Features:
50KW single power module in 3U
N+1or N+X parallel redundancy for power guarantee
Supports horizontal expansion by 1+1 cabinet paralleloperation.
Hot-swappable modular design decreases MTTR
High scalability
Built-in maintenance bypass switch for easy maintenance without interruptible
High efficiency double conversion online UPS
Flexible battery configuration and adjustable charging current
High overload capability
Power walk-in function
Built-in dynamic password protection
Built-in ultra communication slot
Delivery & Availability:Typically 10-21 working days – excluding furniture and heavy/bulky equipment. Please contact us for further information.
Shipped From Abroad
Features:
Pure sine wave output
DSP digital control
Boost and buck AVR for voltage stabilization
Cold start function
Intelligent battery management
Short circuit and overload protection
Off-mode charging
Offering LED and LCD panels for selection
Optional USB/RS232/RJ45/SNMP communication port
Delivery & Availability:Typically 10-21 working days – excluding furniture and heavy/bulky equipment. Please contact us for further information.
Shipped From Abroad
Features:
1)19 inches standard design of rack mount, compact structure.
2)Sin wave output provides best power supply guarantee.
3)Zero transfer time between mains mode and battery mode.
4)Detection function of input neutral wire and live wire.
5)Having voltage surge protection function and strong anti-interference function.
6)Equipped with correction function of input power factor
7) Supporting mobile smart monitoring card , users can real-time monitor every data of the UPS by mobile APP.
Delivery & Availability:Typically 10-21 working days – excluding furniture and heavy/bulky equipment. Please contact us for further information.
Content
Features:
Rated Power: 1000W
Rated Capacity: 932.4wh
Standard Capacity: 3.7V/252000mah
Overload Protecion: 1050+40W
AC Output: AC 110V+10%/60HZ 230V+10%/50HZ
Output Wave: Pure sine wave
USB Output: QC 18W*2
Type-c Output: PD 60W*2
Cigarret Lighter Output: 14V/8A
DC5525 Output: 14V/8A
Wireless Charging: 15W
Charging Input: 12-26 V/150W Max
WorkingTemperature: -10-40 °C
Weight(Net Weight): 8. 2kg
Weight(With Accessories): 10.2kg
Dimension: 345*227*203mm
Applications:
Mammogram
Ultrasound Equipments
Radiology rooms
Description
HIGH INTELLIGENCE AND RELIABLE POWER SUPPLYIGBT Technology
Full microprocessor control with no-break static and manual bypasses.
Online double conversion technology (VFl) with isolation transformer on theinverter output.
Extremely high short-circuit current to ensure compatibility with the most diffificult transformer applications (lighting, drives and industrial processes) and an isolation transformer on the inverter output.
Compatibled with Watch & Save 3000 software as standard and can be remotely monitored using the Power NetGuard system from anywhere in the world.
SIMPLE TO INSTALL
Capability to install the UPS into any distribution system(neutral not required on rectifier input).
Capability to separate the rectifier/bypass power networks and to power them from two separate sources, without Galvanic isolation(Necessary on UPS without an output transformer
MAXIMUM BATTERY CARE
Battery deep discharge protection;
Temperature compensating charger;
Built-in automatic and manual battery test feature.
OTHER CHARACTERISTICS
0.8/0.9 power factor suitable for powering ICT and lndustrial loads.
BACK FEED protection: to avoid energy feeding back into the mains supply cause a fault occur.
MAXIMUM RELIABILITY AND AVAILABILITY
Connect up to 6 units in parallel or N+1 redundancy, even of different power ratings.
The UPS continue to work in parallel even if one of theinterconnecting communication cables is disconnected(CLOSED LOOP)
LOW CONSUMPTION LEVELS
LF31 Series UPS can achieve efficiencies >98% thanks to selectable Economy Mode which can be used in stable electrical environments to provide power supply continuity when the mains fail.
ADVANCE COMMUNICATION:
RS485/RS232/Dry Contact/SNMP(Optional)
Specifications
Model
10KVA
15KVA
20KVA
30KVA
40KVA
60KVA
80KVA
100KVA
Capacity
8KW
12 KW
16 KW
24 KW
32 KW
48 KW
64 KW
80 KW
INPUT
Rated voltage
380/400/415 VAC Three-phase
Voltage range
±20%
Frequency range
45-65Hz
Power factor
>0.92 with harmonic filter
Current harmonic distortion
<5% with harmonic filter
Soft Start
0 -100% in 10″
BYPASS INPUT
Rated voltage
230VAC Single Phase
Permitted voltage range
±15% (selectable from ±10% to ±25% from front panel)
HIGH INTELLIGENCE AND RELIABLE POWER SUPPLYIGBT Technology
Full microprocessor control with no-break static and manual bypasses.
