50/60 Hz synchronised ±1 % With mains absent ±0.1 Hz
Max. Synchronisation Speed
±1 Hz/s
Waveform
Pure Sinewave
Total Harmonic Distortion (THDv)
<2% (Linear Load) ; <5% (Non-linear Load)
Phase Displacement
120° ±1 % (balanced load); 120° ±2% (imbalances 50% of the load)
Dynamic Recovery Time
Restore to 90% of rated value in 3 cycles
Overload capacity
110% for 10min; 150% for 60sec; >160% for 200ms
Admissible Crest Factor
3:1
Admissible Power Factor
0.6-1 (inductive or capacitive)
Imbalance Output Voltage @ 100% Unbalanced Load
<1%
Current Limit
High overload, short-circuit: RMS Voltage Limit; High Crest-Factor current: Peak Voltage Limit
STATIC BYPASS
Type
Solid state
Voltage
3 x 380VAC/400VAC (3Ph + N)
Frequency
50/60 Hz
Activation Criterion
Microprocessor control
Transfer Time
Zero
Admissible Overload
150% for 1 hour; 180% for 30sec; >200% for 200ms
Transfer to Bypass
Immediate, for overloads above 160%
Retransfer
Automatic after alarm clear
MAINTENANCE BYPASS
Type
Without interruption
Voltage
3 * 400V (3Ph + N)
Frequency
50/60 Hz
Overall Efficiency
Line Mode
90%
91%
92%
93%
Battery Mode
90%
91%
93%
93%
BATTERY & CHARGER
Battery Type and Numbers
12VDC * 32 pcs (29-32 pcs adjustable)
Nominal Battery Voltage
384 VDC (Based on 32pcs batteries)
Charging Method
CC/CV
Precision
±1%
Charging Current
Max.: 40 A
Charging Voltage
432 VDC (Based on 32pcs batteries)
PHYSICAL
Dimensions, D x W x H(mm)
656 x 405 x 817
656 x 405 x 941
840x432x1140
975x554x1286
1200x910x1680
1500x1140x1800
Net Weight (Kgs)
180
205
295
330
451
519
950
1350
Features:
Rated Power: 500W
Rated Capacity: 519 . 48wh
Standard Capacity: 3.7V/140400mah
Overload Protecion: 550W + 40W
AC Output: AC 110V+10%/60HZ 230V+10%/50HZ
Output Wave: Pure sine wave
USB Output: QC 18W*2
Type-c Output: PD 60W*2
Cigarret Lighter Output: 14V/8A
DC5525 Output: 14V/8A
Wireless Charging: 15W
Charging Input: 12-26 V/100W Max
WorkingTemperature: -10-40 °C
Weight(Net Weight): 6.8kg
Weight(With Accessories): 8.5kg
Dimension: 345*227*203mm
Applications:
Mammogram
Ultrasound Equipments
Radiology rooms
Features:
Capacity: 1200W 1008Wh /315000mAh
Input AC Output Power:Rated Power 1200W Peak Power 2400W
Input AC Charging:AC100~125V/AC184~264V Bidirectional Inverter 700W Max
Input Car Charging:DC12V~24V/10A 240W Max
Input Solar Charging:DC12V~60V/10A 400W Max
Output Voltage:230VAC±10%/110VAC±10%
Output Frequency: 50Hz±5%/60Hz±5%
USB Output:2*5V2.4A +2*QC18W+2*PD60W Max
DC Output:1*Cigarette Lighter+2*DC5521 Rated Output (13.8V/10A Max)
Output Waveform:Pure Sine Wave
LED:3 Levels(H/M/L)+SOS
UPS Function:Support(≤10mS)
Applications:
Mammogram
Ultrasound Equipments
Radiology rooms
Features:
Intelligent CPU control
Automatic power on when the the main power recovers
Cold start function
Power off charging function
USB/RS232/RJ-11/RJ-45 communication port (optional)
Offering LED and LCD panels for selection
Application:
Personal Computer
Printer
POS(Point of sales)Terminals
Security System
Fax Machine
Modem, WiFi Router
Technical Specifications:
Model
DP600
DP1000
DP1200
DP2000
DP3000
Capacity
600VA/360W
1000VA/600W
1200VA/720W
2000VA/1200W
3000VA/1800W
INPUT
Voltage
110/120VAA or 220/230/240VAC
Voltage Range
67-137VAC/135-275VAC
Frequency Range
50Hz Or 60Hz(Auto-Sensing)
OUTPUT
Output Voltage
110/120VAA or 220/230/240VAC
AC Voltage Regulation
± 10%
Frequency Range
(Batt. Mode)
50 HZ or 60 Hz ± 10%
Transfer Time
Typical 6-10 ms
Waveform
(Battery Mode)
Simulated Sine Wave
BATTERY
Battery Voltage
12V/7AH*1
12V/9AH*1
12V/7AH*2
12V/9AH*2
12V/7AH*4
Charge Time
8 hours up to 80-90%
PROTECTION
Full Protection
Auto Detection, discharge protection,output Short circuit, Over load, Battery low voltage protection
Communication Port
USB/RS232/RJ11/RJ45 (Optional)
Display
LED/LCD
Alarm
Battery Mode
Every 4 Seconds one beep
Low Battery Capacity
Every 1 Seconds one beep
Overload
Every 1 Seconds one beep
Fault
Keep beeping
ENVIRONMENT
Humidity
0-90% Rh @ 0-40℃ (Non-Condensing)
Noise Level
40dB
Dimension(mm)
320*90*140
330* 100*150
365*140*165
365*140*165
395*145*210
N.W.(kg)
5.2
6
10
12.6
21
Description
HIGH INTELLIGENCE AND RELIABLE POWER SUPPLYIGBT Technology
Full microprocessor control with no-break static and manual bypasses.
