100KW 120KW 128KW 150KW 160KW
Peak Power(20ms) 240KVA 288KVA 300KVA 360KVA 384KVA 450KVA 480KVA
Start Motor 40HP 50HP 50HP 60HP 60HP 80HP 80HP
Battery Voltage 384VDC
Size(L*W*Hmm) 875*720*1380 1123*900*1605
Packing Size(L*W*Hmm) 980*825*1560 1185*960*1750
N.W.(kg) 512 592 612 612 642 705 755
G.W.(kg)(Wooden Packing) 552 632 652 652 692 755 805
INPUT DC Input Voltage Range 10.5VDC-15VDC(Single battery voltage)
AC Input Voltage Range 380Vac/400Vac±10%(customized 190Vac/200Vac)
AC Input Frequency Range 45Hz-55Hz(50Hz)/ 55Hz-65Hz(60Hz)
Max AC charging current 0-45A(Depending on the model)
AC charging method Three-stage (constant current, constant voltage, floating charge)
Phase 3 PHASE
OUTPUT Efficiency(Battery Mode) ≥85%
Output Voltage(Battery Mode) 380Vac/400Vac±10%(customized 190Vac/200Vac)
Output Frequency(Battery Mode) 50/60Hz ±1%
Output Wave(Battery Mode) Pure Sine Wave
Output waveform distortion Linear load≤3%
Efficiency(AC Mode) >99%
Output Voltage(AC Mode) Conforming to AC input
Output Frequency(AC Mode) Conforming to AC input
No load loss(Battery Mode) ≤1% rated power
No load loss(AC Mode) ≤2%rated power( charger does not work in AC mode)
No load loss (Energy saving Mode) ≤10W
Phase 3 PHASE
BATTERY VRLA Battery Charge Voltage :13.8V; Float Voltage:13.7V(Single battery voltage)
Customize battery Charging and discharging parameters of different types of batteries can be customized according to user requirements
(charging and discharging parameters of different types of batteries can be set through the operation panel)
Protection Battery undervoltage alarm 11V(Single battery voltage)
Battery undervoltage protection 10.5V(Single battery voltage)
Battery overvoltage alarm 15V(Single battery voltage)
Battery overvoltage protection 17V(Single battery voltage)
Battery overvoltage recovery voltage 14.5V(Single battery voltage)
Overload power protection Automatic protection (battery mode), circuit breaker or insurance (AC mode)
Inverter output short circuit protection Automatic protection (battery mode), circuit breaker or insurance (AC mode)
Temperature protection >90°C(Shut down output)
Alarm A Normal working condition, buzzer has no alarm sound
B Buzzer sounds 4 times per second when battery failure, voltage abnormality, overload protection
C When the machine is turned on for the first time, the buzzer will prompt 5 when the machine is normal
Inside Solar controller Charging Mode MPPT or PWM
(Optional) Charging current PWM: 100A-200A / MPPT: 50A/100A
PV Input Voltage Range PWM: 480V-704V / MPPT: 480V-640V
Max PV Input Voltage(Voc) PWM: 750V / MPPT: 800V
(At the lowest temperature)
PV Array Maximum Power PWM: 44.8KW(100A)/33.6KW*2(150A)/44.8KW*2(200A)) / (MPPT: 22.4KW(50A)/22.4KW*2(100A)
Standby loss ≤3W
Maximum conversion efficiency >95%
Working Mode Battery First/AC First/Saving Energy Mode
Transfer Time ≤4ms
Display LCD
Thermal method Forced Air Cooling
Communication(Optional) RS485/APP(WIFI monitoring or GPRS monitoring)
Environment Operating temperature -10℃~40℃
Storage temperature -15℃~60℃
Noise 2000m(More than derating)
Elevation ≤65dB
Humidity 0%~95% ,No condensation
Features:
  • True double-conversion
  • LCD screen auto-rotation with Rack position ( only for 10K-20K models)
  • DSP technology guarantees high performance
  • Output power factor 1
  • Support 1/1;3/1;3/3 Phase Adjustable
  • Active power factor correction in all phases
  • 50HZ / 60HZ frequency converter mode
  • ECO mode operation for energy saving ( ECO)
  • Emergency power off function ( EPO)
  • Generator compatible
  • Supports dual AC inputs
  • 3-stage extendable charging design for optimized battery performance
  • Adjustable battery numbers for long-run model
  • Supporting Parallel sharing of battery packs
  • Optional isolation transformer offers full isolation and complete common mode noise rejection
  • Support with SNMP,USB, RS232 communication
 
Technical Specifications
MODEL 33RM 10KL 33RM 15KL 33RM 20KL 33RM 30KL 33RM 40KL 33RM 60KL
CAPACITY 10KVA/10KW 15KVA/15KW 20KVA/20KW 30KVA/30KW 40KVA/40KW 60KVA/60KW
PHASE 3 Phase input / 3 Phase output
PARALLEL CAPABILITY 4 Max
INPUT
Nominal Voltage 3×380 VAC (3Ph+N)
Voltage Range 190-520 VAC (3 Phase) @ 50% load , 305-478 VAC (3 Phase) @ 100% load
Frequency Range 46-54 Hz or 56~64Hz
Power Factor ≥ 0.99 @ 100% load
OUTPUT
Output Voltage 3 x 360*/380/400/415 VAC (3Ph+N)
AC Voltage Regulation (Batt. Mode) ± 1%
Frequency Range (Synchronized Range) 46~54Hz or 56~64Hz
Frequency Range (Batt. Mode) 50 Hz ±0.1 Hz or 60 Hz ±0.1 Hz
Current Crest Ratio 3:1 (max.)