Online double conversion technology (VFl) with isolation transformer on theinverter output.
Extremely high short-circuit current to ensure compatibility with the most diffificult transformer applications (lighting, drives and industrial processes) and an isolation transformer on the inverter output.
Compatibled with Watch & Save 3000 software as standard and can be remotely monitored using the Power NetGuard system from anywhere in the world.
SIMPLE TO INSTALL
Capability to install the UPS into any distribution system(neutral not required on rectifier input).
Capability to separate the rectifier/bypass power networks and to power them from two separate sources, without Galvanic isolation(Necessary on UPS without an output transformer
MAXIMUM BATTERY CARE
Battery deep discharge protection;
Temperature compensating charger;
Built-in automatic and manual battery test feature.
OTHER CHARACTERISTICS
0.8/0.9 power factor suitable for powering ICT and lndustrial loads.
BACK FEED protection: to avoid energy feeding back into the mains supply cause a fault occur.
MAXIMUM RELIABILITY AND AVAILABILITY
Connect up to 6 units in parallel or N+1 redundancy, even of different power ratings.
The UPS continue to work in parallel even if one of theinterconnecting communication cables is disconnected(CLOSED LOOP)
LOW CONSUMPTION LEVELS
LF33 Series UPS can achieve efficiencies >98% thanks to selectable Economy Mode which can be used in stable electrical environments to provide power supply continuity when the mains fail.
ADVANCE COMMUNICATION:
RS485/RS232/Dry Contact/SNMP(Optional)
Specifications
Model
10KVA
20KVA
30KVA
40KVA
60KVA
80KVA
100KVA
120KVA
160KVA
200KVA
250KVA
300KVA
400KVA
500KVA
600KVA
Capacity
8KW
16 KW
24 KW
32 KW
48 KW
64 KW
80 KW
96 KW
128 KW
160 KW
200KW
240KW
320KW
400KW
480KW
INPUT
Rated voltage
400 VAC Three-Phase
Voltage range
380/400/415VAC(+25%,Can be set through the LCD panel)
Frequency range
40-70Hz(Automatically select synchronization range according to grid frequency)
Range(HZ)
50±5%(±10%) Bypass synchronization tracking
Rectifying pulse number
6 pulse rectification
6/12 pulse rectification
12 pulse rectifier
Phase system
3φ4W+PE(Three phase five wire system)
Battery voltage
384VDC
480VDC
Battery Quantity
Standard with 32 Cells(30~34, can be set through the LCD panel) Standard 40 Cells(38~42 knots,can be set by LCD panel)
OUTPUT
Power factor
0.8/0.9 (Optional)
Voltage(V)
L-N: 220±1% L-L: 380±1%
Three-phase 100% load
unbalance voltage stability
≤2%,Allow 100% imbalance
Frequency(HZ)
Normal power, tracking the frequency of power, Grid abnormal. 50±0.2%
Transfer time(ms)
0ms
Parallel operation mode
(parallel type)
Max 8 Parallel
Waveform distortion
Linear loadTHD<3% ; Nonlinear loadTHD<5%
Overload capacity
125% full load for 10 minutes, maintain 150 % full load for 1 minute and then switch to bypass power supply,
after reducing the loadcan automatically restore the inverter
Crest factor
3:1
Others
Index
Standard with no transfer time maintenance bypass switch
Communication function
RS232/RS485/Dry Contact/SNMP (Optional)
Panel display
LED displays working status and fault indication; LCD displays three-phase input voltage,
input frequency, three-phase output voltage, load,battery voltage, battery charge and discharge current, etc
Display
7″ Touchable LCD screen display
The audio noise(dB)
<65(within 1 meter)
Alarm function
Battery low voltage, abnormal power supply, overload, UPS failure, over temperature protection
Protection
Input over voltage, battery under voltage, overload, short circuit, over temperature protection
Cooling way
Forced cooling
Operating temperature
0℃ to ~ 40℃
Humidity
0~95%, non-condensing
electromagnetic compatibility
Conform GB7260.2
Size(W*D*H)(mm)
540*660*1135
1100*800*1800
800*800*1900
1200*850*1900
2600*1100*2000
Weight
196
233
276
329
461
547.5
643
754
1375
Features:
50KW single power module in 3U
N+1or N+X parallel redundancy for power guarantee
Supports horizontal expansion by 1+1 cabinet paralleloperation.