Online double conversion technology (VFl) with isolation transformer on theinverter output.
Extremely high short-circuit current to ensure compatibility with the most diffificult transformer applications (lighting, drives and industrial processes) and an isolation transformer on the inverter output.
Compatibled with Watch & Save 3000 software as standard and can be remotely monitored using the Power NetGuard system from anywhere in the world.
SIMPLE TO INSTALL
Capability to install the UPS into any distribution system(neutral not required on rectifier input).
Capability to separate the rectifier/bypass power networks and to power them from two separate sources, without Galvanic isolation(Necessary on UPS without an output transformer
MAXIMUM BATTERY CARE
Battery deep discharge protection;
Temperature compensating charger;
Built-in automatic and manual battery test feature.
OTHER CHARACTERISTICS
0.8/0.9 power factor suitable for powering ICT and lndustrial loads.
BACK FEED protection: to avoid energy feeding back into the mains supply cause a fault occur.
MAXIMUM RELIABILITY AND AVAILABILITY
Connect up to 6 units in parallel or N+1 redundancy, even of different power ratings.
The UPS continue to work in parallel even if one of theinterconnecting communication cables is disconnected(CLOSED LOOP)
LOW CONSUMPTION LEVELS
LF33 Series UPS can achieve efficiencies >98% thanks to selectable Economy Mode which can be used in stable electrical environments to provide power supply continuity when the mains fail.
ADVANCE COMMUNICATION:
RS485/RS232/Dry Contact/SNMP(Optional)
Specifications
Model
10KVA
20KVA
30KVA
40KVA
60KVA
80KVA
100KVA
120KVA
160KVA
200KVA
250KVA
300KVA
400KVA
500KVA
600KVA
Capacity
8KW
16 KW
24 KW
32 KW
48 KW
64 KW
80 KW
96 KW
128 KW
160 KW
200KW
240KW
320KW
400KW
480KW
INPUT
Rated voltage
400 VAC Three-Phase
Voltage range
380/400/415VAC(+25%,Can be set through the LCD panel)
Frequency range
40-70Hz(Automatically select synchronization range according to grid frequency)
Range(HZ)
50±5%(±10%) Bypass synchronization tracking
Rectifying pulse number
6 pulse rectification
6/12 pulse rectification
12 pulse rectifier
Phase system
3φ4W+PE(Three phase five wire system)
Battery voltage
384VDC
480VDC
Battery Quantity
Standard with 32 Cells(30~34, can be set through the LCD panel) Standard 40 Cells(38~42 knots,can be set by LCD panel)
OUTPUT
Power factor
0.8/0.9 (Optional)
Voltage(V)
L-N: 220±1% L-L: 380±1%
Three-phase 100% load
unbalance voltage stability
≤2%,Allow 100% imbalance
Frequency(HZ)
Normal power, tracking the frequency of power, Grid abnormal. 50±0.2%
Transfer time(ms)
0ms
Parallel operation mode
(parallel type)
Max 8 Parallel
Waveform distortion
Linear loadTHD<3% ; Nonlinear loadTHD<5%
Overload capacity
125% full load for 10 minutes, maintain 150 % full load for 1 minute and then switch to bypass power supply,
after reducing the loadcan automatically restore the inverter
Crest factor
3:1
Others
Index
Standard with no transfer time maintenance bypass switch
Communication function
RS232/RS485/Dry Contact/SNMP (Optional)
Panel display
LED displays working status and fault indication; LCD displays three-phase input voltage,
input frequency, three-phase output voltage, load,battery voltage, battery charge and discharge current, etc
Display
7″ Touchable LCD screen display
The audio noise(dB)
<65(within 1 meter)
Alarm function
Battery low voltage, abnormal power supply, overload, UPS failure, over temperature protection
Protection
Input over voltage, battery under voltage, overload, short circuit, over temperature protection
Reviews