Harmonic Distortion ≤1 % THD (Linear Load), ≤3% THD (Non-linear Load)
Transfer Time AC mode to Battery mode zero
Inverter to Bypass zero
Waveform (Batt. Mode) Pure Sine Wave
Overload AC Mode 100-110% for 60 min, 110-125% for 10 min, 125%~150% for 1 min; >150% immediately Protection
Battery Mode 100-110% for 60 min, 110-125% for 10 min, 125%~150% for 1 min; >150% immediately Protection
EFFICIENCY
AC Mode 95.5%
ECO Mode 98.5%
Battery Mode 94.5%
BATTERY
Battery Type Depending on the applications
Numbers 20 pcs 32-40 pcs (Adjustable)
Charging Current (max.) 1A~ 12A (Adjustable) 1A~ 16A (Adjustable) 1A 〜18A (Adjustable)
Charging Voltage ±13.65 VDCx N (N=10) ±13.65VxN (N=16〜20)
PHYSICAL
Dimension, D * W * H (mm) 680*438*133 [3U] 797*438*176 [4U]
Net Weight (kgs) 27 30 40 45
ENVIRONMENT
Operation Temperture 0-40°C
Operation Humidity 0-95% and non-condersing
Noise Level Less than 62dB @ 1 Meter Less than 65dB @ 1 Meter Less than 70dB @ 1 Meter
MANAGEMENT
Smart RS-232/USB Supports Windows® Family, Linux and MAC
Optional SNMP Power management from SNMP manager and web browser
Features:
1)19 inches standard design of rack mount, compact structure. 2)Sin wave output provides best power supply guarantee. 3)Zero transfer time between mains mode and battery mode. 4)Detection function of input neutral wire and live wire. 5)Having voltage surge protection function and strong anti-interference function. 6)Equipped with correction function of input power factor 7) Supporting mobile smart monitoring card , users can real-time monitor every data of the UPS by mobile APP.  
Technical Specifications
Model RTX3110KL RTX3115KL RTX3120KL
Rated Power 10kVA/9kW 15kVA/13.5kW 20kVA/18kW
INPUT Voltage Range 207-475Vac3P4W+G
Working Frequency Range 40-70HZ (settable)
Input Power Factor >0.95
OUTPUT Rated Voltage and Accuracy 220Vac(l±l%)lP2W+G
Output Frequency 46-54Hz synchronize with mains power; 50Hz (Mains power between 40-46Hz and 54-60Hz); 50Hz(Battery)
Rated Current 45A 68A 91A
Output Power Factor 0.9
Output Harmonic Wave W3%
Crest Factor  3:1
Output Overload 105%±5%<Load≤125%±5%: Convert to bypass output and alarm after 1 min; 125%±5%<Load ≤50%±5%: Convert to bypass output and alarm after 30s; Load>150%±5%: Convert to bypass output and alarm after 300ms.
Transfer Time 0ms
Efficiency >92%
BATTERY Rated Voltage 192Vdc
Quantity 16
Charging Current 5.5A
Dimension (LxWxH) mm 665*482.6*132.5 655*482.6*265
Weight 23kg 34kg 35kg
Working Temperature 0°〜40°C
Working Humidity 20% 〜95%
Noise ≤60dB
Features:
  • DSP digital control technology enables UPS more stable performance-+
  • Environment friendly eco-designed
  • Active input power factor correction
  • Wide range of input voltage and frequency
  • Zero power switch delay
  • Adaptive Load Management.
  • Sufficient Expansion Slots: USB ,RS485 ,AS400 SNMP cards(Optional)
  • Support the generator
 
Specifications:
Model 33VT 10K 33VT 10KL 33VT 20K 33VT 20KL 33VT 30KL 33VT 40KL
Capacity 10KVA/9000W 20KVA/18KW 30KVA/27KW 40KVA/36KW
Input Nominal Voltage 380/400/415Vac
Voltage Range 207-475VAC(3P4W+G)
Current 14A 28A 42A 67A
Frequency 40-70Hz (Adjustable)
Power Factor ≥0.99
Output Voltage 380VAC 1±1% (3P4W+G)
Frequency 46-54Hz Synchronous mains power; 50Hz( Frequency Range 40-46Hz -54-60Hz);50Hz(Battery mode)
Current 15A 30A 45A 61A
Power Factor 0.9
Crest Factor 3:1
THD Line load <3%
Chrage Current 5.5A 1A 7.5A 1A 5.5A
Battery Nominal Voltage 192VDC ±192VDC
Transfer Time 0ms
Overload Capacity 105%±5%< Load<125%±5% :1 min transfer to bypass 125% ±5% < Load<135 % ±5 % :30s transfer to bypass Load > 135 % ± 5 %: 300s transfer to bypass
Communication SNMP,RS-232,USB+lntelligent Slot
Operating Environment Temperature 0°C~40°C
Humidity 20%~95%
Dimension Width (mm) 260 260 260 260
Depth (mm) 560 533 710 560
Height (mm) 717 501 717 717
Net Weight(Kg) 26 72 57.5 98 58.5 62
WeightN/AN/AN/AN/AN/AN/A
DimensionsN/AN/AN/AN/AN/AN/A
Additional information
Select the fields to be shown. Others will be hidden. Drag and drop to rearrange the order.
  • Image
  • Rating
  • Price
  • Description
Click outside to hide the comparison bar
Compare