Hot-swappable modular design decreases MTTR
High scalability
Built-in maintenance bypass switch for easy maintenance without interruptible
High efficiency double conversion online UPS
Flexible battery configuration and adjustable charging current
1 hour for ≤110%,10 mins for 111%~125%,1 min for 126%~150% and 200ms for >150%
Haronic Distortion
≤2% THD (Linear Load); ≤4% THD (Non-linear Load)
Eficiency
95.50%
BATTERY / CHARGER
Nominal Voltage
‘+/- 192V~+/- 240V (Selectable)
Maximum Voltage
’+/- 240V (12V×40PCS)
Minimum Voltage
‘+/- 192V(12V×32PCS)
Floating Charge Voltage
2.28V/Cell (2.25~2.33 Selectable)
Boost Charging Voltage
2.35V/Cell
Temperature Compensation
Yes
Maximum Charging Current
(Per Power Module)
12A (Adjustable)
PHYSICAL
Cabinet Dimension (DxWxH)mm
1065x600x2000
1065x600x2000
1065x1000x2000
1065x1000x2000
Net Weight (Kg)
545
654
932
1020
Power Module (PM-50) Net Weight
44KGS
ENVIRONMENT
Operating Temperature
0~40℃
Relative Humidity
0~95% non-condensing
Altitude*
<1000m for Nominal power
IP Protection
IP 20
MANAGEMENT
Smart RS-232/USB
Supports Windows⑧ Family, Linux and MAC
Optional SNMP
Power management from SNMP manager and web browser
STANDARDS
Safety
IEC/EN 62040-1
EMC
IEC/EN 62040-2 Category C3
Features:
Pure sine wave output
DSP digital control
Boost and buck AVR for voltage stabilization
Cold start function
Intelligent battery management
Short circuit and overload protection
Off-mode charging
Offering LED and LCD panels for selection
Optional USB/RS232/RJ45/SNMP communication port
Technical Specifications
MODEL
UPS-AP1K ( L )
UPS-AP2K ( L )
UPS-AP3K ( L )
Capacity
1000VA/700W
2000VA/1400W
3000VA/2100W
INPUT
Voltage range
145~275VAC±5V
Frequency range
50Hz-60Hz
OUTPUT
Output voltage
220VAC
AC voltage range
±10%
Frequency range(batt.mode)
50Hz ± 0.25Hz or 60Hz ± 0.3Hz
Overload
105%-110%: UPS beep alarm, do not shut down.
110%-130%: auto shut down after 30 seconds
> 130%: auto shut down immediately
Transfer time
<typical 4ms
Waveform(batt.mode)
Pure sine wave
BATTERY
Standard model
Battery type
12V7Ah
Numbers
2
4
6
Charging current(Max.)
Assume: 1A± 10%; Max: 1A or 2A for option
Charging voltage
27.3VDC±1%
54.7VDC±1%
82.0VDC±1%
Long-run model
Battery type
12V, AH depending on applicant
Numbers
3
6
8
Charging current(Max.)
> 5A
Charging voltage
27.4VDC±1%
82.1VDC±1%
109.4VDC±1%
PHYSICAL
Standard model
Dimension, LxWxH(mm)
360x147x220
440x192x340
440x192x340
Net weight(kgs)
11.9
22
27.9
Long-run model
Dimension, LxWxH(mm)
360x147x220
440x192x340
440x192x340
Net weight(kgs)
8.5
16
18.2
ENVIRONMENT
Humidity
20-90%RH @0-40°C (non-condensing)
Noise level
Less than 55dBA@1 Meter
MANAGEMENT
Smart RS-232
Support windows 2000/2003/XP/Vista/2008, Windows7/8, Linux, Unix, and MAC
Optional SNMP
Power management from SNMP Management and web browser
Features:
1)19 inches standard design of rack mount, compact structure.
2)Sin wave output provides best power supply guarantee.
3)Zero transfer time between mains mode and battery mode.
4)Detection function of input neutral wire and live wire.
5)Having voltage surge protection function and strong anti-interference function.
6)Equipped with correction function of input power factor
7) Supporting mobile smart monitoring card , users can real-time monitor every data of the UPS by mobile APP.
Technical Specifications
Model
RTX3110KL
RTX3115KL
RTX3120KL
Rated Power
10kVA/9kW
15kVA/13.5kW
20kVA/18kW
INPUT
Voltage Range
207-475Vac3P4W+G
Working Frequency Range
40-70HZ (settable)
Input Power Factor
>0.95
OUTPUT
Rated Voltage and Accuracy
220Vac(l±l%)lP2W+G
Output Frequency
46-54Hz synchronize with mains power; 50Hz (Mains power between 40-46Hz and 54-60Hz); 50Hz(Battery)
Rated Current
45A
68A
91A
Output Power Factor
0.9
Output Harmonic Wave
W3%
Crest Factor
3:1
Output Overload
105%±5%<Load≤125%±5%: Convert to bypass output and alarm after 1 min;
125%±5%<Load ≤50%±5%: Convert to bypass output and alarm after 30s;
Load>150%±5%: Convert to bypass output and alarm after 300ms.